| 2007-06-21 19:16:38 | -----------------DENIED---------------------- |
| | |
| | 1. PLEASE PROVIDE DETAIL DRAWINGS SHOWING HOW ROOF |
| | CURBS ARE TO BE ATTACHED TO THE BUILDING STRUCTURE |
| | MEETING THE MIND LOAD REQUIREMENTS OF FBC 1609. |
| | |
| | 2. PLEASE CLARIFY THE "EQUIPMENT TIE-DOWN DETAIL." |
| | THERE ARE TWO DRAWINGS THERE. ARE BOTH TYPES OF |
| | TIE-DOWNS REQUIRED OR IS IT "EITHER-OR?" ALSO, PLEASE |
| | STATE THE DESIGN WIND SPEED FOR ANY ENGINEERED ASSEMBLY |
| | DESIGNED TO SECURE OUTDOOR EQUIPMENT. FBC 106.1.2. |
| | NOTE: STRAPS OR CABLES SHALL NOT BE INSTALLED FOR WIND |
| | RESISTANCE WHICH WILL INTERFERE WITH THE SERVICE ACCESS |
| | OF ROOFTOP EQUIPMENT. FBC,M 306.1. |
| | |
| | 3. BY WHAT MEANS ARE THE ROOFTOP CONDENSING UNITS TO BE |
| | SUPPORTED/SECURED TO THE ROOF? PLEASE CLARIFY PER FBC |
| | 106.1.1. |
| | NOTE: PRE-ENGINEERED A/C STANDS ARE STRUCTURAL |
| | COMPONENTS AND AS SUCH ARE SUBJECT TO THE FLORIDA |
| | PRODUCT APPROVAL SYSTEM. FAC 9B-72 |
| | |
| | 4. PLEASE SHOW LOCATION OF CONDENSATE DISPOSAL TO BE IN |
| | AN APPROVED LOCATION (NOT IN SANITARY) PER FBC,M |
| | 307.2.1. ALSO, SHOW MEANS OF SECONDARY OR AUXILIARY |
| | DRAIN PROTECTION ON ROOFTOP PACKAGE UNITS PER FBC,M |
| | 307.2.3. |
| | |
| | 5. THE DUCT SMOKE DETECTORS SHALL BE CONNECTED TO A |
| | FIRE ALARM SYSTEM. THE ACTUATION OF A DUCT SMOKE |
| | DETECTOR SHALL ACTIVATE A VISIBLE AND AUDIBLE |
| | SUPERVISORY SIGNAL AT A CONSTANTLY ATTENDED LOCATION. |
| | EXCEPTIONS: |
| | 1) THE SUPERVISORY SIGNAL AT A CONSTANTLY ATTENDED |
| | LOCATION IS NOT REQUIRED WHERE THE DUCT SMOKE DETECTOR |
| | ACTIVATES THE BUILDING=S ALARM-INDICATING APPLIANCES. |
| | 2) IN OCCUPANCIES NOT REQUIRED TO BE EQUIPPED WITH A |
| | FIRE ALARM SYSTEM, ACTUATION OF A SMOKE DETECTOR SHALL |
| | ACTIVATE A VISIBLE AND AN AUDIBLE SIGNAL (HORN AND |
| | STROBE) IN AN APPROVED LOCATION. DUCT SMOKE DETECTOR |
| | TROUBLE CONDITIONS SHALL ACTIVATE A VISIBLE OR AUDIBLE |
| | SIGNAL IN AN APPROVED LOCATION AND SHALL BE IDENTIFIED |
| | AS AIR DUCT DETECTOR TROUBLE. |
| | FBC 606.4.1 |
| | |