 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 1} THE ENGINEERING FIRM LISTED ON THE TITLE BLOCK SHALL
 INDICATE THE CERTIFICATE OF AUTHORIZATIONNUMBER ALONG
 WITH OTHER INFORMATION REQUIRED BY 61G15-23.002 FLORIDA
 ADMINISTRATIVE CODE.
  
 2}PROVIDE A PANEL SCHEDULE PER 408.4 FOR THE SUB
 PANEL ON THE RISER.PLEASE SEE NEW VERBAGE FOR 2005
 NEC: "THE IDENTIFICATION SHALL INCLUDE SUFFICIENT
 DETAIL TO ALLOW EACH CIRCUIT TO BE DISTINGUISHED FROM
 ALL OTHERS."
  
 3} THE SUB PANEL DOES NOT HAVE A FEED LISTED FROM THE
 200 AMP PANEL, AS SHOWN ON THE RISER. INDICATE OCP,
 CONDUIT AND CONDUCTOR SIZE AND TYPE, ALSO GROUND PER
 250.122.
  
 4} THE SUB PANEL ON THE SEPARATE STRUCTURE MUST COMPLY
 WITH 225.31 DISCONNECTING MEANS AND 250.32 GROUNDING.
 INDICATE SAME ON THE RISER.
  
 5} VERIFY CIRCUITS 9,11 ARE #12 CONDUCTORS ON A 30 AMP
 OCP. SEE 430.72(B) AND 310.16.
  
 6} THE EQUIPMENT GROUND BETWEEN THE METER AND
 DISCONNECT ON THE RISER DIAGRAM CREATES A PARALLEL PATH
 TO GROUND WITH THE NEUTRAL AND MUST BE REMOVED. AN
 ISOLATED NEUTRAL AND EQUIPMENT GROUND ARE TO BE RAN
 FROM THE FIRST MEANS OF DISCONNECT. 250.6. IT IS SHOWN
 AS AN EXISTING SERVICE BUT MUST BE CORRECTED AS IT IS A
 LIFE SAFETY ISSUE. THERE IS A POTENTIAL OF ENERGIZING
 ALL METAL PARTS AND EQUIPMENT THE EQUIPMENT GROUNDS ARE
 CONNECTED TO.
  
 7} THE REFERENCE TO 230/240 REGARDING CALCULATIONS IS
 INCORRECT. SEE ARTICLE 220.83 IN THE 2005 NEC, ADOPTED
 DECEMBER 8, 2006. ALSO SEE NOTES 3 AND 7 ARE INCORRECT.
 CHANGE ALL REFERENCES TOCORRELATE WITH THE 2005 NEC
 TO AVOID CONFUSION IN THE FIELD AND FOR CLARITY IN
 RECORD RETENTION.
  
 8} R313.1.1 FBC RESIDENTIAL, SMOKE ALARMS SHALL BE
 LOCATED AS REQUIRED IN NEW DWELLINGS WHEN REPAIRS OR
 ADDITIONS REQUIRING A PERMIT OCCUR. SEE ARTICLE FOR
 COMPLETE TEXT.
  
 PLEASE REMOVE ALL OLD OR VOIDED SHEETS AND REPLACE
 WITH CORRECTED ONES WHEN RESUBMITTING. INCLUDE THEM
 SEPARATELY TO EXPEDITE THE REVIEW PROCESS.
  