| 2007-07-10 12:15:52 | *****DENIED***** |
| | |
| | |
| | 1.THE APPLICABLE CODES SHALL BE REFERENCED:FIRE |
| | CODE - FLORIDA FIRE PREVENTION CODE (2004 EDITION); |
| | LIFE SAFETY - NFPA 101 (2003 EDITION). |
| | |
| | 2.PLEASE EXPLAIN THE NUMERICAL ADDRESS DIFFERENCE. |
| | THE PERMIT APPLICATION HAS 650 SOUTH ROSEMARY WHEREAS |
| | THE SUBMITTED PLANS HAVE 600 SOUTH ROSEMARY AVENUE. |
| | PLEASE BE ADVISED THAT THE CORRECT ADDRESS FOR THIS |
| | PROJECT SHALL BE IN THE TITLE BLOCK OF EACH SUBMITTED |
| | PLAN SHEET. |
| | |
| | 3.ON SHEET G2.0, SITE LOCATION MAP, REFERENCE IS MADE |
| | TO ROSEMARY PLAZA.WHAT/WHERE IS ROSEMARY PLAZA? |
| | |
| | 4.DEMOLITION OR CONSTRUTION OPERATIONS SHALL NOT |
| | INTERFERE OR HINDER EMERGENCY ACCESS RESPONSE TO THE |
| | PROPERTY OR VICINITY THEREOF (INCLUDING STREETS, FIRE |
| | LANES). |
| | |
| | 5.ON THE APPROPIATE EXTERIOR ELEVATION, POST THE |
| | NUMERICAL ADDRESS VISIBLE FROM SOUTH ROSEMARY AVENUE. |
| | AS PER WEST PALM BEACH CODE, THOSE NUMBERS SHALL BE NO |
| | LESS THAN 6" IN HEIGHT AND NO LESS THAN 1" IN WIDTH. |
| | |
| | 6.SPECIFY THE INTERIOR WALL AND CEILING FINISH |
| | MATERIALS IN TERMS OF CLASS A, CLASS B, OR CLASS C. |
| | |
| | 7.SHOW THE LOCATION OF THE 2A:10BC RATED FIRE |
| | EXTINGUISHER(S) WHICH SATISFY THE 75' TRAVEL DISTANCE. |
| | |
| | |
| | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE |
| | LETTER INDICATING WHERE ON THE PLAN EACH ITEM WAS |
| | ADDRESSED |
| | |
| | |
| | CAPT. MICHAEL A. WILLIAMS |
| | FIRE PLAN REVIEW |