| 2007-06-28 17:59:46 | BUILDING REVIEW CHECKLIST: |
| | 1- AFTER PLANS ARE REVISED, BRING THEM TO PALM BEACH |
| | COUNTY (2300 N. JOG RD (561)233-5115)TO VERIFY IF |
| | IMPACT FEES ARE DUE. BRING BACK STAMPED PLANS AND COPY |
| | OF PAID RECEIPT IF FEES ARE DUE. |
| | |
| | 2- PROVIDE 2 COPIES OF PRODUCT APPROVALS (NONE |
| | SUBMITTED THIS TIME) AS REQUIRED BY DCA RULE 9B-72 |
| | FOR: |
| | A) SINGLE HUNG WINDOWS. |
| | B) WINDOW MULLIONS. |
| | C) BEDROOM EXTERIOR DOOR. |
| | D) WORKSHOP DOUBLE DOOR |
| | E) WORKSHOP SINGLE DOOR. |
| | F) ROOF SHINGLES. |
| | G) ALL USP STRUCTURAL CONNECTORS SPECIFIED ON |
| | PLANS. |
| | H) PRECAST LINTELS. |
| | I) WORKSHOP LOUVER VENT SHOWN ON GABLE ENDS. |
| | J) SHUTTERS FOR WINDOWS AND DOORS WITH GLASS IF THEY |
| | DON'T HAVE HURRICANE MISSILE IMPACT GLAZING.AND, |
| | PROVIDE COMPLETE INSTALLATION SCHEDULE. SEE ATTACHED |
| | SAMPLE.ALSO, MARK ON SHUTTERS DRAWINGS SPECIFIC |
| | MOUNTING CONDITIONS (EG: WALL MOUNTED)AND SPECIFIC |
| | ANCHOR TYPE AND SPACING TO BE USED. |
| | K) FLAT ROOF ASSEMBLY. SEE ATTACHED COPY OF CITY |
| | POLICY FOR ROOFING PERMITS.CLEARLY SPECIFY APPROVED |
| | ASSEMBLY TO BE INSTALLED PLUS BASE SHEET FASTENING |
| | OPTION. ALSO, PROVIDE RAS 117 CALCULATIONS FOR NAIL |
| | ENHANCING AT PERIMETER AND CORNER AREAS AS REQUIRED BY |
| | GENERAL LIMITATION #7.ALSO, IF GENERAL LIMITATION #7 |
| | REQUIRES RAS 117 CALCULATIONS DONE BY ANY OF THE |
| | PROFESSIONALS LISTED ON SUCH LIMITATION, THEN ONLY ONE |
| | OF THOSE PROFESSIONALS NEED TO DO THE CALCULATIONS. ON |
| | THE OTHER HAND IF SELECTED ASSEMBLY IS LIMITED BY |
| | GENERAL LIMITATION #9, THEN IT CAN'T BE USED IN THIS |
| | AREA BECAUSE THE DESIGN PRESSURES ARE TOO LOW FOR |
| | CORNER AND PERIMETER AREAS. |
| | |
| | 3- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| | (NOT SIGNING AND SEALING)ALL PRODUCT APPROVALS AS |
| | REQUIRED BY SEC. 106.3.3 CITY AMENDMENTSTO FBC 2004. |
| | |
| | 4-ENGINEER NEEDS TO PROVIDE THE FIRM'S CERTIFICATE OF |
| | AUTHORIZATION NUMBER IN THE TITLE BLOCK AS REQUIRED BY |
| | CHAPTER471 FLORIDA STATUTE AND SEC. 61G15-23.002 |
| | FLORIDA ADMINISTRATIVE CODE. |
| | |
| | 5- PROVIDE COMPLETE WINDOW STRUCTURAL BUCK DETAIL AND |
| | SPECIFY ALL FASTENERS.SEE SEC. R613.6.2OF 2004 |
| | FLORIDA RESIDENTIAL CODE FOR PROPER WAY OF INSTALLING |
| | THE BUCK. |
| | |
| | 6- PROVIDE SOIL TEST REPORT. 2 COPIES WITH ORIGINAL |
| | SEAL AND SIGNATURE. NONE PROVIDED. |
| | |
| | 7- SPECIFY FLAT ROOF ATTIC VENTILATION AND HOW CROSS |
| | VENTILATION IS PROVIDED AS REQUIRED BY SEC. R806 OF |
| | 2004 FLORIDA RESIDENTIAL CODE. |
| | |
| | 8- ENERGY CALCULATIONS: |
| | A) PROVIDE COMPLETE PACKAGE. ONLY TWO SHEETS |
| | SUBMITTED. |
| | B) CLARIFY WHERE ARE THE FRAMED ADJACENT WALLS |
| | SPECIFIED ON ITEM #9. |
| | C) PROVIDE COMPLETE INFORMATION ON TOP OF FORM. |
| | D) OWNER/AGENT TO SIGN AND DATE BOTTOM OF FORM. |
| | |
| | 9) CEILING FAN CREDIT IS TAKEN, THEREFORE,PLANS NEED |
| | TO SHOW CEILING SIZE ON EACH ROOM AS REQUIRED BY TABLE |
| | 13-607.1.A.1 OF FBC 2004. |
| | |
| | 10- SPECIFY CONSTRUCTION TYPE AS REQUIRED BY SEC. 602.1 |
| | FBC 2004. |
| | |
| | 11- SHEET S.P 1: |
| | A) SQUARE FOOTAGE TABULATION IS CONFUSING AND IT |
| | DOESN'T ADD UP. PROVIDE SEPARATE CALCULATIONS FOR |
| | WORKSHOP AREA, AREA IN BEDROOM TO BE ADDED, TOTAL REAR |
| | PORCH, TOTAL FRONT PORCH , ETC. REVISE AS REQUIRED TO |
| | PROVIDE CLEAR TABULATION OF WHAT'S EXISTING AND WHAT IS |
| | NEW. |
| | B) ENGINEER TO SIGN AND SEAL THIS PAGE AS REQUIRED |
| | BY CHAPTER 471 FLORIDA STATUTE. |
| | |
| | 12- SHEET A-2: |
| | A) SPECIFY SIZE OF ATTIC ACCESS LOCATED IN THE |
| | WORKSHOP BUILDING. SEC. R807 OF 2004 FLORIDA |
| | RESIDENTIAL CODE. |
| | B) COLUMN C-2 IS NOT CLEAR.8"X16" DOESN'T MATCH |
| | WHAT IS SHOWN IN THE COLUMN SCHEDULE OR ON FOUNDATION |
| | PLAN. REVISE/CLARIFY AS REQUIRED TO REFLECT CORRECT |
| | SPECIFICATIONS. |
| | |
| | 13- SHEET A-3: |
| | A) SPECIFY SIZE OF LOUVER SHOWN ON WORKSHOP GABLE |
| | END. SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004. |
| | B) PROVIDE COMPLETE DETAILS/SPECS FOR SCREEN |
| | ENCLOSURE.SEC. 2002 OF FBC 2004. |
| | C) SPECIFICATIONS FOR FLAT ROOF ASSEMBLY ARE |
| | INCORRECT. SEE PRODUCT APPROVAL FOR FLAT ROOF SYSTEMS |
| | AND REVISE AS REQUIRED. |
| | ALSO, SEE ITEM 2(K) ABOVE. |
| | |
| | 14- SHEET A-4: |
| | A) WIND LOAD DESIGN PARAMETERS: |
| | * INTERNAL PRESSURE COEFFICIENT AND PARTIAL ENCLOSED |
| | BUILDING DON'T CORRESPOND TO EACH OTHER. REVISE AS |
| | REQUIRED. |
| | ** REVISE ROOF DESIGN PRESSURES.SEE REVISED TABLE |
| | 1609..6.2.1(2) OF 2004 AND REVISE AS REQUIRED. ALSO, |
| | REVISE DESIGN PRESSURES FOR 146 MPH AS SHOWN ON ROOF |
| | TRUSS DESIGN LOADS AND GENERAL STRUCTURAL NOTES ON |
| | SHEET GN.PROVIDE COMPLETE CALCULATIONS TO SHOW HOW |
| | THE DESIGN PRESSURES ARE CALCULATED. SEC. 106.1.2 CITY |
| | AMENDMENTS TO FBC 2004 |
| | B) UPDATE ROOF TRUSS DESIGN LOAD CHART. CURRENT ASCE |
| | 7 EDITION ADOPTED BY THE 2004 FBC IS THE 2002 EDITION, |
| | NOT 98. REVISE AS REQUIRED. |
| | C) PROVIDE COMPLETE INFORMATION AT FRONT PORCH |
| | AREA: |
| | * SPECIFY BEAMS. SEC. 106.1.2 CITY AMENDMENTS TO FBC |
| | 2004. |
| | ** SPECIFY LEDGER SIZE AND ATTACHMENT TO THE EXISTING |
| | MASONRY WALL. CITY AMENDMENTS TO FBC 2004. |
| | D) SPECIFY ROOF SLOPE AS REQUIRED BY SEC. R905.9 AND |
| | R905.11 OF 2004 FLORIDA RESIDENTIAL CODE. |
| | E) WHERE ARE DETAILS B/A-5 AND B/A-6 KEYED ON ROOF |
| | FRAMING PLAN? |
| | F) SECTION A-AAND DETAIL B DON'T MATCH ROOF |
| | FRAMING PLAN.ARE THERE DOUBLE OUTLOOKERS?. IS THERE A |
| | GABLE END TRUSS?, ETC. REVISE AS REQUIRED TO MATCH. G) |
| | DETAIL B: PROVIDE COMPLETE INFORMATION FOR CONSTRUCTION |
| | BETWEEN WALL SHEATHING AND LAST GABLE END TRUSS.IS |
| | THIS A 2X6 WALL? PROVIDE COMPLETE SPECS AND FASTENERS. |
| | SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004. H) SECTION |
| | A-A: |
| | * SPECIFY RIDGE VENT SIZE. SEE SEC. R806 OF 2004 |
| | FLORIDA RESIDENTIAL CODE. |
| | |
| | 15- SHEET GD: |
| | A) WALL SECTION B-B: |
| | * REVISE FLAT ROOF SPECS. SEE ITEM 12(C) ABOVE. |
| | ** REVISE SIZE OF ROOF JOISTS. SEE ROOFFRAMING PLAN. |
| | B) WALL SECTION A-A: |
| | * FOOTING TO BE 12" MIN. BELOW GRADE AS REQUIRED BY |
| | SEC. R403.1.4 OF 2004 RESIDENTIAL CODE.IF FINISH |
| | FLOOR ELEVATION IS 6" ABOVE GRADE, THEN FOOTING WON'T |
| | BE 12" BELOW GRADE. REVISE AS REQUIRED. |
| | ** 1"X4" P.T. CONT. IS FIREBLOCKING, NOT "FIRE WALL". |
| | THESE ARE TWO DIFFERENT CODE ISSUES. REVISE AS |
| | REQUIRED. |
| | *** ROOF SHEATHING SPECS DON'TMATCH PLYWOOD SHEATHING |
| | NAILING SCHEDULE ON PAGE A-4 AND GENERAL NOTES ON SHEET |
| | GN. REVISE AS REQUIRED. |
| | **** OVERHANG LENGTH SHOWN IS 16" WHILE NOTE CALLS FOR |
| | 24". REVISE AS REQUIRED TO MATCH. |
| | ***** CLARIFY MONOLITHIC FOOTING NOTE REGARDING THE 6" |
| | BELOW GRADE. SEE ITEM #14(B) ABOVE. REVISE/CLARIFY AS |
| | REQUIRED. |
| | |
| | 16- SHEET GN: |
| | A) REVISE DESIGN LOADS TO MATCH INFORMATION ON SHEET |
| | A-4. |
| | *ALSO, UPDATE ASCE 7 EDITION. 2002. |
| | B) UPDATE ALLREFERENCED STANDARDS. SEE 2004 |
| | FLORIDA RESIDENTAIL CODE FOR SPECIFIC STANDARDS TO BE |
| | USED AND CHAPTER 43 OF 2004 FLORIDA RESIDENTIAL CODE |
| | FOR SPECIFIC YEAR TO BE REFERENCED. |
| | C) PLYWOOD SHEATHING INFORMATION TO MATCH |
| | INFORMATION ON SHEET A-4. |
| | D) PROVIDE SOIL TEST REPORT SHOWING TYPE OF SOIL |
| | FOUND AS MENTIONED IN SOIL STATEMENT. |
| | E) REVISE MASONRY NOTE #1. SEE SEC. R606.4 OF 2004 |
| | FLORIDA RESIDENTIALCODE FOR CORRECT INFORMATION. |
| | |
| | |
| | ***NOTE*** |
| | PLEASE RETURN REVIEWED SET OF PLANS AFTER PLANS ARE |
| | REVISED TO EXPEDITE THE REVIEW PROCESS. |
| | |
| | |
| | JULIO GOMEZ |
| | BUILDING PLANS EXAMINER |
| | (561)805-6712 |