Plan Review Notes
Plan Review Notes For Permit 07050876
Permit Number 07050876
Review Stop M
Sequence Number 1
Notes
Date Text
2007-06-21 19:16:38-----------------DENIED----------------------
  
 1. PLEASE PROVIDE DETAIL DRAWINGS SHOWING HOW ROOF
 CURBS ARE TO BE ATTACHED TO THE BUILDING STRUCTURE
 MEETING THE MIND LOAD REQUIREMENTS OF FBC 1609.
  
 2. PLEASE CLARIFY THE "EQUIPMENT TIE-DOWN DETAIL."
 THERE ARE TWO DRAWINGS THERE. ARE BOTH TYPES OF
 TIE-DOWNS REQUIRED OR IS IT "EITHER-OR?" ALSO, PLEASE
 STATE THE DESIGN WIND SPEED FOR ANY ENGINEERED ASSEMBLY
 DESIGNED TO SECURE OUTDOOR EQUIPMENT. FBC 106.1.2.
 NOTE: STRAPS OR CABLES SHALL NOT BE INSTALLED FOR WIND
 RESISTANCE WHICH WILL INTERFERE WITH THE SERVICE ACCESS
 OF ROOFTOP EQUIPMENT. FBC,M 306.1.
  
 3. BY WHAT MEANS ARE THE ROOFTOP CONDENSING UNITS TO BE
 SUPPORTED/SECURED TO THE ROOF? PLEASE CLARIFY PER FBC
 106.1.1.
 NOTE: PRE-ENGINEERED A/C STANDS ARE STRUCTURAL
 COMPONENTS AND AS SUCH ARE SUBJECT TO THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FAC 9B-72
  
 4. PLEASE SHOW LOCATION OF CONDENSATE DISPOSAL TO BE IN
 AN APPROVED LOCATION (NOT IN SANITARY) PER FBC,M
 307.2.1. ALSO, SHOW MEANS OF SECONDARY OR AUXILIARY
 DRAIN PROTECTION ON ROOFTOP PACKAGE UNITS PER FBC,M
 307.2.3.
  
 5. THE DUCT SMOKE DETECTORS SHALL BE CONNECTED TO A
 FIRE ALARM SYSTEM. THE ACTUATION OF A DUCT SMOKE
 DETECTOR SHALL ACTIVATE A VISIBLE AND AUDIBLE
 SUPERVISORY SIGNAL AT A CONSTANTLY ATTENDED LOCATION.
 EXCEPTIONS:
 1) THE SUPERVISORY SIGNAL AT A CONSTANTLY ATTENDED
 LOCATION IS NOT REQUIRED WHERE THE DUCT SMOKE DETECTOR
 ACTIVATES THE BUILDING=S ALARM-INDICATING APPLIANCES.
 2) IN OCCUPANCIES NOT REQUIRED TO BE EQUIPPED WITH A
 FIRE ALARM SYSTEM, ACTUATION OF A SMOKE DETECTOR SHALL
 ACTIVATE A VISIBLE AND AN AUDIBLE SIGNAL (HORN AND
 STROBE) IN AN APPROVED LOCATION. DUCT SMOKE DETECTOR
 TROUBLE CONDITIONS SHALL ACTIVATE A VISIBLE OR AUDIBLE
 SIGNAL IN AN APPROVED LOCATION AND SHALL BE IDENTIFIED
 AS AIR DUCT DETECTOR TROUBLE.
 FBC 606.4.1
  