Plan Review Notes
Plan Review Notes For Permit 07050808
Permit Number 07050808
Review Stop E
Sequence Number 3
Notes
Date Text
2007-09-15 12:59:132007-09-15 12:59:13
  
 *** PLANS REDLINED ***
  
 THE E-SHEETS STILL INDICATE A CONCRETE WALL FOR SUPPORT
 AND STRUCTURAL MOUNTING FOR THE TRANSFORMER. THIS WAS
 SPECIFICALLY NOTED ON PREVIOUS REVIEW TO CORRELATE WITH
 THE ARCHITECTURAL AND STRUCTURAL SHEETS. THIS WAS NOT
 DONE.
 AS THE STRUCTURAL ENGINEER HAS PROVIDED A DETAIL WHICH
 IS DESIGNED FOR THE SUPPORT, THE E-SHEET (2) WAS
 REDLINED TO SEE THE DETAIL ON S-2.
 ** ANY CHANGES ARE TO BE REVISED AND SUBMITTED.
 ** ANY REVISIONS ARE TO BE DONE BEFORE ROUGH ELECTRICAL
 INSPECTION.
 ** AT NO TIME MAY A CEILING BE INSTALLED BELOW THE
 TRANSFORMER ENCLOSING THIS ABOVE.THIS IS NOTED ON
 PLANS FOR NO CEILING.