Plan Review Notes
Plan Review Notes For Permit 07050817
Permit Number 07050817
Review Stop B
Sequence Number 3
Notes
Date Text
2009-01-28 16:37:15RESIDENTIAL (R3) ADDITION, BUILDING REVIEW THIRD
 CHECKLIST.
 REVIEW UNDER 2004 FLORIDA RESIDENTIAL CODE WITH 2007
 REVISIONS.
  
 1- BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG
 RD(561)233-5120) TO VERIFY IF IMPACT FEES ARE DUE.
 BRING BACK STAMPED PLANS AND COPY OF PAID RECEIPT IF
 FEES ARE DUE (REPEAT COMMENT - THREE TIMES).
  
 2- FLAT ROOF PRODUCT APPROVAL WAS CHANGED FOR NOA
 06-0410.06. THE FOLLOWING COMMENTS APPLY:
 A) APPROVED ASSEMBLY SELECTED ON SHEET 37 OF 44 CAN'T
 BE USED IN THIS PROJECT BECAUSE THIS ASSEMBLY MEETS
 ONLY 45PSF UPLIFT LOAD. THIS ASSEMBLY IS LIMITED BY
 GENERAL LIMITATION #9, WHICH DOESN'T ALLOW ANY NAIL
 ENHANCING. SEE GENERAL LIMITATION #9 ON LAST PAGE OF
 NOA SUBMITTED. NEED TO SELECT AN ASSEMBLY THAT MEETS
 THE DESIGN PRESSURES CALCULATED BY THE ENGINEER ON
 SHEET A-4.
 TYPICALLY AN ASSEMBLY THAT IS LIMITED BY GENERAL
 LIMITATION #7 CAN BE SELECTED AND ADDITIONAL NAIL
 ENHANCING FOR PERIMETER AND CORNER AREAS MAY BE
 ACHIEVED BY PROVIDING SIGNED AND SEALED RAS 117
 CALCULATIONS. SEE GENERAL LIMITATION #7 ON LAST PAGE OF
 NOA SUBMITTED (REPEAT COMMENT - THREE TIMES).
  
 B) ACCORDING TO MIAMI-DADE WEBSITE NOA 06-0410.06 CAN'T
 BE USED BECAUSE THIS FILE IS CLOSED. SEE ATTACHED COPY
 FROM MIAMI-DADE WEBSITE. NEED TO PROVIDE CURRENT
 APPROVED NOA.
  
 3- ENERGY CALCULATIONS:
 A) PROVIDE COMPLETE CALCULATIONS. ONLY TWO PAGES WERE
 SUBMITTED (REPEAT COMMENT - THREE TIMES).
  
 B) CLARIFY WALL TYPES AND INSULATION R-VALUE SHOWN ON
 ITEM #9 (REPEAT COMMENT - THREE TIMES). CLARIFY WHY
 SAME R-VALUE IS SHOWN FOR CONCRETE BLOCK WALLS AND
 FRAMED WALLS?.
 ALSO, WHAT KIND OF WALL IS OTHERS?
  
 C) PROVIDE COMPLETE INFORMATION ON TOP OF FORM (REPEAT
 COMMENT - THREE TIMES).
  
 D) CLARIFY IF ENERGY CALCULATIONS ARE DONE FOR ENTIRE
 HOUSE OR JUST FOR THE NEW ADDITION (REPEAT COMMENT -
 THREE TIMES)). ITEM #1 STATES ADDITION, WHILE
 CONDITIONED FLOOR AREA SHOWN ON ITEMS #6 AND #10 SHOW
 THE SQUARE FOOTAGE OF ENTIRE HOUSE. ON THE OTHER HAND
 PLANS DON'T SHOW ANY INFORMATION PERTAINING TO THE
 COMPLIANCE WITH THE ENERGY CALCULATION FOR ENTIRE
 HOUSE.
  
 NOTE: COMPLETING FORM 600C-04R IS MORE APPROPRIATE FOR
 THE ADDITION (REPEAT COMMENT - THREE TIMES).
  
 E) ITEM #10: MISSING THE SINGLE ASSEMBLY ROOF AREA.
 ALSO, CLARIFY IF DOING ENTIRE HOUSE OR JUST THE
 ADDITION. COORDINATE WITH ITEM # 3D ABOVE.
  
 F) NUMBER OF BEDROOMS IS INCORRECT. SEE FLOOR PLANS AND
 REVISE AS REQUIRED.
  
 4-ENERGY CALCULATIONS SUBMITTED ARE TAKEN THE CEILING
 FANS CREDIT. THEREFORE, PLANS NEED TO SHOW ALL ROOMS
 WITH CEILING FAN SIZE AS REQUIRED BY TABLE 13-607.1.A.1
 FBC 2004. (REPEAT COMMENT - THREE TIMES). PLANS DON'T
 SHOW CEILING FAN SIZES.
  
 5- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC 2004.
 ENGINEER SIGNED AND SEALED PRODUCT APPROVALS. HE CAN'T
 SIGN AND SEAL THOSE PRODUCT APPROVALS BECAUSE THEY WERE
 NOT PREPARED BY HIM. SIGNING AND SEALING THESE PRODUCT
 APPROVALS IS IN VIOLATION OF FLORIDA STATUTE 471 AND
 FLORIDA ADMINISTRATIVE CODE SEC. 61G15.
  
 6- SHEET A-4:
 A) ROOF DESIGN PRESSURES WERE REVISED, BUT NOW ENGINEER
 IS CONTRADICTING HIMSELF ON DETAIL A SHOWN ON SAME
 PAGE. SELECTED FLAT ROOF ASSEMBLY IS ONLY GOOD FOR UP
 TO 45PSF UPLIFT. THIS ASSEMBLY DOESN'T MEET THE DESIGN
 PRESSURES FOR ROOF ZONE 2 AND 3. NEED TO PROVIDE
 PRODUCT APPROVAL THAT MEETS THE CALCULATED DESIGN
 PRESSURES. COORDINATE WITH ITEM #2 ABOVE.
  
 B) REVISE ALL INFORMATION ON CONNECTOR SCHEDULE. SEE
 CURRENT SIMPSON CATALOG FOR NUMBER, TYPE AND UPLIFT
 CAPACITY OF EACH CONNECTOR. OTHERWISE, PROVIDE COMPLETE
 ENGINEERING ANALYSIS FOR INFORMATION THAT DIFFER FROM
 THAT TESTED AND PUBLISHED BY THE MANUFACTURER. SEC.
 106.1.2 CITY AMENDMENTS TO FBC 2004 TO VERIFY
 COMPLIANCE WITH SEC. R301 OF 2004 FLORIDA RESIDENTIAL
 CODE (REPEAT COMMENT).
  
 C) ROOF FRAMING PLAN WAS REVISED. * SPECIFY HOW
 PROVIDING ROOF CROSS VENTILATION TO COMPLY WITH SEC.
 R806 OF 2004 FLORIDA RESIDENTIAL CODE. KEEP IN MIND
 THAT USING 2X12 SOLID ROOF RAFTERS.
  
 D) REVISE ROOF SLOPE SPECIFIED ON ROOF FRAMING PLAN AND
 DETAILS. NEED 1/4" PER FT. MIN. AS REQUIRED BY SEC.
 R905.11.1 OF 2004 FLORIDA RESIDENTIAL CODE.
  
 E) REVISE BLOCK SHOWN ON DETAIL "C" TO ALLOW PROPER
 ROOF PITCH AS REQUIRED BY ITEM 6D ABOVE.
  
 F) REVISE DETAIL "B": SIMPSON CONNECTOR "H10S" DOESN'T
 WORK FOR PROPOSED INSTALLATION. SEE CATALOG FOR PROPER
 CONNECTOR PROFILE AND PROVIDE DETAIL SHOWING ACTUAL
 CONNECTOR PROFILE.
  
 7- SHEET A-3:
 A) ARCH FORM DETAIL: PROVIDE SPECIFICATIONS FOR
 FASTENINGS OF 2X6'S TO WALL AND FASTENING OF PLYWOOD TO
 VERIFY COMPLIANCE WITH SEC. R301 OF 2004 FLORIDA
 RESIDENTIAL CODE.
  
 B) SPECIFY 2 LAYERS OF WATER RESISTANT BARRIERS AS
 REQUIRED BY SEC. R703.6.3 OF 2004 FLORIDA RESIDENTIAL
 CODE.
  
 8- TYPICAL WALL SECTION ON SHEET GD:
 A) REVISE ROOF SLOPE AND DETAIL SHOWING BLOCKING TO GET
 THE REQUIRED SLOPE. SEE ITEM 6D ABOVE.
  
 B) REVISE FLAT ROOF ASSEMBLY INFORMATION. SEE ITEM 6A
 ABOVE.
  
 C) REVISE INFORMATION FOR ROOF CROSS VENTILATION. SEE
 ITEM 6C ABOVE.
  
 8- SHEET GN: UPDATE ALL REFERENCES CITED ON ALL NOTES.
 SEE CHAPTER 43 OF 2004 FLORIDA RESIDENTIAL CODE FOR
 YEAR EDITION TO BE USED ON ADOPTED STANDARDS AND REVISE
 AS REQUIRED (REPEAT COMMENT).
  
 9- ONE SHEET GD WAS NOT SIGNED AND SEALED BY THE
 ENGINEER.
  
 10- A) CALCULATIONS SUBMITTED TO CHECK BEAM SPECIFY
 2X12 SOUTHER PINE #1. GENERAL NOTES ON SHEET GN
 SPECIFIES SOUTHER PINE #2. REVISE AS REQUIRED. AND,
 CLEARLY SPECIFY ON ROOF FRAMING PLAN GRADE OF WOOD TO
 BE USED.
  
 B) CALCULATIONS NEED TO BE SIGNED AND SEALED BY THE
 ENGINEER OF RECORD AS REQUIRED BY CHAPTER 471 FLORIDA
 STATUTE AND FLORIDA ADMINISTRATIVE CODE SEC. 61G15.
  
 11- NOTICE OF COMMENCEMENT WAS RECORDED ON 02/14/2008.
 NOTICE OF COMMENCEMENT EXPIRES AFTER 90 DAYS IF WORK IS
 NOT STARTED. NEED TO PROVIDE RE-RECORDED NOTICE OF
 COMMENCEMENT. SEC. 713.13 FLORIDA STATUTE.
 NOTE: THIS MAY BE RECORDED AT TIME OF PERMIT PICK UP TO
 AVOID EXPIRATION.
  
 12- ENGINEER TO REVIEW ATTACHED COPY FLORIDA STATUTE
 SEC. 55380(2)(B) REGARDING FEES FOR MULTIPLE REVIEWS.
 ONE COPY OF PLANS WILL BE RETAINED IN THIS OFFICE TO
 VERIFY IF COMMENTS ARE PROPERLY ADDRESSED.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712