| Date |
Text |
| 2007-06-22 11:21:44 | DENIED |
| | REFERENCE: |
| | ** FBC-2004 PLUMBING. |
| | ** FBC-2004 CHAPTER 1, THE CITY OF |
| | WEST PALM BEACH AMENDMENTS. |
| | ** FLORIDA ADMINISTRATIVE CODE. |
| | ** FLORIDA STATUTES. |
| | |
| | THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR |
| | PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE: |
| | |
| | 1. FBC-2004 CHAPTER 1,SECTION 106.3.4.3: |
| | THE PERSON RESPONSIBLE FOR THE DESIGN OF |
| | THE DRAWING SHALL CLEARLY PRINT AND SIGN |
| | NAME, AND ALSO DATE DRAWING. IF AN ARCHITECT OR |
| | ENGINEER, COMPLY WITH 418 AND 417 FS, RESPECTIVELY. |
| | PLEASE DO THIS PRIOR TO RESUBMITTING. |
| | |
| | 2. MORE INFORMATION IS REQUIRED FOR THE REPLACEMENT OF |
| | EXISTING BUS WASH EQUIPMENT. IS THIS NEW SYSTEM LARGER |
| | THAN THE EXISTING OR IS IT A LIKE FOR LIKE CHANGE OUT |
| | USING THE SAME OIL AND SAND INTERCEPTORS. THE |
| | REPLACEMENT OF THE BUS WASHING EQUIPMENT NEEDS THE |
| | FOLLOWING INFORMATION ON THE DRAWINGS PER FBC-2004 |
| | PLUMBING. |
| | A} SECTION 1003.4, OIL SEPARATOR REQUIRED. |
| | B} SECTION 1003.4.1, SEPARATION OF LIQUIDS. |
| | C} SECTION 1003.4.2, OIL SEPARATION DESIGN. OIL |
| | SEPERATORS SHALL BE DESIGNED IN ACCORDANCE WITH |
| | SECTIONS 1003.4.2.1, GENERAL DESIGN REQUIREMENTS AND |
| | SECTION 1003.4.2.2 GARAGES AND SERVICE STATIONS. |
| | D} SECTION 1003.11 SAND INTERCEPTORS IN |
| | COMMERCIAL ESTABLISHMENTS. |
| | AND APPROVAL OF THE SIZE AND LOCATION FROM |
| | ENVIRONMENTAL COMPLIANCE DIVISION OF THE UTILITY DEPT. |
| | PLEASE CONTACT RODNEY COMPO, (561) 822-2272 OR CALVIN |
| | WILLIAMS, (561) 822-2284. THEIR FAX NUMBER IS (561) |
| | 822-2287 AND THEIR E-MAIL ADDRESSES ARE [email protected] |
| | AND [email protected] CODE ARTICLE III |
| | SECTION 90-124. |
| | |
| | 3. DRAWING NUMBER 6806-P, PLEASE CORRECT AND ADD THE |
| | FOLLOWING INFORMATION: |
| | A}PLUMBING NOTE #2 DUE TO THE HIGH HAZARD AND |
| | CHEMICAL INDUCTION IN THE WASH SYSTEM PLEASE CLEARLY |
| | INDICATE THAT A REDUCED PRESSURE ZONE BACKFLOW |
| | PREVENTOR IS BEING USED TO PROTECT THE POTABLE WATER. |
| | B} PLEASE CLEARLY INDICATE THE POTABLE WATER |
| | SUPPLY TO THE BUS WASH SYSTEM WITH THE LOCATION OF THE |
| | REDUCED PRESSURE ZONE BACKFLOW PREVENTOR. |
| | C} PLEASE INDICATE IN THE LEGEND THE SYMBOL OF |
| | THE REDUCED PRESSURE ZONE BACKFLOW PREVENTOR. |
| | |
| | END OF COMMENTS: |
| | |
| | REVIEW BY MIKE PERSON |
| | (561) 805-6730 |
| | FAX (561) 805-6731 |
| | E-MAIL [email protected] |
| | UNDER SUPERVISION OF K.STEVENS |
| | (561) 805-6721 |