Date Text
2007-09-20 08:16:22CITYPLACE STAR BUCKS
 650 S ROSEMARY AVE
 SEPT 20,2007
  
 BUILDING PLAN REVIEW
  
 PERMIT: 07050808
 ADD: 650 S ROSEMARY AVE
 CONT: PEMBERTON BUILDING
 TEL: (561)744-3399
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 3RDREVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 2) COMPLIED..
  
 3) NOTE:FL S S 713.13NOTICE OF COMMENCEMENT, TO BE
 FILED WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF
 THE WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS
 NOT ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE
 RECORDING THEREOF, SUCH NOTICE IS NULL & VOID. NOTE:
 713.13(6) THE POSTING OF THE NOTICE OF COMMENCEMENT AT
 THE CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 4) THIRD REQUEST, THE PRODUCT APPROVALS SUBMITTED
 REQUIRE FLORIDA COVERSHEETS. PRODUCT APPROVALS
 SUBMITTED WITH PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA PRODUCT
 APPROVAL SYSTEM. FOR INFORMATION PLEASE SEE THE STATE
 WEBSITE AT WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE SUBMITTED WITH A
 COVER SHEET THAT LISTS THE PRODUCT IDENTITY NUMBER FROM
 THE STATE. IF THE PRODUCT DOES NOT HAVE STATEWIDE
 APPROVAL, SUBMIT AN APPLICATION FOR LOCAL PRODUCT
 APPROVAL OR SITE SPECIFIC FORM PER RULE 9B-72. REPORTS
 MISSING THE FLORIDA APPROVAL COVERSHEETS ARE:
 4A) PGT SERIES **PW-701** IS A NON-IMPACT WINDOW,
 PROVIDE DOCUMENTATION THAT THE EXISTING SHUTTERS ARE
 RATED FOR THE 140 MPH WIND ZONE & LARGE MISSILE
 TESTED.
 4B) PGT SERIES HR-810 IS A HORIZONTAL ROLLER NOT USED
 SEE SHEET G2.0
 4C) FIXED WINDOW- SHEET G2.0 INDICATES NEW LARGE
 MISSILE RATED NO REPORTS SUBMITTED.
 4D) FIREDOOR SERIES 4080 SINGLE
 4E FIREDOOR SERIES S-6070
  
 5) COMPLIED.
  
 6-8) COMPLIED.
  
 9A)TRANSFORMER MOUNT THERE IS A DISCREPANCY BETWEEN
 THE STRUCTURAL SHEET S2 AND THE ELECTRICAL SHEET E2.
 THE UPDATED S2 DOES NOW SHOW STEEL TUBING TO HANDLE THE
 LOADS OF THE BRAKET CARRYING THE TRANSFORMERS WEIGHT
 BUT THE E2 SHEET NEEDS TO CORRELATE THE THE SAME TYPE
 OF STRUCTURAL SUPPORT FORTHIS UNIT. DISCREPANCY BETWEEN
 PLANS, 106.1.2*
  
 9B) THE SECOND ISSUE IS THE DRYWALL RUNS BEHIND
 BRACKET, THERE WOULD APPEAR TO BE CRUSHING CONCERNS
 THIS PORTION OF WALL WILL QUICKLY BE CRUSHED AND THE
 BRACKET BECOMING LOOSE! 106.1.2*?
 102.1* WHERE, IN ANY SPECIFIC CASE, DIFFERENT SECTIONS
 OF THIS CODE SPECIFY DIFFERENT MATERIALS, METHODS OF
 CONSTRUCTION OR OTHER REQUIREMENTS, THE MOST
 RESTRICTIVE SHALL GOVERN. WHERE THERE IS A CONFLICT
 BETWEEN A GENERAL REQUIREMENT AND A SPECIFIC
 REQUIREMENT, THE SPECIFIC
 REQUIREMENT SHALL BE APPLICABLE.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
  
  
  
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
  
  
  
  
  
  