Plan Review Notes
Plan Review Notes For Permit 07050876
Permit Number 07050876
Review Stop E
Sequence Number 1
Notes
Date Text
2007-06-23 15:43:03*** UNSAT ***
  
  
  
 1) NOTE: PLEASE SEE THIS PROPOSED WORK FOR NEW BANK HAS
 NOT BEEN SUBMITTED FOR PERMIT AND HAS ONLY BEEN
 SUBMITTED FOR * PLAN REVIEW ONLY *. PLEASE KNOW EVEN
 WHEN PLANS ARE CODE COMPLIANT THE REVIEW STATUS WILL
 STILL BE *FAILED* AS LICENSING, PERMIT APPLICATIONS,
 VALUATION ETC IS VERIFIED AT TIME OF ISSUANCE.
  
 2) NOTE:PLEASE KNOW THAT ANY PERMIT APPLICATIONS
 WHICH ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES
 PROJECTS UNDER THE NEW CODES ADOPTED BY THE STATE.
 PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO
 THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70.
 PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY
 AFFECT DESIGNS FOR ALL TRADES.
 PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS
 REVIEWER AT A MINIMUM.
 2004 FBC W/ 2006 REVISIONS
 2005 NFPA-70
 2002 NFPA-72
 2003 NFPA-101
  
 ** PLEASE SEE THERE ARE SEVERAL CODES ON SEVERAL SHEETS
 WHICH DO NOT APPLY TO PROJECT IN THIS STATE. PLEASE
 REMOVE.
  
 ** PLEASE KNOW THAT CHANGES FOR NEW CODES IS REQUIRED
 FOR ALL TRADES AND FOR ALL REVIEWS EVEN IF COMMENT IS
 NOT MADE BY OTHER TRADE(S).
  
 3) NOTE PLEASE SEE THE PLANS MUST CONTAIN AN ORIGINAL
 SIGNATURE FOR ALL DESIGNERS. PLEASE SEE THE
 ARCHITECTURAL SHEETS WHICH DO NOT CONTAIN AN ORIGINAL
 SIGNATURE FROM ARCHITECT. SHEETS IN FACT CONTAIN A
 RAISED SEAL OVER PHOTO-COPIED SIGNATURE/PRINTED. PLEASE
 SEE FS 481.221, FAC 61G1-16.004.
 ** THIS IS REQUIRED FOR ALL SHEETS AND TRADES WHETHER
 OR NOT COMMENT IS MADE BY OTHER TRADE(S).
  
 4) NOTE: PLEASE SEE THE *S* SHEETS WHICH CONTAIN A SEAL
 WHICH IS NO LONGER VALID IN THE STATE OF FLORIDA.
 PLEASE SEE RULING61G15-23.001 AS OF FEBRUARY 04,
 WHICH REQUIRES ALL ENGINEERS TO OBTAIN A SEAL WITH THE
 WORDING OF ?LICENSE? AND THE WORDING OF *CERTIFICATE*
 COULD NOT LONGER BE USED. AN EXTENSION WAS GRANTED ONLY
 TO DECEMBER 31ST, 2005.
 PLEASE OBTAIN NEW SEAL. THIS COMMENT IS REQUIRED
 WHETHER OR NOT COMMENT IS MADE BY OTHER TRADE(S).
  
 5) NOTE: PLEASE SEE FAC 61G1-16.004 FOR MISSING
 INFORMATION ON TITLE BLOCK FOR ARCHITECTURAL FIRM.
 PLEASE SEE THE LICENSE NUMBER AS PRINTED FOR THE
 CERTIFICATE OF AUTHORIZATION NUMBER IS NOT CORRECT.
 PLEASE SEE A DIGIT IS MISSING AS LISTED ON THE STATE
 WEBSITE. PLEASE SEE DEPARTMENT OF BUSINESS AND
 PROFESSIONAL REGULATION PRINT OUT ATTACHED TO NOTES. **
 REQUIRED FOR ALL SHEETS WHICH CONTAIN THIS TITLE BLOCK
 WHETHER OR NOT COMMENT IS MADE BY OTHER TRADE(S).
  
 6)NOTE: PLEASE SEE THE ENERGY CALCULATIONS CAN NOT BE
 VERIFIED AT THIS TIME AS THE PLANS DO NOT CONTAIN ANY
 FIXTURE LEGEND AND COORDINATION OF LABELING OF FIXTURES
 STILL NEEDS TO BE DONE.
 PLEASE SEE 13-415.2.ABC.1.2 FOR TRACK LIGHTING. PLEASE
 SEE SOME SEPARATE SPACES ARE MISSING THE REQUIRED
 CONTROLS.
 PLEASE SEE NO TIMES FOR THE OVER RIDE DEVICES COULD BE
 LOCATED.
 PLEASE SEE SOME OVER RIDE DEVICE LOCATIONS COULD NOT BE
 FOUND ON PLANS AS REQUIRED.
 PLEASE SEE THE DESIGN WATTS ON ENERGY CALCULATIONS
 SHEET 5 DOES NOT CORRELATE WITH THE DESIGN WATTS ON
 SHEET 2.
 PLEASE SEE THE SQ FT AS SHOWN CALCULATIONS ON ONE PART
 IS NOTED AS 84,000 SQ FT?
 PLEASE SEE THE SHEET 2 ON ENERGY CALCULATIONS MUST BE
 SIGNED BY OWNER AGENT.
 PLEASE SEE 13-103.1.1.1, 13-415.1.ABC.1.1, .1.2 AND
 .1.3, 13-415.1.AB.1.1, 13-415.2 ETC
 PLEASE PROVIDE WORST CASE VOLTAGE DROP FOR FEEDER(S)
 AND BRANCH CIRCUIT(S).
 PLEASE SEE 13-413.1ABC.1
  
 7) NOTE: PLEASE PROVIDE MORE INFORMATION FOR MAIN.
 PLEASE SEE THE MAIN WHICH CONTAIN THE MANUAL MEANS OF
 DISCONNECT RATED FOR THE LOAD SERVED PER 230.76 AND
 230.79 SHALL BE INSTALLED AT A LOCATION WHICH HAS READY
 ACCESS. AS SHOWN ON PLANS THE MAIN IS LOCATED A
 DISTANCE IN THE BUILDING AND BEHIND SEVERAL LOCKED
 DOORS. PLEASE SEE THIS IS A LIFE SAFETY AND PROPERTY
 HAZARD IN ORDER FOR THE FIRE DEPARTMENT OR ANY OTHER
 PERSON NEEDING TO SHUT OFF POWER TO BUILDING. THE USE
 OF A SHUNT TRIP LOCATED OUTSIDE IS NOT PERMITTED AS IT
 DOES NOT MEET THE ABOVE CODE SECTIONS.
 PLEASE SEE A DIRECT ACCESS TO MAIN ELECTRICAL ROOM FROM
 OUTSIDE OR SOME OTHER MEANS TO ACCESS MAIN WILL BE
 REQUIRED. THIS WAS CONFIRMED WITH THE FIRE MARSHALS
 OFFICE.
 230.70, 230.71, 230.72 ETC.
  
 8) NOTE: PLEASE PROVIDE THE MANUFACTURES SPECS/CUT
 SHEETS FOR THE NEW PROPOSED MTS. 90.7, 110.3.
 FBC 106.1.2
  
 9) NOTE: PLEASE SEE THE PLANS SEEM TO CONTAIN MANY
 AREAS IN WHICH THERE IS INFORMATION PRINTED IN *LT
 GRAY* AND NOT EASILY READ. PLEASE SEE ELECTRICAL
 SHEETS.
  
 10) NOTE: PLEASE KNOW THE LOW VOLTAGE WORK SHOWN ON
 PLANS WILL BE REQUIRED TO BE UNDER SEPARATE PERMITS.
 THESE PLANS MAY BE USED AS A REFERENCE FOR A
 *TURN-AROUND* PERMIT HOWEVER SEPARATE FEES WILL BE DUE
 FOR THIS SCOPE OF WORK.
 PLEASE SEE THE LOW VOLTAGE PERMIT FOR ANY SECURITY,
 FIRE ALARM AND FIRE SPRINKLER SYSTEMS WILL BE UNDER
 SEPARATE PERMITS.
  
 11) NOTE: PLEASE SEE IF THERE ARE ANY FIRE ALARMS
 SYSTEMS REQUIRED OR INSTALLED EVEN IF UNDER SEPARATE
 PERMITS THE MINIMUM LEVELS FOR ADA COMPLIANCE NEEDS TO
 BE ON PLANS.
 PLEASE SEE FBC 11-4.28.1,. AND .3(4) FOR MINIMUM LEVELS
 TO BE STATED ON BASE PLANS.
  
 12) NOTE: PLEASE PROVIDE ANY SITE LIGHTING ELECTRICAL
 DETAILS. PLEASE PROVIDE MINIMUM WIND LOAD INFORMATION
 FOR POLES.
 PLEASE KNOW THESE MAY BE UNDER A SEPARATE PERMIT AT A
 LATER DATE.
 FBC 106.1.2, 106.3
  
 13) NOTE: PLEASE SEE THE COLOR CODING EVEN THOUGH NOT
 APPLICABLE IN THIS SERVICE SITUATION FOR 277/480V IS
 BROWN, PURPLE, AND YELLOW.
 THIS DOES NOT NEED TO BE CHANGED, AND WILL BE
 REDLINED.
  
 14) NOTE: PLEASE CONTACT THE LOCAL POLICE DEPARTMENT AS
 THERE IS LOCAL ORDINANCE WHICH REQUIRES MINIMUM
 LIGHTING LEVELS FOR ATM MACHINES/DRIVE UP AREAS OF
 BANKS.
 THIS WILL AFFECT THE ELECTRICAL SITE LIGHTING PLANS
 NOT YET SUBMITTED.
  
  
 ** PLEASE KNOW AS THERE ARE SOME ITEMS NOT YET
 SUBMITTED FOR REVIEW AND THE CHANGES WHICH WILL BE
 NEEDED FOR SERVICE A COMPLETE REVIEW CAN NOT BE DONE AT
 THIS TIME.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
 ** PLEASE SEE ANY POSSIBLE COMMENTS FROM OTHER TRADES
 WHICH MAY AFFECT ELECTRICAL PLANS.
2007-06-23 14:55:172007-06-23 14:55:17
 REIVEW IN PROGRESS.
2007-06-22 19:35:452007-06-22 19:35:45
 REVIEW TO CONTINUE AND NOTES TO FOLLOW.
2007-06-22 18:46:442007-06-22 18:46:44
 IN ELEC FOR REVIEW.