| Notes |
| Date |
Text |
| 2007-06-20 16:06:50 | DENIED | | | REFERENCE: FBC-2004 PLUMBING | | | FBC-2004 CHAPTER 1 | | | | | | 1. SHT A0.0 NOTES #8 IN THE REMOVAL OF ANY PART OF A | | | DRAINAGE SYSTEM, DEAD ENDS ARE PROHIBITED. SECTION | | | 704.5. ALL DEMO'D/CAPPED PIPES SHALL BE LEFT UNCOVERED | | | UNITL INSPECTED AND APPROVED BY FIELD INSPECTOR. | | | | | | 2. SHT P2.0INDICATES REVERSE OSMOSIS FILTER. FILTER | | | SHALL MEET THE REQUIREMENTS OF NSF-58. PLEASE SUBMIT | | | MANUF. SPECIFICATIONS SHOWING COMPLIANCE. SECTION | | | 611.2. | | | | | | 3. SHT P3.0 NOTES #'S 1 & 2 INDICATE INDIRECT WASTE TO | | | A FLOOR DRAIN. FLOOR DRAINS ARE NOT APPROVED INDIRECT | | | WASTE RECEPTORS. INDIRECT WASTE SHALL DRAIN TO A FLOOR | | | SINK OR A HUB DRAIN PER SECTIONS 802.3 & 802.3.2. | | | PLEASE CHANGE REFERENCES. | | | | | | 4. SHT P3.0 NOTE # 24 INDICATES AN AAV. THESE ARE NOT | | | SHOWN ON THE RISER DIAGRAM OR FLOOR PLAN, AND ARE NOT | | | NEEDED IN A COMBINATION WASTE & VENT SYSTEM PER SECTION | | | 912.2.2.PLEASE DELETE REFERENCE FROM FLOOR PLAN & | | | NOTES. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] |
|