Plan Review Notes
Plan Review Notes For Permit 07050808
Permit Number 07050808
Review Stop B
Sequence Number 2
Notes
Date Text
2007-08-27 08:44:33BUILDING PLAN REVIEW
  
 PERMIT: 07050808
 ADD: 650 S ROSEMARY AVE
 CONT: PEMBERTON BUILDING
 TEL: (561)744-3399
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 2NDREVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 2) COMPLIED..
  
 3) NOTE:FL S S 713.13NOTICE OF COMMENCEMENT, TO BE
 FILED WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF
 THE WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS
 NOT ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE
 RECORDING THEREOF, SUCH NOTICE IS NULL & VOID. NOTE:
 713.13(6) THE POSTING OF THE NOTICE OF COMMENCEMENT AT
 THE CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 4) 2ND REQUEST, THE PRODUCT APPROVALS SUBMITTED REQUIRE
 FLORIDA COVERSHEETS. PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003 ARE REQUIRED
 TO COMPLY WITH THE FLORIDA PRODUCT APPROVAL SYSTEM. FOR
 INFORMATION PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH STATEWIDE
 APPROVAL ARE REQUIRED TO BE SUBMITTED WITH A COVER
 SHEET THAT LISTS THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE STATEWIDE APPROVAL,
 SUBMIT AN APPLICATION FOR LOCAL PRODUCT APPROVAL OR
 SITE SPECIFIC FORM PER RULE 9B-72. REPORTS MISSING THE
 FLORIDA APPROVAL COVERSHEETS ARE:
 4A) PGT SERIES **PW-701**
 4B) PGT SERIES HR-810
 4C) FIREDOOR SERIES 4080 SINGLE
 4D) FIREDOOR SERIES S-6070
  
 5) COMPLIED.
  
 6) SHEET G1.0 SITE INFO:
 6A) 2ND REQUEST, PLEASE SEE THAT PLANS SUBMITTED AFTER
 DEC. 8/ 2006 WILL BE REVIEWED TO THE 2006 FBC, AND THE
 2006 FBC EXISTING BUILDING CODE. PLEASE INDICATE TO
 WHAT LEVEL YOU WILL BE DOING ALTERATIONS UNDER THE
 SCOPE OF THIS PERMIT?
  
 6B) ENERGY CODE WILL BE REVIEWED UNDER THE 2006 FBC,
 CHAPTER 13- 400 COMMERCIAL
  
 6C) COMPLIED.
  
 6D)SHEET G1.0 2ND REQUEST, TYPE OF OCCUPANCY SEE: 302.1
 GENERAL.STRUCTURES OR PORTIONS OF STRUCTURES SHALL BE
 CLASSIFIED WITH RESPECT TO OCCUPANCY IN ONE OR MORE OF
 THE GROUPS LISTED BELOW.
  
 6E) TYPE OF CONSTRUCTION: 503.1 GENERAL.THE HEIGHT
 AND AREA FOR BUILDINGS OF DIFFERENT CONSTRUCTION TYPES
 SHALL BE GOVERNED BY THE INTENDED USE OF THE BUILDING
 AND SHALL NOT EXCEED THE LIMITS IN TABLE 503 EXCEPT AS
 MODIFIED HEREAFTER PROVIDE THE MINIMUM BUILDING TYPE
 FOR THIS STRUCTURE.
  
 7) COMPLIED.
  
 8) COMPLIED.
  
 9) NEW COMMENT: SHEETE.2 TRANSFORMER MOUNT DETAIL
 INDICATES THAT TRANSFORMER BRACKET IS TO USE (2) ??
 WITH 6? EMBEDMENT INTO FILLED WALL CELLS (CMU). SHEET
 A2.0 INDICATES THIS WALL TO BE A TYPE# 23 5/8? 20G
 METAL STUD WITH5/8? GREEN BOARD . PLEASE CORRECT
 DETAIL.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
  
  
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]