| 2007-08-26 18:13:03 | 2007-08-26 18:13:03 |
| | |
| | ** DENIED 2ND REVIEW ** |
| | |
| | ** PLEASE SEE SOME COMMENTS FROM THE PREVIOUS REVIEW |
| | ARE IN NEED OF ADDRESSING ALONG WITH SOME NEW COMMENTS |
| | BASED ON THE PLANS AND DOCUMENTS SUBMITTED AND |
| | REVISIONS MADE TO PLANS WHICH WERE NOT ON PREVIOUS |
| | SUBMITTED PLANS. |
| | |
| | ** PLEASE BE SURE ALL NEW REVISED SHEETS CONTAINS THE |
| | REQUIRED CITY PLACE REVIEW STAMP.OLD/VOIDED SHEETS |
| | WIHT THE STAMP WILL NOT BE ACCEPTED IN LIEU OF THE |
| | REVISED SHEETS CONTAINING NEW STAMPS. |
| | |
| | |
| | 1) NOTE:PLEASE SEE AS REQUESTED ON THE PREVIOUS |
| | REVIEW: |
| | PLEASE SUBMIT TWO COMPLETE SETS WITH ALL SHEETS IN |
| | ORDER AS STATED ON COVER SHEET. |
| | PLEASE SEE THE END OF THE PREVIOUS REVIEW AND NOTE #1 |
| | FROM PREVIOUS REQUESTED ALL OLD/VOIDED SHEETS TO BE |
| | REMOVED FROM SETS AND ONLY INCLUDE NEW REVISED SHEETS |
| | IN SETS. |
| | THE REVIEW ALSO REQUESTED NOT TO ATTACH PRODUCT |
| | APPROVALS/ ENERGY CALCULATIONS AND SUPPORTING DOCUMENTS |
| | DOWN THE LEFT SIDE OF PLANS. THESE SHOULD BE ATTACHED |
| | INTO TWO SETS BOUND TOGETHER IN SOME FASHION.THESE |
| | MAY BE PLACED IN SPIRAL BOOK OR OTHER FOLDER OF SOME |
| | TYPE LABELED/TABBED FOR EASE OF REVIEW IN EXPEDITING |
| | THE PLAN REVIEW PROCESS. |
| | ** PLEASE SEE NOTE BELOW LABELED AS IMPORTANT. |
| | |
| | ** THE DOCUMENTS WHICH WERE ATTACHED DOWN THE LEFT SIDE |
| | OF PLANS WERE REMOVED. |
| | |
| | 2) NOTE: PLEASE SUBMIT ENERGY CALCULATIONS WHICH ARE |
| | SIGNED DATED AND SEALED AS REQUIRED PER FAC |
| | 61G15-23.002, FS 471.025 AND FBC 13-103.1.1.1. PLEASE |
| | CLARIFY HOW THE TOTAL LPD ON THE CALCULATIONS IS |
| | DIFFERENT THAN THAT STATED ON THE PLANS. |
| | 13-415.2, 13-415.1.C |
| | |
| | 3) NOTE: PLEASE SEE THE RISER HAS BEEN REVISED FOR THE |
| | TRANSFORMER HOWEVER NO GROUNDING ELECTRODE SYSTEM IS |
| | SHOWN? |
| | PLEASE SEE 250.50, 250.20, 250.30, 250.66 ETC. |
| | |
| | 4) NOTE: PLEASE SEE THE STRUCTURAL DETAIL SUBMITTED IS |
| | OK, HOWEVER SHOULD BE REVIEWED BY THE |
| | ARCHITECT/STRUCTURAL ENGINEER AND SIGNED AS REVIEWED |
| | FOR ADEQUATE SUPPORT. |
| | THE REVISIONS TO THE ARCHITECTURAL PLANS SHOULD INCLUDE |
| | ANY REVISIONS FOR FILLED CELLS AS STATED ON DETAIL. |
| | PLEASE SEE THE ARCHITECTURAL SHEETS INDICATE THIS WALL |
| | AS METAL STUDS, NO POUR CONCRETE AS STATED ON |
| | E-SHEETS. |
| | PLEASE PROVIDE A STRUCTURAL SUPPORTING DETAIL FOR THE |
| | 75KVA WALL MOUNTED TRANSFORMER. |
| | PLEASE PROVIDE ELEVATION DETAIL TO MEET 110.26A3 PLEASE |
| | ALSO SEE 450.13 AND PROVIDE A NOTE THAT EQUIPMENT MAY |
| | NOT BE INSTALLED ABOVE CEILING LINE. FBC 106.1.2. |
| | |
| | 5) NOTE: PLEASE SEE 210.8B2 FOR REQUIRED GFI PROTECTION |
| | FOR 15/20A 120V CIRCUITS IN KITCHEN AREA(S). |
| | THIS NOTE REMAINS AS THE PLANS ARE SIMPLY ONLY STATING |
| | THE CODE IN LIEU OF SHOWING AND INDICATING THE ACTUAL |
| | PROTECTION EITHER BY WAY AT THE DEVICE LOCATION OR |
| | BREAKERS IN PANELS. |
| | PLEASE SEE FBC 106.1.1, 106.1.2, 106.3.5.1.2 WHICH |
| | REQUIRES DETAIL(S) TO BE SHOWN. |
| | PLEASE ADJUST. |
| | |
| | 6) NOTE: AS REQUESTED ON PREVIOUS REVIEW: |
| | PLEASE SEE THE APPLIED ADDRESS DOES NOT MATCH WITH |
| | PLANS. |
| | PLEASE SEE ANY COMMENTS FROM OTHER TRADES. PLANS WILL |
| | BE FORWARDED TO THE ADDRESSING REVIEW FOR COMMENTS. |
| | PLEASE BE SURE ALL TITLE BLOCKS CONTAIN THE CORRECTED |
| | ADDRESS ALONG WITH PERMIT APPLICATION. |
| | FAC 61G1-16.004 |
| | ** THIS IS THE SAME COMMENT AS THE APPLIED ADDRESS AND |
| | LOCATION IS 650 S ROSEMARY WHEREAS THE PLANS STATE 600 |
| | S ROSEMARY. |
| | |
| | ** PLEASE SEE ANY POSSIBLE COMMENTS FROM OTHER TRADES |
| | WHICH MAY AFFECT ELECTRICAL PLANS. |
| | |
| | AS STATED IN THE PREVIOUS REVIEWS: |
| | PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |