Plan Review Notes
Plan Review Notes For Permit 07050876
Permit Number 07050876
Review Stop P
Sequence Number 1
Notes
Date Text
2007-07-02 11:30:54DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 BUILDING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. SHTS LA1, LA2, LA3, IR1, IR2, IR3 & TP1. THE LICENSE
 NUMBER FOR ANTHONY J. VIERS IS INDICATED ON THE FLORIDA
 STATE DBPR WEBSITE AS LA6666830, BUT IS INDICATED ON
 THE TITLE BLOCKS AS LA666830. PLEASE UPDATE THE DBPR
 WEBSITE OR TITLE BLOCKS PRIOR TO RESUBMITTING SO
 LICENSE NUMBER ON THE TITLE BLOCKS AND DBPR WEBSITE
 CORRELATE. FAC 61G1-16.004(2) & FS 481.219, 481.2055.
 (SEE ATTACHED SHEET).
  
 2. ALL ARCHITECTURAL SHEETS. NAME OF ARCHITECTURAL FIRM
 & FIRM LICENSE NUMBER DO NOT REFLECT WHAT IS ON FILE AT
 THE FLORIDA STATE DBPR WEBSITE. PLEASE UPDATE THE DBPR
 WEBSITE OR THE TITLE BLOCKS PRIOR TO RESUBMITTING SO
 THE NAME AND THE LICENSE NUMBER ON THE TITLE BLOCKS AND
 DBPR WEBSITE CORRELATE. FAC 61G1-16.004(1)(2) & FS
 481.2055. (SEE ATTACHED SHEET).
  
 3. PLANS SHALL CONTAIN THE ORIGINAL SIGNATURE FOR ALL
 ARCHITECTURAL SHEETS. PHOTO COPIES AND/OR SIGNATURE
 STAMPS ARE NOT APPROVED. FAC 61G1-16.003,
 61G1-16.004(5) & FS 481.2055.
  
 4. SHT A200 THE DRINKING FOUNTAIN IS REQUIRED PER TABLE
 403.1 MINIMUM PLUMBING FACILITIES AND AS SUCH SHALL BE
 ACCESSIBLE TO THE CUSTOMERS, PATRONS AND VISITORS. THE
 DRINKING FOUNTAIN LOCATED BY THE LOUNGE, (ROOM 108),
 DOES NOT AFFORD ACCESS BY THE CUSTOMERS, PATRONS OR
 VISITORS. PLEASE LOCATE THE DRINKING FOUNTAIN TO MAKE
 IT ACCESSIBLE SO THE CUSTOMERS MAY USE THE REQUIRED
 FIXTURE.
  
 5. SHT A200 THE ADDRESS FOR THE JOB ON THE TITLE BLOCK
 IS NOT CORRECT. (2648 N.W. FEDERAL HWY. STUART
 FLORIDA). PLEASE SHOW CORRECT ADDRESS. FAC
 61G1-16.004(1) AND FS 481.2055.
  
 6. SHTS A202, A203 & A204 SUBMIT CALCULATIONS FOR
 PRIMARY AND SECONDARY ROOF DRAINS FOR ALL ROOFS.
 INDICATE AREA DRAINING INTO EACH ROOF DRAIN, PLUS SHOW
 1/2 AREA OF ALL VERTICAL WALLS, INCLUDING PARAPETS
 ADDED TO ROOF AREAS IN THE CALCULATIONS. SECTIONS 1106
 & 1107 WITH ALL SUBSECTIONS & TABLES.
  
 7. SHT A510 PER SECTION 1210.2 WALLS WITHIN 2FT OF
 W/C'S SHALL HAVE A "SMOOTH, HARD, NONABSORBENT"
 SURFACE. SHEET A900 INDICATES WF-1 TO BE VINAL WALL
 COVERING. THIS DOES NOT MEET THE REQUIREMENT FOR A
 "HARD SURFACE" PLEASE SHOW A MATERIAL TO MEET THIS
 REQUIREMENT ON THE FINISH SCHEDULE.
  
 8. SHT A944 DETAIL 5. THE SINK SHALL BE ACCESSIBLE.
 SHOW COMPLIANCE WITH THE FOLLOWING:
 A. 11-4.24.3 KNEE CLEARANCE
 B. 11-4.24.4 SINK DEPTH
 C. 11-4.24.5 CLEAR FLOOR SPACE (FORWARD APPROACH
 REQUIRED. CABINET DOORS NOT ALLOWED).
 D. 11-4.24.6 EXPOSED PIPES & SURFACES
 E. 11-4.24.7 FAUCETS
  
 9. ALL STRUCTURAL SHEETS. THE SEAL USED BY THE
 STRUCTURALENGINEER IS NOT APPROVED. (SEE ATTACHED
 SHEET FROM THE FLORIDA BOARD OF PROFESSIONAL
 ENGINEERS).
  
 10. ALL P.M.E. SHEETS. THE DATE THE SIGNATURE & SEAL
 ARE AFFIXED TO THE PLANS SHALL BE INDICATED UNDER THE
 SIGNATURE. FAC 61G15-23.002(1) & FS 471.025.
  
 11. SHTS P-101 & P-102 PLANS SHALL BE DRAWN TO A
 MINIMUM OF 1/8"/FT SCALE PER SECTION 106.1.3. SHTS
 INDICATE SCALE "AS NOTED", BUT SCALE IS NOT NOTED.
 PLEASE INDICATE THE SCALE OF THE PLANS AS REQUIRED.
  
 12. THERMAL EXPANSION CONTROL IS REQUIRED PER SECTION
 607.3.2. PLEASE INDICATE METHOD.
  
 13. SHT P-104 THE DOMESTIC WATER RISER DIAGRAM DOES NOT
 REFLECT THE FLOOR PLAN AT THE PANTRY SINK/DRINKING
 FOUNTAIN AREA. PLEASE CORRELATE INFORMATION ON THE
 FLOOR PLAN AND THE RISER DIAGRAM. SECTION 106.1.1.
  
 14. SHT P-104 THE SANITARY RISER DIAGRAM DOES NOT
 REFLECT THE FLOOR PLAN FOR THE VENTING IN THE TOILET
 ROOMS AND AT THE MOP SINK. THE FLOOR PLAN SHOWS TWO
 VTR'S AT THE LAVS, AND THE RISER DIAGRAM SHOWS ONE VTR
 AT THE MOP SINK. PLEASE CORRELATE. SECTION 106.1.1.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID
 SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY
 ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved