| 2007-08-27 08:44:33 | BUILDING PLAN REVIEW |
| | |
| | PERMIT: 07050808 |
| | ADD: 650 S ROSEMARY AVE |
| | CONT: PEMBERTON BUILDING |
| | TEL: (561)744-3399 |
| | |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | W/ 2006 FBC REVISIONS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 2NDREVIEW |
| | ACTION: DENIED |
| | |
| | 1)--- VERY IMPORTANT STATEMENT --- |
| | PLEASE DO NOT IGNORE! |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL |
| | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH |
| | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE |
| | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE |
| | FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR |
| | YOUR ANTICIPATED COOPERATION. |
| | |
| | 2) COMPLIED.. |
| | |
| | 3) NOTE:FL S S 713.13NOTICE OF COMMENCEMENT, TO BE |
| | FILED WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF |
| | THE WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS |
| | NOT ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE |
| | RECORDING THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: |
| | 713.13(6) THE POSTING OF THE NOTICE OF COMMENCEMENT AT |
| | THE CONSTRUCTION SITE BEFORE THE FIRST INSPECTION. |
| | |
| | 4) 2ND REQUEST, THE PRODUCT APPROVALS SUBMITTED REQUIRE |
| | FLORIDA COVERSHEETS. PRODUCT APPROVALS SUBMITTED WITH |
| | PERMIT APPLICATION AFTER OCTOBER 1, 2003 ARE REQUIRED |
| | TO COMPLY WITH THE FLORIDA PRODUCT APPROVAL SYSTEM. FOR |
| | INFORMATION PLEASE SEE THE STATE WEBSITE AT |
| | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH STATEWIDE |
| | APPROVAL ARE REQUIRED TO BE SUBMITTED WITH A COVER |
| | SHEET THAT LISTS THE PRODUCT IDENTITY NUMBER FROM THE |
| | STATE. IF THE PRODUCT DOES NOT HAVE STATEWIDE APPROVAL, |
| | SUBMIT AN APPLICATION FOR LOCAL PRODUCT APPROVAL OR |
| | SITE SPECIFIC FORM PER RULE 9B-72. REPORTS MISSING THE |
| | FLORIDA APPROVAL COVERSHEETS ARE: |
| | 4A) PGT SERIES **PW-701** |
| | 4B) PGT SERIES HR-810 |
| | 4C) FIREDOOR SERIES 4080 SINGLE |
| | 4D) FIREDOOR SERIES S-6070 |
| | |
| | 5) COMPLIED. |
| | |
| | 6) SHEET G1.0 SITE INFO: |
| | 6A) 2ND REQUEST, PLEASE SEE THAT PLANS SUBMITTED AFTER |
| | DEC. 8/ 2006 WILL BE REVIEWED TO THE 2006 FBC, AND THE |
| | 2006 FBC EXISTING BUILDING CODE. PLEASE INDICATE TO |
| | WHAT LEVEL YOU WILL BE DOING ALTERATIONS UNDER THE |
| | SCOPE OF THIS PERMIT? |
| | |
| | 6B) ENERGY CODE WILL BE REVIEWED UNDER THE 2006 FBC, |
| | CHAPTER 13- 400 COMMERCIAL |
| | |
| | 6C) COMPLIED. |
| | |
| | 6D)SHEET G1.0 2ND REQUEST, TYPE OF OCCUPANCY SEE: 302.1 |
| | GENERAL.STRUCTURES OR PORTIONS OF STRUCTURES SHALL BE |
| | CLASSIFIED WITH RESPECT TO OCCUPANCY IN ONE OR MORE OF |
| | THE GROUPS LISTED BELOW. |
| | |
| | 6E) TYPE OF CONSTRUCTION: 503.1 GENERAL.THE HEIGHT |
| | AND AREA FOR BUILDINGS OF DIFFERENT CONSTRUCTION TYPES |
| | SHALL BE GOVERNED BY THE INTENDED USE OF THE BUILDING |
| | AND SHALL NOT EXCEED THE LIMITS IN TABLE 503 EXCEPT AS |
| | MODIFIED HEREAFTER PROVIDE THE MINIMUM BUILDING TYPE |
| | FOR THIS STRUCTURE. |
| | |
| | 7) COMPLIED. |
| | |
| | 8) COMPLIED. |
| | |
| | 9) NEW COMMENT: SHEETE.2 TRANSFORMER MOUNT DETAIL |
| | INDICATES THAT TRANSFORMER BRACKET IS TO USE (2) ?? |
| | WITH 6? EMBEDMENT INTO FILLED WALL CELLS (CMU). SHEET |
| | A2.0 INDICATES THIS WALL TO BE A TYPE# 23 5/8? 20G |
| | METAL STUD WITH5/8? GREEN BOARD . PLEASE CORRECT |
| | DETAIL. |
| | |
| | BUILDING PLAN REVIEW |
| | JIM WITMER C. B. O. |
| | |
| | |
| | |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |
| | E-MAIL: [email protected] |