2007-11-14 14:29:50PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST
 PALM BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 MECHANICAL REVISION
 *** DENIED ***
 1) THE POCKET DOOR FROM THE LIVING ROOM TO THE HALL
 (SEE YELLOW HIGH LIGHT ON PLAN) WILL STOP THE AIR FROM
 RETURNING TO THE AIR HANDLER. SEE 2004 FBC/R M16.02.4,
 PLEASE CORRECT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]
  