Plan Review Notes
Plan Review Notes For Permit 07050808
Permit Number 07050808
Review Stop E
Sequence Number 1
Notes
Date Text
2007-06-19 12:44:01*** UNSAT ***
  
 1) NOTE: PLEASE SUBMIT TWO COMPLETE SETS WITH ALL
 SHEETS IN ORDER AS STATED ON COVER SHEET. PLEASE SEE
 ELECTRICAL AND PLUMBING PLANS ARE MIXED.
 PLEASE ALSO DO NOT ATTACH PRODUCT APPROVALS/ ENERGY
 CALCULATIONS AND SUPPORTING DOCUMENTS DOWN THE LEFT
 SIDE OF PLANS. THESE SHOULD BE ATTACHED INTO TWO SETS
 BOUND TOGETHER IN SOME FASHION.THESE MAY BE PLACED IN
 SPIRAL BOOK OR OTHER FOLDER OF SOME TYPE LABELED/TABBED
 FOR EASE OF REVIEW IN EXPEDITING THE PLAN REVIEW
 PROCESS.
 ** PLEASE SEE NOTE BELOW LABELED AS IMPORTANT.
  
 2) NOTE: PLEASE BE SURE PLANS THE CURRENT CODES AS
 FOLLOWS.
 2004 FBC W/2006 REVISIONS.
 2005 NFPA-70
 2003 NFPA-101
 ** PLEASE SEE POSSIBLE COMMENTS FROM OTHER TRADES WHICH
 MAY REQUIRE OTHER CODES.
 THESE SECTIONS SHOULD ALSO BE STATED ON ELECTRICAL
 PLANS AS WELL AS PROJECT COVER SHEET.
  
 3) NOTE: PLEASE SUBMIT ENERGY CALCULATIONS AS ADOPTED
 BY FBC 2004 W/2006 REVISIONS.13-415.1.C, 13-415.2
 PLEASE SEE THE SHEET ATTACHED DOES NOT SHOWIF THIS IS
 THE LATEST ADOPTED VERSION NOR DOES IT CONTAIN THE
 INPUT DATA REPORT IN ORDER TO REVIEW FOR COORDINATION
 WITH PLANS AND LIGHTING FIXTURE SCHEDULE. PLEASE SEE
 THE USE AS STATED.
 ** AS THIS WAS NOT SUBMITTED FOR REVIEW PLEASE BE SURE
 THE FIXTURES, TYPE OF FIXTURES AND WATTAGE ON FIXTURES
 ETC CORRELATE WITH PLANS AND FIXTURE SCHEDULE.
  
 4) NOTE: PLEASE KNOW LOW VOLTAGE SCOPE OF WORK SHOWN
 FOR ANY PHONE OR CATV WILL BE REQUIRED UNDER A SEPARATE
 PERMIT. THESE PLANS MAY BE REFERENCED FOR PERMIT;
 HOWEVER FEES AND PERMIT APPLICATION WILL BE REQUIRED.
 PLEASE KNOW ANY LOW VOLTAGE SECURITY WORK WILL ALSO BE
 UNDER A SEPARATE PERMIT.
  
 5) NOTE: PLEASE SEE THE FEEDERS BEING SHOWN TO THE
 TRANSFORMER INDICATE A NEUTRAL CONDUCTOR? PLEASE
 CLARIFY HOW THIS IS POSSIBLE WHEN THIS IS A SEPARATELY
 DERIVED SYSTEM.
 250.6,250.24,250.20,250.30 ETC.
  
 6) NOTE: PLEASE PROVIDE A STRUCTURAL SUPPORTING DETAIL
 FOR THE 75KVA WALL MOUNTED TRANSFORMER.
 PLEASE ALSO SEE 450.13 AND PROVIDE A NOTE THAT
 EQUIPMENT MAY NOT BE INSTALLED ABOVE CEILING LINE. FBC
 106.1.2.
  
 7) NOTE: PLEASE SEE 210.8B2 FOR REQUIRED GFI PROTECTION
 FOR 15/20A 120V CIRCUITS IN KITCHEN AREA(S).
  
 8) NOTE: PLEASE SEE THE APPLIED ADDRESS DOES NOT MATCH
 WITH PLANS. PLEASE SEE ANY COMMENTS FROM OTHER TRADES.
 PLANS WILL BE FORWARDED TO THE ADDRESSING REVIEW FOR
 COMMENTS.
 PLEASE BE SURE ALL TITLE BLOCKS CONTAIN THE CORRECTED
 ADDRESS ALONG WITH PERMIT APPLICATION.
 FAC 61G1-16.004
  
 ** PLEASE SEE ANY POSSIBLE COMMENTS FROM OTHER TRADES
 WHICH MAY AFFECT ELECTRICAL PLANS.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]