Plan Review Notes
Plan Review Notes For Permit 07050817
Permit Number 07050817
Review Stop B
Sequence Number 2
Notes
Date Text
2008-03-31 16:09:46RESIDENTIAL ADDITION BUILDING REVIEW SECOND CHECKLIST.
 REVIEW UNDER FBC 2004 WITH 2007 REVISIONS.
  
 1- BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG RD
 (561)233-5120), TO VERIFY IF IMPACT FEES ARE DUE. BRING
 BACK STAMPED PLANS AND COPY OF PAID RECEIPT IF FEES ARE
 DUE.
  
 2- PROVIDE TWO COPIES OF PRODUCT APPROVALS AS REQUIRED
 BY DCA RULE 9B-72 FOR:
 A) EXTERIOR SWING DOOR. (REPEAT COMMENT).
  
 B) ALL USP STRUCTURAL CONNECTORS SPECIFIED ON PLANS.
 (REPEAT COMMENT). PROVIDE COVER PAGE OF PRODUCT
 APPROVAL AND PAGE WHERE CONNECTORS ARE SHOWN.
  
 3- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 ALL PRODUCT APPROVALSAS REQUIRED BY SEC. 106.3.3 CITY
 AMENDMENTS TO FBC 2004.
  
 4- FLAT ROOF PRODUCT APPROVAL. PROVIDE RAS 117
 CALCULATIONS AS REQUIRED BY GENERAL LIMITATION #7 ON
 PAGE 26 AND 32 OF NOA 03-0501.02 SUBMITTED. (REPEAT
 COMMENT).
  
 5- STORM SHUTTERS INSTALLATION SCHEDULE:
 A) REVISESHUTTERS SPAN. THIS IS ASKING FOR PANEL
 LENGTH.IF PANELS ARE MOUNTED VERTICALLY HOW CAN THE
 PANELS BE 167" AND 25.5" .REVISE SIZE OF PANEL AS
 REQUIRED.
 NOTE: TAKE INTO CONSIDERATION THE MINIMUM EDGE DISTANCE
 REQUIRED.
  
 6- ENERGY CALCULATIONS:
 A) PROVIDE COMPLETE CALCULATIONS. ONLY TWO PAGES
 SUBMITTED. (REPEAT COMMENT).
  
 B) CLARIFY WHERE ARE THE FRAMED ADJACENT WALLS SHOWN
 ON ITEM #9 TAKEN FROM?. SEE PLANS. (REPEAT COMMENT).
  
 C) PROVIDE COMPLETE INFORMATION ON TOP OF FORM.
 (REPEAT COMMENT).
  
 D) OWNER/AGENT TO SIGN AND DATE BOTTOM OF FORM.
 (REPEAT COMMENT).
  
 7- CLARIFY IF ENERGY CALCULATIONS ARE DONE FOR ENTIRE
 HOUSE OF JUST FOR THE NEW ADDITION.CONDITIONED FLOOR
 AREA ON ITEMS #6 AND #10(A)NEED TO REFLECT THIS
 INFORMATION. ALSO,TAKE INTO CONSIDERATION THAT THAT
 PLANS DON'T SHOW ANY INFORMATION SHOWING COMPLIANCE
 WITH THE ENERGY CALCULATIONS FOR THE REST OF THE
 HOUSE.
  
 NOTE:FILLING OUT FORM 600C-04R IS MORE APPROPRIATE
 FOR THE ADDITION.
  
 8- ENERGY CALCULATIONS SUBMITTED ARE TAKEN THE CEILING
 FANS CREDIT.THEREFORE, PLANS NEED TO SHOW ALL ROOMS
 WITH CEILING FAN SIZE AS REQUIRED BY TABLE 13-607.1.A.1
 FBC 2004. (REPEAT COMMENT).
  
 9- SHEET A-3:ENGINEER IS CONFUSING ROOF SHEATHING
 FASTENING WITH FASTENING FOR FLAT ROOF ASSEMBLY. REVISE
 SPECIFICATIONS FOR FLAT ROOF ASSEMBLY. SEE FLAT ROOF
 PRODUCT APPROVAL AND SPECIFICAPPROVED ASSEMBLY AND
 REVISE SPECIFICATIONS AS REQUIRED.
 ***NOTE: THIS APPLIES TOFINISH ROOF SPECIFICATIONS ON
 WALL SECTION A-A ONSHEET GD.
  
 10- SHEET A-4:
 A) REVISE ROOF DESIGN PRESSURES. (REPEAT COMMENT).
 SEE TABLE R301.2(2)OF 2004 FLORIDA RESIDENTIAL CODE
 (OR TABLE 1609.6B FBC 2004).THIS IS A LOW SLOPE ROOF.
 NEED TO USE ROOF>0 TO 10 DEGREES CHART.
  
 B) THERE ARE NOT TRUSSES USED IN THIS PROJECT. OMIT
 ROOF TRUSS DESIGN LOAD INFORMATION TO AVOID CONFLICTS
 WITH INFORMATION SHOWN ON WIND LOAD DESIGN PARAMETERS.
  
 C) SPECIFY CONNECTOR FORALL 3X10 ROOF RAFTERS THAT
 ARE RESTING ON EXISTING MASONRY WALL, INCLUDING DOUBLE
 3X10 RAFTERS.THERE ARE NOT CONNECTORS SPECIFIED. SEE
 COMMENTS ON PLANS.
  
 D) SPECIFY HOW MUCH EMBEDMENT IS REQUIRED FOR RED
 HEAD ANCHORS SPECIFIED TO HOLD 2X6 AND 2X8 LEDGERS?.
 SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004 TO VERIFY
 COMPLIANCE WITHSEC. R301.
  
 E) FASTENER TYPE AND NUMBER SPECIFIED ON CONNECTOR
 SCHEDULE NEED TO MATCH INFORMATION SHOWN ON USP CURRENT
 CATALOG.OTHERWISE PROVIDE COMPLETE ENGINEERING
 ANALYSIS FOR FASTENER TYPE AND NUMBER THAT DIFFER FROM
 THOSE TESTED AND PUBLISHED BY THE MANUFACTURER.SEC.
 106.1.2 CITY AMENDMENTS TO FBC 2004 TO VERIFY
 COMPLIANCE WITH SEC. R301.
  
 F) SPECIFY HOW ARE 2X6 AND 2X8RAFTERS ATTACHED TO
 THE CORRESPONDING LEDGERS.CONNECTOR"A"DOESN'T
 APPLY TO THIS INSTALLATION. SEC. 106.1.2 CITY
 AMENDMENTS TO FBC 2004 TO VERIFY COMPLIANCE WITH SEC.
 R301.
  
 G) SPECIFY CONNECTORS AT BOTH ENDS FOR DOUBLE 2X8
 RAFTER. SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004 TO
 VERIFY COMPLIANCE WITH SEC. R301.
  
 H) SPECIFY HOWARE CONNECTORS "C" INSTALLED. SEE
 USP CATALOG FOR PROPER INSTALLATION.
 ALSO, ARE YOU PROPOSING TO INSTALL 2 CONNECTOR AT EACH
 RAFTER END.?
  
 I) WHERE IS DETAIL "B"/GD?.SHEET GD DOESN'T SHOW
 THIS DETAIL.
  
 J) PROVIDE DETAIL SHOWING HOW CONNECTOR "B"
 (JUS26-2) IS INSTALLED TO SUPPORT SINGLE 2X6 RAFTERS?.
 SEE USP CATALOG FOR SIZE SPECIFIED AND SIZE OF RAFTER.
  
 11- SHEET GD:
 A) REVISE ROOF SLOPE.PRODUCT APPROVAL SUBMITTED
 IS FOR A MODIFIED BITUMEN ROOFING. SEE SEC. R905.11.1
 AND REVISE SLOPE.
  
 B) REVISE ROOF SPECIFICATIONS. SEE ITEM #9 ABOVE.
  
 12- SHEET GN:
 A) REVISE DESIGN LOADS TO MATCH INFORMATION ON SHEET
 A-4. (REPEAT COMMENT).
  
 B) UPDATE ALL REFERENCED STANDARDS. SEE CHAPTER 43
 OF 2004 FLORIDA RESIDENTIAL CODE FOR SPECIFIC STANDARDS
 AND SPECIFIC YEAR TO BE REFERENCED. (REPEAT COMMENT).
 EG: SEE YEAR REFERENCED FOR ACI 318.. AND, CHECK ALL
 OTHER REFERENCES.
  
 C) PLYWOOD SHEATHING INFORMATION TO MATCH
 INFORMATION ON SHEET A-4. (REPEAT COMMENT). SEE TYPE OF
 FASTENER. 10D RING SHANK NAILS AND 10D NAILS ARE TWO
 DIFFERENT TYPE OF NAILS.
  
 D) SOIL STATEMENT NOTE #1 SPECIFIES 2000PSF SOIL
 BEARING CAPACITY. WHILENOTE #3 ON SAME PAGE CALLS FOR
 2500PSF SOIL BEARING CAPACITY. REVISE AS REQUIRED.
 ALSO, STRUCTURAL DETAILS CALL FOR 2500 BEARING
 CAPACITY.COORDINATE AND REVISE AS REQUIRED.
  
 E) REVISE MASONRY NOTE #1. SEE SEC. R606.4 OF 2004
 FLORIDA RESIDENTIAL CODE.PROVIDE SPECIFICATIONS FOR
 BLOCK COMPRESSIVE STRENGTH.NOTE SAYING TO COMPLY WITH
 SUCH SECTION IS NOT ACCEPTABLE.
  
 F) REVISE MASONRY NOTE #2. SEE ITEM 312(E) ABOVE.
 FM=1000PSI IS INCORRECT.
  
 13- PLEASE RETURN REVIEWED SET AFTER CORRECTIONS ARE
 DONE TO ORIGINAL DRAWINGS TO EXPEDITE REVIEW PROCESS.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712