| Date |
Text |
| 2007-06-19 12:44:01 | *** UNSAT *** |
| | |
| | 1) NOTE: PLEASE SUBMIT TWO COMPLETE SETS WITH ALL |
| | SHEETS IN ORDER AS STATED ON COVER SHEET. PLEASE SEE |
| | ELECTRICAL AND PLUMBING PLANS ARE MIXED. |
| | PLEASE ALSO DO NOT ATTACH PRODUCT APPROVALS/ ENERGY |
| | CALCULATIONS AND SUPPORTING DOCUMENTS DOWN THE LEFT |
| | SIDE OF PLANS. THESE SHOULD BE ATTACHED INTO TWO SETS |
| | BOUND TOGETHER IN SOME FASHION.THESE MAY BE PLACED IN |
| | SPIRAL BOOK OR OTHER FOLDER OF SOME TYPE LABELED/TABBED |
| | FOR EASE OF REVIEW IN EXPEDITING THE PLAN REVIEW |
| | PROCESS. |
| | ** PLEASE SEE NOTE BELOW LABELED AS IMPORTANT. |
| | |
| | 2) NOTE: PLEASE BE SURE PLANS THE CURRENT CODES AS |
| | FOLLOWS. |
| | 2004 FBC W/2006 REVISIONS. |
| | 2005 NFPA-70 |
| | 2003 NFPA-101 |
| | ** PLEASE SEE POSSIBLE COMMENTS FROM OTHER TRADES WHICH |
| | MAY REQUIRE OTHER CODES. |
| | THESE SECTIONS SHOULD ALSO BE STATED ON ELECTRICAL |
| | PLANS AS WELL AS PROJECT COVER SHEET. |
| | |
| | 3) NOTE: PLEASE SUBMIT ENERGY CALCULATIONS AS ADOPTED |
| | BY FBC 2004 W/2006 REVISIONS.13-415.1.C, 13-415.2 |
| | PLEASE SEE THE SHEET ATTACHED DOES NOT SHOWIF THIS IS |
| | THE LATEST ADOPTED VERSION NOR DOES IT CONTAIN THE |
| | INPUT DATA REPORT IN ORDER TO REVIEW FOR COORDINATION |
| | WITH PLANS AND LIGHTING FIXTURE SCHEDULE. PLEASE SEE |
| | THE USE AS STATED. |
| | ** AS THIS WAS NOT SUBMITTED FOR REVIEW PLEASE BE SURE |
| | THE FIXTURES, TYPE OF FIXTURES AND WATTAGE ON FIXTURES |
| | ETC CORRELATE WITH PLANS AND FIXTURE SCHEDULE. |
| | |
| | 4) NOTE: PLEASE KNOW LOW VOLTAGE SCOPE OF WORK SHOWN |
| | FOR ANY PHONE OR CATV WILL BE REQUIRED UNDER A SEPARATE |
| | PERMIT. THESE PLANS MAY BE REFERENCED FOR PERMIT; |
| | HOWEVER FEES AND PERMIT APPLICATION WILL BE REQUIRED. |
| | PLEASE KNOW ANY LOW VOLTAGE SECURITY WORK WILL ALSO BE |
| | UNDER A SEPARATE PERMIT. |
| | |
| | 5) NOTE: PLEASE SEE THE FEEDERS BEING SHOWN TO THE |
| | TRANSFORMER INDICATE A NEUTRAL CONDUCTOR? PLEASE |
| | CLARIFY HOW THIS IS POSSIBLE WHEN THIS IS A SEPARATELY |
| | DERIVED SYSTEM. |
| | 250.6,250.24,250.20,250.30 ETC. |
| | |
| | 6) NOTE: PLEASE PROVIDE A STRUCTURAL SUPPORTING DETAIL |
| | FOR THE 75KVA WALL MOUNTED TRANSFORMER. |
| | PLEASE ALSO SEE 450.13 AND PROVIDE A NOTE THAT |
| | EQUIPMENT MAY NOT BE INSTALLED ABOVE CEILING LINE. FBC |
| | 106.1.2. |
| | |
| | 7) NOTE: PLEASE SEE 210.8B2 FOR REQUIRED GFI PROTECTION |
| | FOR 15/20A 120V CIRCUITS IN KITCHEN AREA(S). |
| | |
| | 8) NOTE: PLEASE SEE THE APPLIED ADDRESS DOES NOT MATCH |
| | WITH PLANS. PLEASE SEE ANY COMMENTS FROM OTHER TRADES. |
| | PLANS WILL BE FORWARDED TO THE ADDRESSING REVIEW FOR |
| | COMMENTS. |
| | PLEASE BE SURE ALL TITLE BLOCKS CONTAIN THE CORRECTED |
| | ADDRESS ALONG WITH PERMIT APPLICATION. |
| | FAC 61G1-16.004 |
| | |
| | ** PLEASE SEE ANY POSSIBLE COMMENTS FROM OTHER TRADES |
| | WHICH MAY AFFECT ELECTRICAL PLANS. |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |