Plan Review Notes
Plan Review Notes For Permit 07050787
Permit Number 07050787
Review Stop P
Sequence Number 3
Notes
Date Text
2007-10-15 09:26:36REVISION DENIED
 REFERENCE:
 ** FBC-2004 WITH 05 & 06 REVISIONS, PLUMBING.
 ** FBC-2004 CHAPTER 1, THE CITY OF
 WEST PALM BEACH AMENDMENTS.
 ** FLORIDA ADMINISTRATIVE CODE (FAC).
 ** FLORIDA STATUTES (FS).
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 THE PLUMBING REVISION PLAN REVIEW TO MEET CODE
 COMPLIANCE:
  
 1. SHEET A102 AS BUILT SANITARY RISER DIAGRAM DOES NOT
 REFLECT THE FLOOR PLAN. PER FBC-2004 CHAPTER 1 SECTION
 106.1.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL
 BE OF SUFFICIENT CLARITY TO INDICATE THE
 LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL
 CONFORM TO THE PROVISIONS OF THIS CODE
 AND RELAVENT LAWS, ORDINANCES, RULES AND REGULATIONS,
 AS DETERMINED BY THE
 BUILDING OFFICIAL.
 NOTE: PLEASE ADDRESS THE FOLLOWING.
 A} PLEASE INDICATE ALL REQUIRED DRAINAGE FOR THE
 RELOCATED DOUBLE BOWL KITCHEN SINK W/ DISHWASHER.
 B} IS IT THE INTENT TO HAVE THE RELOCATED WASHING
 MACHINE BOX OUT OF THE WALL. PLEASE CLARIFY THE
 LOCATION ON THE RESUBMITTAL.
  
 2. SHEET A102 AS BUILT SANITARY RISER DIAGRAM A
 CLEANOUT FOR THE WASHING MACHINE IS REQUIRED PER THE
 FOLLOWING FBC-2004 W/05 & 06 REV. SECTIONS.
 (A) 708.7 MINIMUM SIZE. CLEANOUTS SHALL
 BE THE SAME NOMINAL SIZE AS THE PIPE
 THEY SERVE UP TO 4 INCHES (102MM)
 NOTE: CLEANOUT FOR THE WASHING MACHINE TO BE 3 INCH.
 (B) 708.9 ACCESS. ACCESS SHALL BE
 PROVIDED TO ALL CLEANOUTS.
 NOTE: CLEANOUT FOR THE WASHING MACHINE TO BE LOCATED AT
 4' A.F.F.
  
 3. SHEET A102 AS BUILT SANITARY RISER DIAGRAM PER
 FB-2004 W/05 & 06 REV. SECTION 1002.1 EACH PLUMBING
 FIXTURE SHALL BE SEPERATELY TRAPPED BY A WATER SEAL
 TRAP. PLEASE INDICATE THE REQUIRED TRAP FOR THE
 FOLLOWING.
 A} LAVATORY IN TUB BATH.
 B} DOUBLE BOWL KITCHEN SINK.
 C} LAVATORY IN SHOWER BATH.
  
 ********IMPORTANT INFORMATION********
 IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING,
 PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED, PLEASE INCLUDE A
 TRANSMITTAL LETTER INDICATING HOW EACH
 ITEM WAS ADDRESSED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY.
 NOTE: THERE IS ONLY ONE CORRECTED DRAWING
 IN RED INK ON THE INDICATED PLAN SHEETS BY THIS PLANS
 EXAMINER FOR REFERENCE FOR THE
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved