| 2007-06-15 07:37:46 | BUILDING PLAN REVIEW |
| | PERMIT: 07050808 |
| | ADD: 650 S ROSEMARY AVE |
| | CONT: PEMBERTON BUILDING |
| | TEL: (561)744-3399 |
| | |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | W/ 2006 FBC REVISIONS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | REVIEW |
| | ACTION: DENIED |
| | |
| | 1)--- VERY IMPORTANT STATEMENT --- |
| | PLEASE DO NOT IGNORE! |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL |
| | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH |
| | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE |
| | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE |
| | FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR |
| | YOUR ANTICIPATED COOPERATION. |
| | |
| | 2) THE WRONG PROPERTY CONTROL NUMBER WAS USED ON THIS |
| | PERMIT APPLICATION, THIS MAY AFFECT THE ADDRESS. PLEASE |
| | CORRECT THE PROPERTY CONTROL NUMBER. |
| | |
| | 3)FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED |
| | WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE |
| | WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS NOT |
| | ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING |
| | THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6) |
| | THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE |
| | CONSTRUCTION SITE BEFORE THE FIRST INSPECTION. |
| | |
| | 4)THE PRODUCT APPROVALS SUBMITTED REQUIRE FLORIDA |
| | COVERSHEETS. PRODUCT APPROVALS SUBMITTED WITH PERMIT |
| | APPLICATION AFTER OCTOBER 1, 2003 ARE REQUIRED TO |
| | COMPLY WITH THE FLORIDA |
| | PRODUCT APPROVAL SYSTEM. FOR INFORMATION PLEASE SEE THE |
| | STATE WEBSITE AT WWW.FLORIDABUILDING.ORG. PRODUCTS WITH |
| | STATEWIDE APPROVAL ARE REQUIRED TO BE SUBMITTED WITH A |
| | COVER SHEET THAT LISTS |
| | THE PRODUCT IDENTITY NUMBER FROM THE STATE. IF THE |
| | PRODUCT DOES NOT HAVE STATEWIDE APPROVAL, SUBMIT AN |
| | APPLICATION FOR LOCAL PRODUCT APPROVAL OR SITE SPECIFIC |
| | FORM PER RULE 9B-72. SEE |
| | ATTACHMENT. WWW.FLORIDABUILDING.ORG |
| | |
| | 5) PRODUCT APPROVAL FIREDOOR DIVISION OF ARK II |
| | MANUFACTURING IS MISSING THE TECHNICAL SHEETS 1-4. |
| | PLEASE PROVIDE. |
| | |
| | 6) SHEET G1.0 SITE INFO: |
| | 6A) PLEASE SEE THAT PLANS SUBMITTED AFTER DEC. 8/ 2006 |
| | WILL BE REVIEWED TO THE 2006 FBC, AND THE 2006 FBC |
| | EXISTING BUILDING CODE. |
| | PLEASE INDICATE TO WHAT LEVEL YOU WILL BE DOING |
| | ALTERATIONS UNDER THE SCOPE OFTHIS PERMIT? |
| | |
| | 6B) ENERGY CODE WILL BE REVIEWED UNDER THE 2006 FBC, |
| | CHAPTER 13- 400 COMMERCIAL |
| | |
| | 6C) ACCESSIBILITY WILL BE REVIEWED UNDER THE 2006 FBC, |
| | BUILDING CHAPTER 11 |
| | |
| | 6D) TYPE OF OCCUPANCY SEE:302.1 GENERAL.STRUCTURES |
| | OR PORTIONS OF STRUCTURES SHALL BE CLASSIFIED WITH |
| | RESPECT TO OCCUPANCY IN ONE OR MORE OF THE GROUPS |
| | LISTED BELOW. STRUCTURES WITH MULTIPLE USES SHALL BE |
| | CLASSIFIED ACCORDING TO SECTION 302.3 |
| | |
| | 6E) TYPE OF CONSTRUCTION: 503.1 GENERAL.THE HEIGHT |
| | AND AREA FOR BUILDINGS OF DIFFERENT CONSTRUCTION TYPES |
| | SHALL BE GOVERNED BY THE INTENDED USE OF THE BUILDING |
| | AND SHALL NOT EXCEED THE LIMITS IN TABLE 503 EXCEPT AS |
| | MODIFIED HEREAFTER PROVIDE THE MINIMUM BUILDING TYPE |
| | FOR THIS STRUCTURE. |
| | |
| | 7) SHEET S1 DOESN'T INDICATE TO WHAT WIND DESIGN THE |
| | EXTERIOR COMPONENTS WERE DESINDE TOO? 2004 FL. BLD |
| | CODE 1603.1.4 THE |
| | FOLLOWING INFORMATION RELATED TO WIND |
| | SHALL BE SHOWN ON THE CONSTRUCTION |
| | DRAWINGS, |
| | 1)- BASIC WIND SPEED, MPH |
| | 2)- WIND IMPORTANCE FACTOR, & BUILDING |
| | CATEGORY |
| | 3)- WIND EXPOSURE |
| | 4)- INTERNAL PRESSURE COEFFICIENT, |
| | 5)- COMPONENTS & CLADDING, THE DESIGN |
| | WIND PRESSURES IN TERMS OF PSF. |
| | |
| | 8) A1.0 THE EXTERIOR OF THE BUILDING INDICATES THATNO |
| | WORK IS TO BE COMPLETED ON THE EXISTING WINDOWS |
| | ALTHOUGH THERE ARE PRODUCT APPROVAL FOR FIXED AND |
| | HORIZONTAL SLIDERS? |
| | PLEASE CORRECT THIS SHEET , SHEET A2.0 INDICATES |
| | WINDOWS TO BE REPLACED. |
| | |
| | BUILDING PLAN REVIEW |
| | JIM WITMER C. B. O. |
| | |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |
| | E-MAIL: [email protected] |
| | |