Plan Review Notes
Plan Review Notes For Permit 07050857
Permit Number 07050857
Review Stop P
Sequence Number 1
Notes
Date Text
2007-06-22 11:21:44DENIED
 REFERENCE:
 ** FBC-2004 PLUMBING.
 ** FBC-2004 CHAPTER 1, THE CITY OF
 WEST PALM BEACH AMENDMENTS.
 ** FLORIDA ADMINISTRATIVE CODE.
 ** FLORIDA STATUTES.
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE:
  
 1. FBC-2004 CHAPTER 1,SECTION 106.3.4.3:
 THE PERSON RESPONSIBLE FOR THE DESIGN OF
 THE DRAWING SHALL CLEARLY PRINT AND SIGN
 NAME, AND ALSO DATE DRAWING. IF AN ARCHITECT OR
 ENGINEER, COMPLY WITH 418 AND 417 FS, RESPECTIVELY.
 PLEASE DO THIS PRIOR TO RESUBMITTING.
  
 2. MORE INFORMATION IS REQUIRED FOR THE REPLACEMENT OF
 EXISTING BUS WASH EQUIPMENT. IS THIS NEW SYSTEM LARGER
 THAN THE EXISTING OR IS IT A LIKE FOR LIKE CHANGE OUT
 USING THE SAME OIL AND SAND INTERCEPTORS. THE
 REPLACEMENT OF THE BUS WASHING EQUIPMENT NEEDS THE
 FOLLOWING INFORMATION ON THE DRAWINGS PER FBC-2004
 PLUMBING.
 A} SECTION 1003.4, OIL SEPARATOR REQUIRED.
 B} SECTION 1003.4.1, SEPARATION OF LIQUIDS.
 C} SECTION 1003.4.2, OIL SEPARATION DESIGN. OIL
 SEPERATORS SHALL BE DESIGNED IN ACCORDANCE WITH
 SECTIONS 1003.4.2.1, GENERAL DESIGN REQUIREMENTS AND
 SECTION 1003.4.2.2 GARAGES AND SERVICE STATIONS.
 D} SECTION 1003.11 SAND INTERCEPTORS IN
 COMMERCIAL ESTABLISHMENTS.
 AND APPROVAL OF THE SIZE AND LOCATION FROM
 ENVIRONMENTAL COMPLIANCE DIVISION OF THE UTILITY DEPT.
 PLEASE CONTACT RODNEY COMPO, (561) 822-2272 OR CALVIN
 WILLIAMS, (561) 822-2284. THEIR FAX NUMBER IS (561)
 822-2287 AND THEIR E-MAIL ADDRESSES ARE [email protected]
 AND [email protected] CODE ARTICLE III
 SECTION 90-124.
  
 3. DRAWING NUMBER 6806-P, PLEASE CORRECT AND ADD THE
 FOLLOWING INFORMATION:
 A}PLUMBING NOTE #2 DUE TO THE HIGH HAZARD AND
 CHEMICAL INDUCTION IN THE WASH SYSTEM PLEASE CLEARLY
 INDICATE THAT A REDUCED PRESSURE ZONE BACKFLOW
 PREVENTOR IS BEING USED TO PROTECT THE POTABLE WATER.
 B} PLEASE CLEARLY INDICATE THE POTABLE WATER
 SUPPLY TO THE BUS WASH SYSTEM WITH THE LOCATION OF THE
 REDUCED PRESSURE ZONE BACKFLOW PREVENTOR.
 C} PLEASE INDICATE IN THE LEGEND THE SYMBOL OF
 THE REDUCED PRESSURE ZONE BACKFLOW PREVENTOR.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved