| Plan Review Notes For Permit 07050808 |
| Permit Number |
07050808 |
|
| Review Stop |
E |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2007-09-15 12:59:13 | 2007-09-15 12:59:13 | | | | | | *** PLANS REDLINED *** | | | | | | THE E-SHEETS STILL INDICATE A CONCRETE WALL FOR SUPPORT | | | AND STRUCTURAL MOUNTING FOR THE TRANSFORMER. THIS WAS | | | SPECIFICALLY NOTED ON PREVIOUS REVIEW TO CORRELATE WITH | | | THE ARCHITECTURAL AND STRUCTURAL SHEETS. THIS WAS NOT | | | DONE. | | | AS THE STRUCTURAL ENGINEER HAS PROVIDED A DETAIL WHICH | | | IS DESIGNED FOR THE SUPPORT, THE E-SHEET (2) WAS | | | REDLINED TO SEE THE DETAIL ON S-2. | | | ** ANY CHANGES ARE TO BE REVISED AND SUBMITTED. | | | ** ANY REVISIONS ARE TO BE DONE BEFORE ROUGH ELECTRICAL | | | INSPECTION. | | | ** AT NO TIME MAY A CEILING BE INSTALLED BELOW THE | | | TRANSFORMER ENCLOSING THIS ABOVE.THIS IS NOTED ON | | | PLANS FOR NO CEILING. |
|