2007-07-07 14:14:14COMMERCE BANK 2031 P B LAKES
 **PLAN REVIEW**
 BUILDING PLAN REVIEW
 PERMIT: 07050876
 ADD: 2031 PALM BEACH LAKSE
 CONT: **PLAN REVIEW**
 TEL: (954)648-6068
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 2) FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS NOT
 ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3) SHEET A000
 3A) ALL OF THE ARCHITECTURAL SHEETS HAVE COPIES OF THE
 ARCHITECTS SIGNATURE WITH A RAISED
 SEAL.PLANS, SPECIFICATIONS, REPORTS OR OTHER
 DOCUMENTS PREPARED BY THE DESIGN PROFESSIONAL AND BEING
 FILED FOR PUBLIC
 RECORD SHALL HAVE THE SIGNATURE AND SEAL OF THE DESIGN
 PROFESSIONAL AFFIXED TO THE DOCUMENT. ARCHITECTS FL
 STATE STAT: 61G16.003 ARCHITECTS.
  
 3B) INTERARCH IS MISSING THEIR CERTIFICATE OF
 AUTHORIZATION, 471.023 F.S.CERTIFICATE OF
 AUTHORIZATION.THE TITLE BLOCK FOR ANY SHEET BEARING
 THE NAME OF AN ENGINEER
 PRACTICING UNDER A FICTITIOUS NAME, A CORPORATION, OR A
 PARTNERSHIP, OFFERING ENGINEERING SERVICES, SHALL
 INCLUDE THE CERTIFICATE OF AUTHORIZATION NUMBER. ADD
 THE NUMBER TO EACH SHEET.
  
 3C) MICHAEL A BEACH & ASSOCIATES, LLC, CONSULTING
 STRUCTURAL ENGINEERS, ALSO ARE MISSING THEIR
 CERTIFICATE OF AUTHORIZATION. 481.023 F.S.CERTIFICATE
 OFAUTHORIZATION.THE TITLE BLOCK FOR ANY SHEET
 BEARING THE NAME OF AN ENGINEER PRACTICING UNDER A
 FICTITIOUS NAME, A CORPORATION, OR A PARTNERSHIP,
 OFFERING ENGINEERING SERVICES, SHALL INCLUDE THE
 CERTIFICATE OF AUTHORIZATION NUMBER. ADD THE NUMBER TO
 EACH SHEET.THIS MAY
 BE ADDED BY HAND.
  
 4) SHEET A200 HAS THE WRONG LOCATION IN THE TITLE
 BLOCK.
  
 5) SHEET A301 INDICATES A NIGHT DEPOSITORY BUT NO ATM
 MACHINE? IF SUCH SYSTEMS ARE TO BE USED, PLEASE LOOK TO
 11-4.34 FOR ACCESSIBILITY AND TABLE 13-415.2ABC.1.3 270
 WATTS PER LOCATION.
  
 6) 1609.1.4 PROTECTION OF OPENINGS. IN WIND-BORNE
 DEBRIS REGIONS, EXTERIOR GLAZING THAT RECEIVES POSITIVE
 PRESSURE IN THE LOWER 60 FEET (18.3 M) IN BUILDINGS
 SHALL BE ASSUMED TO BE OPENINGS AND THE BALANCE OF
 GLAZED OPENINGS IN THE REST OF THE BUILDING SHALL BE
 ASSUMED TO BE ZERO UNLESS SUCH GLAZING THAT RECEIVES
 POSITIVE PRESSURE IS IMPACT RESISTANT OR PROTECTED WITH
 AN IMPACT RESISTANT COVERING MEETING THE REQUIREMENTS
 OF SSTD 12, ASTM E 1886 AND ASTM E 1996, OR MIAMI-DADE
 TAS 201, 202 AND 203 REFERENCED THEREIN AS FOLLOWS: 1.
 GLAZED OPENINGS LOCATED WITHIN 30 FEET (9.1 M) OF GRADE
 SHALL MEET THE REQUIREMENTS OF THE LARGE MISSILE TEST.
 2.GLAZED OPENINGS LOCATED MORE THAN
 30 FEET (9.1 M) ABOVE GRADE SHALL MEET THE PROVISIONS
 OF THE SMALL MISSILE TEST.
  
 FL BLD CODE 1609.1.4: COMPONENTS & CLADDING, PROVIDE
 2 COPIES(3 IF THRESHOLD OR RESIDENT INSPECTOR) OF
 PRODUCT TESTING REPORTS,
 MISSING REPORTS ARE AS FOLLOWS:
  
 A) VISTAWALL HR-250 , PLEASE HIGHLIGHT WHICH GLAZING
 SYSTEM WILL BE USED.
 NOTE: SEE MIAMI-DADE NOA, THIS NOA HAS NOT BEEN
 REVIEWED UNDER THE 2004 FBC, THIS TEST WAS TAKEN WHEN
 1.33 STEEL INCREASES WERE TAKEN ON FASTENERS!!!!
 INTERARCH HAS SIGNED OFF BEWARE!!!!!
  
 1605.3.1.1 LOAD REDUCTION.
 1.IT IS PERMITTED TO MULTIPLY THE COMBINED EFFECT
 OF TWO OR MORE VARIABLE LOADS BY 0.75 AND ADD THE
 EFFECT OF DEAD LOAD. THE COMBINED LOAD USED IN DESIGN
 SHALL NOT BE LESS THAN THE SUM OF THE EFFECT OF DEAD
 LOAD AND ANY OF THE VARIABLE LOADS.
 2.INCREASES IN ALLOWABLE STRESS SPECIFIED IN THE
 MATERIALS, SECTIONS OF THIS CODE OR A REFERENCED
 STANDARD SHALL NOT BE PERMITTED TO BE USED WITH LOAD
 COMBINATIONS OF SECTIONS 1605.3.1 . DURATION OF LOAD
 INCREASE SHALL BE PERMITTED IN ACCORDANCE WITH CHAPTER
 23 .
  
 B) FIREDOOR: REQUIRES FLORIDA COVERSHEET,PRODUCT
 APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003 ARE REQUIRED
 TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION PLEASE SEE THE
 STATE WEBSITE ATWWW.FLORIDABUILDING.ORG. PRODUCTS
 WITH STATEWIDE APPROVAL ARE REQUIRED TO BE SUBMITTED
 WITH A COVER SHEET THAT LISTS THE PRODUCT IDENTITY
 NUMBER FROM THE STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICATION FOR LOCAL
 PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE ATTACHMENT.
 WWW.FLORIDABUILDING.ORG!!!! INTERARCH HAS
 SIGNED OFF BEWARE!!!!!
  
 1605.3.1.1 LOAD REDUCTION.
 1.IT IS PERMITTED TO MULTIPLY THE COMBINED EFFECT
 OF TWO OR MORE VARIABLE LOADS BY 0.75 AND ADD THE
 EFFECT OF DEAD LOAD. THE COMBINED LOAD USED IN DESIGN
 SHALL NOT BE LESS THAN THE SUM OF THE EFFECT OF DEAD
 LOAD AND ANY OF THE VARIABLE LOADS.
 2.INCREASES IN ALLOWABLE STRESS SPECIFIED IN THE
 MATERIALS, SECTIONS OF THIS CODE OR A REFERENCED
 STANDARD SHALL NOT BE PERMITTED TO BE USED WITH LOAD
 COMBINATIONS OF SECTIONS 1605.3.1 . DURATION OF LOAD
 INCREASE SHALL BE PERMITTED IN ACCORDANCE WITH CHAPTER
 23 .
  
 C) RELIABLE PRODUCTS: AEL-42D-7060 ALUMINUM LOUVER IS
 IN THE SAME SITUATION AS THE TWO REPORTS LISTED ABOVE
 SEE **C** CALCULATIONS: 2004 FBC NOT LISTED!
  
 D) MERCHANT & EVANS ALUMINUM ZIP RIB STANDING SEAM ROOF
 PANEL:
 HIGHLIGHT WHICH SYSTEM YOU WILL BE USING, SYSTEM A(1)
 OR SYSTEMA(2).
  
 E) GAF MATERIAL ? MODIFIED BITUMEN ROOFING REQUIRES
 FLORIDA COVERSHEET, AND
 HIGHLIGHT WHICH SUBSYSTEM WILL BE USED. ALSO NOTE
 LIMITATION 7 OR 9!!!!!PROVDE THE RAS 117 CALCULATIONS
 FOR THE ENHANCED FASTENING IN ZONES 2& 3.
  
 F) ROOF HATCH: NOTE THAT NO INFORMATION WAS SUBMITTED,
 CURRENTLY THERE ARE NO ROOF HATCHES
 AVAILABLE THROUGH MIAMI-DADE OR THE FLORIDA WEBSITE.
 BILCO IS SUPPOSE TO BE GOING THROUGH A TESTING PROGRAM
 AT THIS TIME!
  
 G)EFIS TRIM- PROVIDE ALSO DOCUMENTATION FOR TESTING.
  
  
 H) STOREFRONT SYSTEMS OR FIXED GLASS( TELLER WINDOW) NO
 REPORTS WERE SUBMITTED.
  
 7) SHEET A320 THE CEILING ASSEMBLY OF THE DRIVE
 THROUGH, PLEASE PROVIDE ADDITIONAL INFORMATION ON THE
 TYPE OF WIRE MESH TO BE USED FOR THE STUCCO CEILING?
 SIZE, WEIGHT, NAILING & SPACING? ASTM C-1063.
  
 8)BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
 BUILDING PLAN REVIEW II
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]