| 2007-06-23 15:43:03 | *** UNSAT *** |
| | |
| | |
| | |
| | 1) NOTE: PLEASE SEE THIS PROPOSED WORK FOR NEW BANK HAS |
| | NOT BEEN SUBMITTED FOR PERMIT AND HAS ONLY BEEN |
| | SUBMITTED FOR * PLAN REVIEW ONLY *. PLEASE KNOW EVEN |
| | WHEN PLANS ARE CODE COMPLIANT THE REVIEW STATUS WILL |
| | STILL BE *FAILED* AS LICENSING, PERMIT APPLICATIONS, |
| | VALUATION ETC IS VERIFIED AT TIME OF ISSUANCE. |
| | |
| | 2) NOTE:PLEASE KNOW THAT ANY PERMIT APPLICATIONS |
| | WHICH ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES |
| | PROJECTS UNDER THE NEW CODES ADOPTED BY THE STATE. |
| | PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO |
| | THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70. |
| | PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY |
| | AFFECT DESIGNS FOR ALL TRADES. |
| | PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS |
| | REVIEWER AT A MINIMUM. |
| | 2004 FBC W/ 2006 REVISIONS |
| | 2005 NFPA-70 |
| | 2002 NFPA-72 |
| | 2003 NFPA-101 |
| | |
| | ** PLEASE SEE THERE ARE SEVERAL CODES ON SEVERAL SHEETS |
| | WHICH DO NOT APPLY TO PROJECT IN THIS STATE. PLEASE |
| | REMOVE. |
| | |
| | ** PLEASE KNOW THAT CHANGES FOR NEW CODES IS REQUIRED |
| | FOR ALL TRADES AND FOR ALL REVIEWS EVEN IF COMMENT IS |
| | NOT MADE BY OTHER TRADE(S). |
| | |
| | 3) NOTE PLEASE SEE THE PLANS MUST CONTAIN AN ORIGINAL |
| | SIGNATURE FOR ALL DESIGNERS. PLEASE SEE THE |
| | ARCHITECTURAL SHEETS WHICH DO NOT CONTAIN AN ORIGINAL |
| | SIGNATURE FROM ARCHITECT. SHEETS IN FACT CONTAIN A |
| | RAISED SEAL OVER PHOTO-COPIED SIGNATURE/PRINTED. PLEASE |
| | SEE FS 481.221, FAC 61G1-16.004. |
| | ** THIS IS REQUIRED FOR ALL SHEETS AND TRADES WHETHER |
| | OR NOT COMMENT IS MADE BY OTHER TRADE(S). |
| | |
| | 4) NOTE: PLEASE SEE THE *S* SHEETS WHICH CONTAIN A SEAL |
| | WHICH IS NO LONGER VALID IN THE STATE OF FLORIDA. |
| | PLEASE SEE RULING61G15-23.001 AS OF FEBRUARY 04, |
| | WHICH REQUIRES ALL ENGINEERS TO OBTAIN A SEAL WITH THE |
| | WORDING OF ?LICENSE? AND THE WORDING OF *CERTIFICATE* |
| | COULD NOT LONGER BE USED. AN EXTENSION WAS GRANTED ONLY |
| | TO DECEMBER 31ST, 2005. |
| | PLEASE OBTAIN NEW SEAL. THIS COMMENT IS REQUIRED |
| | WHETHER OR NOT COMMENT IS MADE BY OTHER TRADE(S). |
| | |
| | 5) NOTE: PLEASE SEE FAC 61G1-16.004 FOR MISSING |
| | INFORMATION ON TITLE BLOCK FOR ARCHITECTURAL FIRM. |
| | PLEASE SEE THE LICENSE NUMBER AS PRINTED FOR THE |
| | CERTIFICATE OF AUTHORIZATION NUMBER IS NOT CORRECT. |
| | PLEASE SEE A DIGIT IS MISSING AS LISTED ON THE STATE |
| | WEBSITE. PLEASE SEE DEPARTMENT OF BUSINESS AND |
| | PROFESSIONAL REGULATION PRINT OUT ATTACHED TO NOTES. ** |
| | REQUIRED FOR ALL SHEETS WHICH CONTAIN THIS TITLE BLOCK |
| | WHETHER OR NOT COMMENT IS MADE BY OTHER TRADE(S). |
| | |
| | 6)NOTE: PLEASE SEE THE ENERGY CALCULATIONS CAN NOT BE |
| | VERIFIED AT THIS TIME AS THE PLANS DO NOT CONTAIN ANY |
| | FIXTURE LEGEND AND COORDINATION OF LABELING OF FIXTURES |
| | STILL NEEDS TO BE DONE. |
| | PLEASE SEE 13-415.2.ABC.1.2 FOR TRACK LIGHTING. PLEASE |
| | SEE SOME SEPARATE SPACES ARE MISSING THE REQUIRED |
| | CONTROLS. |
| | PLEASE SEE NO TIMES FOR THE OVER RIDE DEVICES COULD BE |
| | LOCATED. |
| | PLEASE SEE SOME OVER RIDE DEVICE LOCATIONS COULD NOT BE |
| | FOUND ON PLANS AS REQUIRED. |
| | PLEASE SEE THE DESIGN WATTS ON ENERGY CALCULATIONS |
| | SHEET 5 DOES NOT CORRELATE WITH THE DESIGN WATTS ON |
| | SHEET 2. |
| | PLEASE SEE THE SQ FT AS SHOWN CALCULATIONS ON ONE PART |
| | IS NOTED AS 84,000 SQ FT? |
| | PLEASE SEE THE SHEET 2 ON ENERGY CALCULATIONS MUST BE |
| | SIGNED BY OWNER AGENT. |
| | PLEASE SEE 13-103.1.1.1, 13-415.1.ABC.1.1, .1.2 AND |
| | .1.3, 13-415.1.AB.1.1, 13-415.2 ETC |
| | PLEASE PROVIDE WORST CASE VOLTAGE DROP FOR FEEDER(S) |
| | AND BRANCH CIRCUIT(S). |
| | PLEASE SEE 13-413.1ABC.1 |
| | |
| | 7) NOTE: PLEASE PROVIDE MORE INFORMATION FOR MAIN. |
| | PLEASE SEE THE MAIN WHICH CONTAIN THE MANUAL MEANS OF |
| | DISCONNECT RATED FOR THE LOAD SERVED PER 230.76 AND |
| | 230.79 SHALL BE INSTALLED AT A LOCATION WHICH HAS READY |
| | ACCESS. AS SHOWN ON PLANS THE MAIN IS LOCATED A |
| | DISTANCE IN THE BUILDING AND BEHIND SEVERAL LOCKED |
| | DOORS. PLEASE SEE THIS IS A LIFE SAFETY AND PROPERTY |
| | HAZARD IN ORDER FOR THE FIRE DEPARTMENT OR ANY OTHER |
| | PERSON NEEDING TO SHUT OFF POWER TO BUILDING. THE USE |
| | OF A SHUNT TRIP LOCATED OUTSIDE IS NOT PERMITTED AS IT |
| | DOES NOT MEET THE ABOVE CODE SECTIONS. |
| | PLEASE SEE A DIRECT ACCESS TO MAIN ELECTRICAL ROOM FROM |
| | OUTSIDE OR SOME OTHER MEANS TO ACCESS MAIN WILL BE |
| | REQUIRED. THIS WAS CONFIRMED WITH THE FIRE MARSHALS |
| | OFFICE. |
| | 230.70, 230.71, 230.72 ETC. |
| | |
| | 8) NOTE: PLEASE PROVIDE THE MANUFACTURES SPECS/CUT |
| | SHEETS FOR THE NEW PROPOSED MTS. 90.7, 110.3. |
| | FBC 106.1.2 |
| | |
| | 9) NOTE: PLEASE SEE THE PLANS SEEM TO CONTAIN MANY |
| | AREAS IN WHICH THERE IS INFORMATION PRINTED IN *LT |
| | GRAY* AND NOT EASILY READ. PLEASE SEE ELECTRICAL |
| | SHEETS. |
| | |
| | 10) NOTE: PLEASE KNOW THE LOW VOLTAGE WORK SHOWN ON |
| | PLANS WILL BE REQUIRED TO BE UNDER SEPARATE PERMITS. |
| | THESE PLANS MAY BE USED AS A REFERENCE FOR A |
| | *TURN-AROUND* PERMIT HOWEVER SEPARATE FEES WILL BE DUE |
| | FOR THIS SCOPE OF WORK. |
| | PLEASE SEE THE LOW VOLTAGE PERMIT FOR ANY SECURITY, |
| | FIRE ALARM AND FIRE SPRINKLER SYSTEMS WILL BE UNDER |
| | SEPARATE PERMITS. |
| | |
| | 11) NOTE: PLEASE SEE IF THERE ARE ANY FIRE ALARMS |
| | SYSTEMS REQUIRED OR INSTALLED EVEN IF UNDER SEPARATE |
| | PERMITS THE MINIMUM LEVELS FOR ADA COMPLIANCE NEEDS TO |
| | BE ON PLANS. |
| | PLEASE SEE FBC 11-4.28.1,. AND .3(4) FOR MINIMUM LEVELS |
| | TO BE STATED ON BASE PLANS. |
| | |
| | 12) NOTE: PLEASE PROVIDE ANY SITE LIGHTING ELECTRICAL |
| | DETAILS. PLEASE PROVIDE MINIMUM WIND LOAD INFORMATION |
| | FOR POLES. |
| | PLEASE KNOW THESE MAY BE UNDER A SEPARATE PERMIT AT A |
| | LATER DATE. |
| | FBC 106.1.2, 106.3 |
| | |
| | 13) NOTE: PLEASE SEE THE COLOR CODING EVEN THOUGH NOT |
| | APPLICABLE IN THIS SERVICE SITUATION FOR 277/480V IS |
| | BROWN, PURPLE, AND YELLOW. |
| | THIS DOES NOT NEED TO BE CHANGED, AND WILL BE |
| | REDLINED. |
| | |
| | 14) NOTE: PLEASE CONTACT THE LOCAL POLICE DEPARTMENT AS |
| | THERE IS LOCAL ORDINANCE WHICH REQUIRES MINIMUM |
| | LIGHTING LEVELS FOR ATM MACHINES/DRIVE UP AREAS OF |
| | BANKS. |
| | THIS WILL AFFECT THE ELECTRICAL SITE LIGHTING PLANS |
| | NOT YET SUBMITTED. |
| | |
| | |
| | ** PLEASE KNOW AS THERE ARE SOME ITEMS NOT YET |
| | SUBMITTED FOR REVIEW AND THE CHANGES WHICH WILL BE |
| | NEEDED FOR SERVICE A COMPLETE REVIEW CAN NOT BE DONE AT |
| | THIS TIME. |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |
| | ** PLEASE SEE ANY POSSIBLE COMMENTS FROM OTHER TRADES |
| | WHICH MAY AFFECT ELECTRICAL PLANS. |
| 2007-06-23 14:55:17 | 2007-06-23 14:55:17 |
| | REIVEW IN PROGRESS. |
| 2007-06-22 19:35:45 | 2007-06-22 19:35:45 |
| | REVIEW TO CONTINUE AND NOTES TO FOLLOW. |
| 2007-06-22 18:46:44 | 2007-06-22 18:46:44 |
| | IN ELEC FOR REVIEW. |