| Notes |
| Date |
Text |
| 2007-06-21 10:11:06 | ***************PROVISO**************** | | | PLEASE PROVIDE A SOCONDARY OR AUXILIARY DRAIN | | | PROTECTION SYSTEM PER FBC,M 307.2.3: | | | | | | A SECONDARY DRAIN OR AUXILIARY DRAIN PAN SHALL BE | | | REQUIRED FOR EACH COOLING OR EVAPORATOR COIL WHERE | | | DAMAGE TO ANY BUILDING COMPONENTS WILL OCCUR AS A | | | RESULT OF OVERFLOW FROM THE EQUIPMENT DRAIN PAN OR | | | STOPPAGE IN THE CONDENSATE DRAIN PIPING. | | | | | | RONALD J REGUEIRO | | | 561.805.6719 | | | [email protected] |
|