Plan Review Notes
Plan Review Notes For Permit 07050817
Permit Number 07050817
Review Stop B
Sequence Number 1
Notes
Date Text
2007-06-28 17:59:46BUILDING REVIEW CHECKLIST:
 1- AFTER PLANS ARE REVISED, BRING THEM TO PALM BEACH
 COUNTY (2300 N. JOG RD (561)233-5115)TO VERIFY IF
 IMPACT FEES ARE DUE. BRING BACK STAMPED PLANS AND COPY
 OF PAID RECEIPT IF FEES ARE DUE.
  
 2- PROVIDE 2 COPIES OF PRODUCT APPROVALS (NONE
 SUBMITTED THIS TIME) AS REQUIRED BY DCA RULE 9B-72
 FOR:
 A) SINGLE HUNG WINDOWS.
 B) WINDOW MULLIONS.
 C) BEDROOM EXTERIOR DOOR.
 D) WORKSHOP DOUBLE DOOR
 E) WORKSHOP SINGLE DOOR.
 F) ROOF SHINGLES.
 G) ALL USP STRUCTURAL CONNECTORS SPECIFIED ON
 PLANS.
 H) PRECAST LINTELS.
 I) WORKSHOP LOUVER VENT SHOWN ON GABLE ENDS.
 J) SHUTTERS FOR WINDOWS AND DOORS WITH GLASS IF THEY
 DON'T HAVE HURRICANE MISSILE IMPACT GLAZING.AND,
 PROVIDE COMPLETE INSTALLATION SCHEDULE. SEE ATTACHED
 SAMPLE.ALSO, MARK ON SHUTTERS DRAWINGS SPECIFIC
 MOUNTING CONDITIONS (EG: WALL MOUNTED)AND SPECIFIC
 ANCHOR TYPE AND SPACING TO BE USED.
 K) FLAT ROOF ASSEMBLY. SEE ATTACHED COPY OF CITY
 POLICY FOR ROOFING PERMITS.CLEARLY SPECIFY APPROVED
 ASSEMBLY TO BE INSTALLED PLUS BASE SHEET FASTENING
 OPTION. ALSO, PROVIDE RAS 117 CALCULATIONS FOR NAIL
 ENHANCING AT PERIMETER AND CORNER AREAS AS REQUIRED BY
 GENERAL LIMITATION #7.ALSO, IF GENERAL LIMITATION #7
 REQUIRES RAS 117 CALCULATIONS DONE BY ANY OF THE
 PROFESSIONALS LISTED ON SUCH LIMITATION, THEN ONLY ONE
 OF THOSE PROFESSIONALS NEED TO DO THE CALCULATIONS. ON
 THE OTHER HAND IF SELECTED ASSEMBLY IS LIMITED BY
 GENERAL LIMITATION #9, THEN IT CAN'T BE USED IN THIS
 AREA BECAUSE THE DESIGN PRESSURES ARE TOO LOW FOR
 CORNER AND PERIMETER AREAS.
  
 3- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING)ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 106.3.3 CITY AMENDMENTSTO FBC 2004.
  
 4-ENGINEER NEEDS TO PROVIDE THE FIRM'S CERTIFICATE OF
 AUTHORIZATION NUMBER IN THE TITLE BLOCK AS REQUIRED BY
 CHAPTER471 FLORIDA STATUTE AND SEC. 61G15-23.002
 FLORIDA ADMINISTRATIVE CODE.
  
 5- PROVIDE COMPLETE WINDOW STRUCTURAL BUCK DETAIL AND
 SPECIFY ALL FASTENERS.SEE SEC. R613.6.2OF 2004
 FLORIDA RESIDENTIAL CODE FOR PROPER WAY OF INSTALLING
 THE BUCK.
  
 6- PROVIDE SOIL TEST REPORT. 2 COPIES WITH ORIGINAL
 SEAL AND SIGNATURE. NONE PROVIDED.
  
 7- SPECIFY FLAT ROOF ATTIC VENTILATION AND HOW CROSS
 VENTILATION IS PROVIDED AS REQUIRED BY SEC. R806 OF
 2004 FLORIDA RESIDENTIAL CODE.
  
 8- ENERGY CALCULATIONS:
 A) PROVIDE COMPLETE PACKAGE. ONLY TWO SHEETS
 SUBMITTED.
 B) CLARIFY WHERE ARE THE FRAMED ADJACENT WALLS
 SPECIFIED ON ITEM #9.
 C) PROVIDE COMPLETE INFORMATION ON TOP OF FORM.
 D) OWNER/AGENT TO SIGN AND DATE BOTTOM OF FORM.
  
 9) CEILING FAN CREDIT IS TAKEN, THEREFORE,PLANS NEED
 TO SHOW CEILING SIZE ON EACH ROOM AS REQUIRED BY TABLE
 13-607.1.A.1 OF FBC 2004.
  
 10- SPECIFY CONSTRUCTION TYPE AS REQUIRED BY SEC. 602.1
 FBC 2004.
  
 11- SHEET S.P 1:
 A) SQUARE FOOTAGE TABULATION IS CONFUSING AND IT
 DOESN'T ADD UP. PROVIDE SEPARATE CALCULATIONS FOR
 WORKSHOP AREA, AREA IN BEDROOM TO BE ADDED, TOTAL REAR
 PORCH, TOTAL FRONT PORCH , ETC. REVISE AS REQUIRED TO
 PROVIDE CLEAR TABULATION OF WHAT'S EXISTING AND WHAT IS
 NEW.
 B) ENGINEER TO SIGN AND SEAL THIS PAGE AS REQUIRED
 BY CHAPTER 471 FLORIDA STATUTE.
  
 12- SHEET A-2:
 A) SPECIFY SIZE OF ATTIC ACCESS LOCATED IN THE
 WORKSHOP BUILDING. SEC. R807 OF 2004 FLORIDA
 RESIDENTIAL CODE.
 B) COLUMN C-2 IS NOT CLEAR.8"X16" DOESN'T MATCH
 WHAT IS SHOWN IN THE COLUMN SCHEDULE OR ON FOUNDATION
 PLAN. REVISE/CLARIFY AS REQUIRED TO REFLECT CORRECT
 SPECIFICATIONS.
  
 13- SHEET A-3:
 A) SPECIFY SIZE OF LOUVER SHOWN ON WORKSHOP GABLE
 END. SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004.
 B) PROVIDE COMPLETE DETAILS/SPECS FOR SCREEN
 ENCLOSURE.SEC. 2002 OF FBC 2004.
 C) SPECIFICATIONS FOR FLAT ROOF ASSEMBLY ARE
 INCORRECT. SEE PRODUCT APPROVAL FOR FLAT ROOF SYSTEMS
 AND REVISE AS REQUIRED.
 ALSO, SEE ITEM 2(K) ABOVE.
  
 14- SHEET A-4:
 A) WIND LOAD DESIGN PARAMETERS:
 * INTERNAL PRESSURE COEFFICIENT AND PARTIAL ENCLOSED
 BUILDING DON'T CORRESPOND TO EACH OTHER. REVISE AS
 REQUIRED.
 ** REVISE ROOF DESIGN PRESSURES.SEE REVISED TABLE
 1609..6.2.1(2) OF 2004 AND REVISE AS REQUIRED. ALSO,
 REVISE DESIGN PRESSURES FOR 146 MPH AS SHOWN ON ROOF
 TRUSS DESIGN LOADS AND GENERAL STRUCTURAL NOTES ON
 SHEET GN.PROVIDE COMPLETE CALCULATIONS TO SHOW HOW
 THE DESIGN PRESSURES ARE CALCULATED. SEC. 106.1.2 CITY
 AMENDMENTS TO FBC 2004
 B) UPDATE ROOF TRUSS DESIGN LOAD CHART. CURRENT ASCE
 7 EDITION ADOPTED BY THE 2004 FBC IS THE 2002 EDITION,
 NOT 98. REVISE AS REQUIRED.
 C) PROVIDE COMPLETE INFORMATION AT FRONT PORCH
 AREA:
 * SPECIFY BEAMS. SEC. 106.1.2 CITY AMENDMENTS TO FBC
 2004.
 ** SPECIFY LEDGER SIZE AND ATTACHMENT TO THE EXISTING
 MASONRY WALL. CITY AMENDMENTS TO FBC 2004.
 D) SPECIFY ROOF SLOPE AS REQUIRED BY SEC. R905.9 AND
 R905.11 OF 2004 FLORIDA RESIDENTIAL CODE.
 E) WHERE ARE DETAILS B/A-5 AND B/A-6 KEYED ON ROOF
 FRAMING PLAN?
 F) SECTION A-AAND DETAIL B DON'T MATCH ROOF
 FRAMING PLAN.ARE THERE DOUBLE OUTLOOKERS?. IS THERE A
 GABLE END TRUSS?, ETC. REVISE AS REQUIRED TO MATCH. G)
 DETAIL B: PROVIDE COMPLETE INFORMATION FOR CONSTRUCTION
 BETWEEN WALL SHEATHING AND LAST GABLE END TRUSS.IS
 THIS A 2X6 WALL? PROVIDE COMPLETE SPECS AND FASTENERS.
 SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004. H) SECTION
 A-A:
 * SPECIFY RIDGE VENT SIZE. SEE SEC. R806 OF 2004
 FLORIDA RESIDENTIAL CODE.
  
 15- SHEET GD:
 A) WALL SECTION B-B:
 * REVISE FLAT ROOF SPECS. SEE ITEM 12(C) ABOVE.
 ** REVISE SIZE OF ROOF JOISTS. SEE ROOFFRAMING PLAN.
 B) WALL SECTION A-A:
 * FOOTING TO BE 12" MIN. BELOW GRADE AS REQUIRED BY
 SEC. R403.1.4 OF 2004 RESIDENTIAL CODE.IF FINISH
 FLOOR ELEVATION IS 6" ABOVE GRADE, THEN FOOTING WON'T
 BE 12" BELOW GRADE. REVISE AS REQUIRED.
 ** 1"X4" P.T. CONT. IS FIREBLOCKING, NOT "FIRE WALL".
 THESE ARE TWO DIFFERENT CODE ISSUES. REVISE AS
 REQUIRED.
 *** ROOF SHEATHING SPECS DON'TMATCH PLYWOOD SHEATHING
 NAILING SCHEDULE ON PAGE A-4 AND GENERAL NOTES ON SHEET
 GN. REVISE AS REQUIRED.
 **** OVERHANG LENGTH SHOWN IS 16" WHILE NOTE CALLS FOR
 24". REVISE AS REQUIRED TO MATCH.
 ***** CLARIFY MONOLITHIC FOOTING NOTE REGARDING THE 6"
 BELOW GRADE. SEE ITEM #14(B) ABOVE. REVISE/CLARIFY AS
 REQUIRED.
  
 16- SHEET GN:
 A) REVISE DESIGN LOADS TO MATCH INFORMATION ON SHEET
 A-4.
 *ALSO, UPDATE ASCE 7 EDITION. 2002.
 B) UPDATE ALLREFERENCED STANDARDS. SEE 2004
 FLORIDA RESIDENTAIL CODE FOR SPECIFIC STANDARDS TO BE
 USED AND CHAPTER 43 OF 2004 FLORIDA RESIDENTIAL CODE
 FOR SPECIFIC YEAR TO BE REFERENCED.
 C) PLYWOOD SHEATHING INFORMATION TO MATCH
 INFORMATION ON SHEET A-4.
 D) PROVIDE SOIL TEST REPORT SHOWING TYPE OF SOIL
 FOUND AS MENTIONED IN SOIL STATEMENT.
 E) REVISE MASONRY NOTE #1. SEE SEC. R606.4 OF 2004
 FLORIDA RESIDENTIALCODE FOR CORRECT INFORMATION.
  
  
 ***NOTE***
 PLEASE RETURN REVIEWED SET OF PLANS AFTER PLANS ARE
 REVISED TO EXPEDITE THE REVIEW PROCESS.
  
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712