Plan Review Notes
Plan Review Notes For Permit 07050876
Permit Number 07050876
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2007-07-31 12:04:14***DENIED***
  
 1) IN ADDITION TO FLORIDA FIRE PREVENTION CODE, LIFE
 SAFETY TO COMPLY WITH NFPA 101, 2003 EDITION.
  
 2) CONSTRUCTION, ALTERATION AND DEMOLITION TO COMPLY
 WITH NFPA 241.
  
 3) NO COMBUSTIBLES PERMITTED ABOVE CEILING IF BEING
 USED AS RETURN AIR PLENUM.
  
 4) ADDRESS REQUIRED ON BUILDING THAT SHALL BE MINIMUM
 OF 6" IN HEIGHT AND CONTRASTING TO BACKGROUND.
  
 5) PLEASE ADVISE IF BUILDING WILL BE PROTECTED BY
 AUTOMATIC FIRE SPRINKLER AND OR FIRE ALARM SYSTEMS.
 (SHT A-400 NOTE C AND I)
  
 6) PLEASE SEE OTHER REVIEW COMMENTS REGARDING FS AND
 FAC REQUIREMENTS FOR PLANS.
  
 7) EXIT DOORS TO COMPLY WITH NFPA 101, SEC. 7.2.1.5.
 REGARDING LOCKING ARRANGEMENTS.
  
 8) WHAT ARRANGEMENT IS PROVIDED FOR EMERGENCY ACCESS
 INTO BUILDING AFTER NORMAL BUSINESS HOURS?
  
 9) CONFLICTING INFORMATION EXISTS ON PLANS REGARDING
 THE INSTALLATION OF FIRE DAMPERS. WHERE PROVIDED,
 DAMPERS TO BE TESTED FOR CLOSURE IN ACCORDANCE WITH UL
 555 PRIOR TO FINAL INSPECTION.
  
 10) IF FIRE PROTECTION SYSTEMS ARE PLANNED FOR THIS
 PROJECT, A SYSTEM LAYOUT IS REQUIRED WITH SUBMITTAL FOR
 PERMIT. SEPARATE SHOP DRAWINGS AND PERMITS WILL BE
 REQUIRED PRIOR TO INSTALLATION.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756