| 2007-08-16 07:48:50 | |
| | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: |
| | |
| | THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004 |
| | RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002, |
| | NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND |
| | NONCOMPLIANT WITH THE FOLLOWING: |
| | |
| | 1} THE GENERATOR MUST BE PERMITTED SEPARATELY. THE |
| | MANUAL TRANSFER SWITCH MAY BE LEFT ON THE RISER WITH |
| | THIS PERMIT, BUT MANUFACTURERS SPECIFICATIONS MUST BE |
| | SUBMITTED FOR REVIEW PRIOR TO A PERMIT BEING ISSUED. |
| | MAKE A NOTE ON THE RISER DIAGRAM, SHEET E-2, THAT THE |
| | GENERATOR WILL BE PERMITTED SEPARATELY. REMOVE THE " |
| | +NEW DRIVEWAY+NEW GENERATOR" PENCIL ADDITIONS IN THE |
| | DESCRIPTION ON THE APPLICATION. IF ADDING TO THE |
| | DESCRIPTION INCREASE THE VALUE TO INCLUDE SAME. |
| | |
| | 2}NOTE THE SIZE PER 250.122, #2 IS EXCESSIVE, AND |
| | ALTHOUGH PERMITTED, WILL PROBABLY RESULT IN A LATER |
| | REVISION. SEE TABLE. THIS COMMENT REFERS TO THE PANEL |
| | "A" FEED FROM THE TRANSFER SWITCH. |
| | |
| | 3} REGARDING NOTE #5, PREVIOUS REVIEW "THERE IS |
| | EQUIPMENT LISTED IN THE CALCULATIONS THAT ARE NOT ON |
| | ANY PANEL SCHEDULES. SEE REVIEWED PLAN." THE POOL PANEL |
| | WITH A 10240 W CALCULATED LOAD STILL IS LISTED IN THE |
| | LOAD CALCULATION(SERVICE), 6283 VA IN THE POOL |
| | EQUIPMENT CALCULATION AND ONLY A PUMP AND LIGHT ARE |
| | LISTED IN PANEL "A". PLEASE CORRELATE TO INDICATE |
| | ACTUAL CONDITIONS. |
| | |
| | 4} PANEL "A", CIRCUIT 1,3,SHEET E-2, LISTS #3 |
| | CONDUCTORS FEEDING PANEL "B", AND THE RISER FEEDERS ARE |
| | LISTED AS #2. PLEASE VERIFY EXISTING CONDITIONS AND |
| | CORRECT ON PLAN. |
| | |
| | 5} CIRCUITS 16 AND 18, PANEL "A" ARE REVERSED FROM THE |
| | NUMBERED CIRCUITS ON SHEET E-2. SMALL APPLIANCE |
| | (REQUIRED) AND LIGHTING. |
| | |
| | NOTE #1: CIRCUIT # A24,FOR THE SMOKE DETECTORS MUST |
| | BE ON A AFCI PER 210.12, THE OUTSIDE LIGHTS ARE ON THIS |
| | SAME CIRCUIT, NO VIOLATION, JUST A NOTE. |
| | #2: ALTHOUGH THE GENERATOR IS NOT BEING |
| | REVIEWED AT THIS TIME, IT WAS NOTED THAT THE GENERATOR |
| | CALCULATION IS 101 AMPS (24KW), THE SPEC'S SUBMITTED |
| | ARE FOR A 20KW GENERATOR WITH AN OUTPUT OF 84 AMPS. |
| | |
| | THE DESIGNER OF RECORD IS THE ENGINEER THAT SEALED THE |
| | PLAN, THE RESPONSE FOR THE PREVIOUS REVIEW WAS SIGNED |
| | BY THE ARCHITECT. PLEASE SEE THAT ALL GET A COPY OF |
| | THESE COMMENTS. |
| | |
| | PLEASE REMOVE ALL OLD OR VOIDED SHEETS AND REPLACE WITH |
| | CORRECTED ONES WHEN RESUBMITTING. INCLUDE THEM |
| | SEPARATELY TO EXPEDITE THE REVIEW PROCESS. |
| | ANSWER REVIEW COMMENTS IN WRITING. |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |
| | BILL TROBAUGH |
| | ELECTRICAL PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | 561/805-6718 |
| | [email protected] |
| | |
| | |
| | |
| | |
| | |
| | |