| 2007-11-02 14:36:32 | RESIDENTIAL RENOVATION BUILDING REVISION SECOND |
| | CHECKLIST. |
| | REVIEW DONE UNDER EXISTING BUILDING 2004, FLORIDA |
| | RESIDENTIAL CODE 2004 AND FBC 2004. |
| | |
| | 1- VALUE WAS NOT UPDATED TO INCLUDE ADDITIONAL WORK. |
| | SEC. 108.3 CITY AMENDMENTS TO FBC 2004. (REPEAT |
| | COMMENT). |
| | |
| | 2- PROVIDE PRODUCT APPROVAL AS REQUIRED BY DCA RULE |
| | 9B-72 (REPEAT COMMENT. NONE SUBMITTED) FOR: |
| | A) NEW ENTRY DOOR. |
| | |
| | B) FRENCH DOORS AS SHOWN ON PLANS. |
| | |
| | C) STORM SHUTTERS IF DOORS AND WINDOWS DON'T HAVE |
| | IMPACT GLAZING. IN ADDITION PROVIDE COMPLETE |
| | INSTALLATION SCHEDULE. |
| | |
| | D) PICTURE WINDOW AT NEW ENTRY AREA. |
| | |
| | ***NOTE: CONTRACTOR WROTE ON SUBMITTAL FORM THAT SINGLE |
| | HUNG WINDOW PRODUCT APPROVAL IS ON FILE. THIS IS |
| | CORRECT, BUTPRODUCT APPROVALS FOR OTHER DOORS AND |
| | WINDOWS WERE NOT SUBMITTED. |
| | |
| | 3- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| | (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS |
| | REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC 2004. |
| | (REPEAT COMMENT). |
| | |
| | 4- PROVIDEFRAMING DETAILS FOR NEW DOUBLE FRENCH |
| | DOORS. SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004. |
| | (REPEAT COMMENT).STRUCTURALSHEET S-1 DOESN'T |
| | PROVIDE THIS INFORMATION AS TOLD BY CONTRACTOR OVER THE |
| | PHONE ON 10-18-07. |
| | |
| | 5- PROVIDE COMPLETE FRAMING DETAIL FOR WIDENING OF |
| | OPENING IN BEARING WALL BY KITCHEN AREA LEADING TO THE |
| | FAMILY ROOM.SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004. |
| | (REPEAT COMMENT). CONTRACTOR CALLED ME OVER THE PHONE |
| | AND TOLD ME THAT THIS INFORMATION IS ON STRUCTURAL PLAN |
| | IN FILE.CHECKED FILE AND STRUCTURAL DRAWING S-1 |
| | DOESN'T PROVIDE THIS INFORMATION EITHER. |
| | |
| | 6- ONLY TWO SETS OF PLANS AND PRODUCT APPROVALS ARE |
| | REQUIRED NOT THREE. |
| | |
| | ***NOTE: PLANS WERE ROUTED TO THE OTHER TRADES BECAUSE |
| | NEW SHEETS WITH REVISIONS WERE SUBMITTED. |
| | |