| 2007-11-28 16:28:52 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH |
| | 05 & 06 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS |
| | TO CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE |
| | (F.A.C.), AND FLORIDA STATUTES (F.S.). |
| | |
| | PLUMBING PLAN REVIEW: |
| | DENIED 2ND TIME: |
| | |
| | THE FOLLOWING CORRECTIONS/INFORMATION ARE STILL |
| | REQUIRED FOR PLUMBING PLAN REVIEW ON THE RESUBMITTED |
| | PLANS TO MEET CODE COMPLIANCE. |
| | |
| | 1. COMMENT NOT ADDRESSED. ** FBC-2004 CHAPTER |
| | 1,SECTION 106.3.4.3: |
| | THE PERSON RESPONSIBLE FOR THE DESIGN OF |
| | THE DRAWING SHALL CLEARLY PRINT AND SIGN |
| | NAME, AND ALSO DATE DRAWING. IF AN ARCHITECT OR |
| | ENGINEER, COMPLY WITH 418 AND 417 FS, RESPECTIVELY. |
| | PLEASE DO THIS PRIOR TO RESUBMITTING. |
| | **NOTE: RESUBMITTED PLANS DO NOT AN EMBOSING IMPRESSION |
| | SEAL PER *FS 417.025. |
| | |
| | 2. COMMENT NOT ADDRESSED. MORE INFORMATION IS REQUIRED |
| | FOR THE REPLACEMENT OF THE EXISTING BUS WASH EQUIPMENT. |
| | IS THE NEW SYSTEM LARGER THAN THE EXISTING OR IS IT A |
| | LIKE FOR LIKE CHANGE OUT USING THE SAME SIZE EQUIPMENT |
| | AS THAT OF THE EXISTING, AND ARE YOU USING THE EXISTING |
| | OIL SEPERATOR AND SAND INTERCEPTORS. PER *1003.4 OIL |
| | SEPERATOR REQUIRED, *1003.4.1 SEPERATION OF LIQUIDS, |
| | *1003.4.2 OIL SEPERATION DESIGN, *1003.4.2.1 GENERAL |
| | DESIGN REQUIREMENTS, *1003.4.2.2 GARAGE AND SERVICE |
| | STATIONS, 1003.11 SAND INTERCEPTORS IN COMMERCIAL |
| | ESTABLISHMENTS. |
| | |
| | **NOTE: SHEET 6806-P ON THE RESUBMITTED PLANS ARE |
| | INDICATING THE "SCOPE OF WORK IS TO CHANGE THE EXISTING |
| | BUS WASH EQUIPMENT W/LIKE-KIND EQUIPMENT". THIS IS |
| | CONFUSING, DO YOU MEAN THIS IS A LIKE FOR LIKE CHANGE |
| | OUT WITH THE EQUIPMENT BEING THE SAME SIZE? PLEASE |
| | CLARIFY THIS ON THE RESUBMITTAL AND INDICATE ON THE |
| | PLANS THAT BUS WASH IS USING THE EXISTING OIL SEPERATOR |
| | AND EXISTING SAND INTERCEPTOR. |
| | |
| | PER RULE 62-62..803,FAC,A CAR WASH RECYCLE GENERAL |
| | PERMT NOTIFICATION FORM IS REQUIRED TO BE FILLED OUT |
| | AND APPROVED BY ENVIRONMENTAL COMPLIANCE PRIOR TO |
| | PERMITTING. THIS FORM WAS FAXED TO THE CONTRACTOR H.A. |
| | CONTRACTING CORP. AND THIS PLANS EXAMINER ON 6/22/07. |
| | PLEASE CONTACT ENVIRONMENTAL COMPLIANCE DIVISION OF THE |
| | UTILITY DEPARTMENT. PLEASE CONTACT RODNEY COMPO, PHONE: |
| | (561) 822-2272, E-MAIL: [email protected] OR CLAVIN |
| | WILLIAMS, PHONE: (561) 822-2284, E-MAIL: |
| | [email protected]. THEIR FAX NUMBER IS (561) 822-2287 |
| | FOR FURTHER INFORMATION REGAURDING THIS ISSUE. |
| | |
| | 3. COMMENT WAS ADDRESSED. |
| | |
| | END OF COMMENTS: |
| | |
| | REVIEW BY: MIKE PERSON |
| | PLUMBING PLANS EXAMINER |
| | (561) 805-6730 |
| | FAX (561) 805-6731 |
| | E-MAIL: [email protected] |