Plan Review Notes
Plan Review Notes For Permit 07050808
Permit Number 07050808
Review Stop E
Sequence Number 2
Notes
Date Text
2007-08-26 18:13:032007-08-26 18:13:03
  
 ** DENIED 2ND REVIEW **
  
 ** PLEASE SEE SOME COMMENTS FROM THE PREVIOUS REVIEW
 ARE IN NEED OF ADDRESSING ALONG WITH SOME NEW COMMENTS
 BASED ON THE PLANS AND DOCUMENTS SUBMITTED AND
 REVISIONS MADE TO PLANS WHICH WERE NOT ON PREVIOUS
 SUBMITTED PLANS.
  
 ** PLEASE BE SURE ALL NEW REVISED SHEETS CONTAINS THE
 REQUIRED CITY PLACE REVIEW STAMP.OLD/VOIDED SHEETS
 WIHT THE STAMP WILL NOT BE ACCEPTED IN LIEU OF THE
 REVISED SHEETS CONTAINING NEW STAMPS.
  
  
 1) NOTE:PLEASE SEE AS REQUESTED ON THE PREVIOUS
 REVIEW:
 PLEASE SUBMIT TWO COMPLETE SETS WITH ALL SHEETS IN
 ORDER AS STATED ON COVER SHEET.
 PLEASE SEE THE END OF THE PREVIOUS REVIEW AND NOTE #1
 FROM PREVIOUS REQUESTED ALL OLD/VOIDED SHEETS TO BE
 REMOVED FROM SETS AND ONLY INCLUDE NEW REVISED SHEETS
 IN SETS.
 THE REVIEW ALSO REQUESTED NOT TO ATTACH PRODUCT
 APPROVALS/ ENERGY CALCULATIONS AND SUPPORTING DOCUMENTS
 DOWN THE LEFT SIDE OF PLANS. THESE SHOULD BE ATTACHED
 INTO TWO SETS BOUND TOGETHER IN SOME FASHION.THESE
 MAY BE PLACED IN SPIRAL BOOK OR OTHER FOLDER OF SOME
 TYPE LABELED/TABBED FOR EASE OF REVIEW IN EXPEDITING
 THE PLAN REVIEW PROCESS.
 ** PLEASE SEE NOTE BELOW LABELED AS IMPORTANT.
  
 ** THE DOCUMENTS WHICH WERE ATTACHED DOWN THE LEFT SIDE
 OF PLANS WERE REMOVED.
  
 2) NOTE: PLEASE SUBMIT ENERGY CALCULATIONS WHICH ARE
 SIGNED DATED AND SEALED AS REQUIRED PER FAC
 61G15-23.002, FS 471.025 AND FBC 13-103.1.1.1. PLEASE
 CLARIFY HOW THE TOTAL LPD ON THE CALCULATIONS IS
 DIFFERENT THAN THAT STATED ON THE PLANS.
 13-415.2, 13-415.1.C
  
 3) NOTE: PLEASE SEE THE RISER HAS BEEN REVISED FOR THE
 TRANSFORMER HOWEVER NO GROUNDING ELECTRODE SYSTEM IS
 SHOWN?
 PLEASE SEE 250.50, 250.20, 250.30, 250.66 ETC.
  
 4) NOTE: PLEASE SEE THE STRUCTURAL DETAIL SUBMITTED IS
 OK, HOWEVER SHOULD BE REVIEWED BY THE
 ARCHITECT/STRUCTURAL ENGINEER AND SIGNED AS REVIEWED
 FOR ADEQUATE SUPPORT.
 THE REVISIONS TO THE ARCHITECTURAL PLANS SHOULD INCLUDE
 ANY REVISIONS FOR FILLED CELLS AS STATED ON DETAIL.
 PLEASE SEE THE ARCHITECTURAL SHEETS INDICATE THIS WALL
 AS METAL STUDS, NO POUR CONCRETE AS STATED ON
 E-SHEETS.
 PLEASE PROVIDE A STRUCTURAL SUPPORTING DETAIL FOR THE
 75KVA WALL MOUNTED TRANSFORMER.
 PLEASE PROVIDE ELEVATION DETAIL TO MEET 110.26A3 PLEASE
 ALSO SEE 450.13 AND PROVIDE A NOTE THAT EQUIPMENT MAY
 NOT BE INSTALLED ABOVE CEILING LINE. FBC 106.1.2.
  
 5) NOTE: PLEASE SEE 210.8B2 FOR REQUIRED GFI PROTECTION
 FOR 15/20A 120V CIRCUITS IN KITCHEN AREA(S).
 THIS NOTE REMAINS AS THE PLANS ARE SIMPLY ONLY STATING
 THE CODE IN LIEU OF SHOWING AND INDICATING THE ACTUAL
 PROTECTION EITHER BY WAY AT THE DEVICE LOCATION OR
 BREAKERS IN PANELS.
 PLEASE SEE FBC 106.1.1, 106.1.2, 106.3.5.1.2 WHICH
 REQUIRES DETAIL(S) TO BE SHOWN.
 PLEASE ADJUST.
  
 6) NOTE: AS REQUESTED ON PREVIOUS REVIEW:
 PLEASE SEE THE APPLIED ADDRESS DOES NOT MATCH WITH
 PLANS.
 PLEASE SEE ANY COMMENTS FROM OTHER TRADES. PLANS WILL
 BE FORWARDED TO THE ADDRESSING REVIEW FOR COMMENTS.
 PLEASE BE SURE ALL TITLE BLOCKS CONTAIN THE CORRECTED
 ADDRESS ALONG WITH PERMIT APPLICATION.
 FAC 61G1-16.004
 ** THIS IS THE SAME COMMENT AS THE APPLIED ADDRESS AND
 LOCATION IS 650 S ROSEMARY WHEREAS THE PLANS STATE 600
 S ROSEMARY.
  
 ** PLEASE SEE ANY POSSIBLE COMMENTS FROM OTHER TRADES
 WHICH MAY AFFECT ELECTRICAL PLANS.
  
 AS STATED IN THE PREVIOUS REVIEWS:
 PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
  