| Date |
Text |
| 2007-07-31 12:04:14 | ***DENIED*** |
| | |
| | 1) IN ADDITION TO FLORIDA FIRE PREVENTION CODE, LIFE |
| | SAFETY TO COMPLY WITH NFPA 101, 2003 EDITION. |
| | |
| | 2) CONSTRUCTION, ALTERATION AND DEMOLITION TO COMPLY |
| | WITH NFPA 241. |
| | |
| | 3) NO COMBUSTIBLES PERMITTED ABOVE CEILING IF BEING |
| | USED AS RETURN AIR PLENUM. |
| | |
| | 4) ADDRESS REQUIRED ON BUILDING THAT SHALL BE MINIMUM |
| | OF 6" IN HEIGHT AND CONTRASTING TO BACKGROUND. |
| | |
| | 5) PLEASE ADVISE IF BUILDING WILL BE PROTECTED BY |
| | AUTOMATIC FIRE SPRINKLER AND OR FIRE ALARM SYSTEMS. |
| | (SHT A-400 NOTE C AND I) |
| | |
| | 6) PLEASE SEE OTHER REVIEW COMMENTS REGARDING FS AND |
| | FAC REQUIREMENTS FOR PLANS. |
| | |
| | 7) EXIT DOORS TO COMPLY WITH NFPA 101, SEC. 7.2.1.5. |
| | REGARDING LOCKING ARRANGEMENTS. |
| | |
| | 8) WHAT ARRANGEMENT IS PROVIDED FOR EMERGENCY ACCESS |
| | INTO BUILDING AFTER NORMAL BUSINESS HOURS? |
| | |
| | 9) CONFLICTING INFORMATION EXISTS ON PLANS REGARDING |
| | THE INSTALLATION OF FIRE DAMPERS. WHERE PROVIDED, |
| | DAMPERS TO BE TESTED FOR CLOSURE IN ACCORDANCE WITH UL |
| | 555 PRIOR TO FINAL INSPECTION. |
| | |
| | 10) IF FIRE PROTECTION SYSTEMS ARE PLANNED FOR THIS |
| | PROJECT, A SYSTEM LAYOUT IS REQUIRED WITH SUBMITTAL FOR |
| | PERMIT. SEPARATE SHOP DRAWINGS AND PERMITS WILL BE |
| | REQUIRED PRIOR TO INSTALLATION. |
| | |
| | |
| | MIKE WENNERGREN, ASSISTANT FIRE MARSHAL |
| | FIRE PLAN REVIEW |
| | FIRE PREVENTION (561) 804-4756 |