Plan Review Notes
Plan Review Notes For Permit 07050795
Permit Number 07050795
Review Stop B
Sequence Number 3
Notes
Date Text
2007-12-03 08:07:58****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 FROM PREVIOUS LISTS:
  
 1.)THE TITLE SHEET IS NOT SEALED AND DATED. DOCUMENTS
 PREPARED BY AN ENGINEER AND SUBMITTED FOR PUBLIC RECORD
 ARE TO BE SIGNED, SEALED, DATED ORIGINALS FS471.025.
 WIND DESIGN CRITERIA REQURED TO SHOW CODE COMPLIANCE IS
 ON THE TITLE SHEET.
  
 2.)THE PRINTED NAME AND LICENSE NUMBER OF THE
 INDIVIDUAL SEALING THE DOCUMENT IS TO BE ON EACH SHEET,
 FAC61G15-23.002 (TITLE SHEET).
  
 2ND & 3RD REVIEWS - TITLE SHEET MUST BE SIGNED, SEALED
 DATED WITH THE PRINTED NAME AND LICENSE NUMBER.THE
 SHEET IS SIGNED BUT NOT SEALED AND THE PRINTED NAME AND
 LICENSE NUMBER OF THE INDIVIDUAL WHO HAS SIGNED T1 IS
 NOT INCLUDED.
  
 NEW COMMENT:
  
 3.)DECLARE EXPOSURE CLASSIFICATION,
 FBC1609.6.2.1(2)(MUST BE "C").NOTE THAT THE
 DEFINITION FOR EXPOSURE C HAS CHANGED EFFECTIVE
 DECEMBER 8, 2006 FBC1609.4, FBC R301.2.1.4.