| | PERMIT # 07050787 |
| | ELECTRICAL PLAN REVIEW |
| | 245 ALPINE ROAD |
| | |
| | WEST PALM BEACH, FL. |
| | |
| | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: |
| | |
| | THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004 |
| | RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002, |
| | NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1, AND |
| | FOUND NONCOMPLIANT WITH THE FOLLOWING: |
| | |
| | THE PERMITTED SET OF PLANS LOCATED THE ELECTRICAL |
| | PANEL ON SHEET A101 WHERE A WALL BETWEEN THE KITCHEN |
| | AND BATHROOM IS NOW PROPOSED. THE ELECTRICAL NOTES ON |
| | SHEET A103 INDICATE ?NO CHANGE IN THE SERVICE |
| | REQUIRED?. THE SERVICE IS SHOWN ON THE REVISION, WHERE |
| | A WINDOW IS TO BE REMOVED. THE SERVICE OBVIOUSLY IS TO |
| | BE RELOCATED AT THE VERY LEAST, IF NOT UPGRADED. |
| | THEREFORE THE FOLLOWING ITEMS ARE REQUIRED. |
| | |
| | 1} PROVIDE A PANEL SCHEDULE PER 408.4. INCLUDE OCP AND |
| | CONDUCTOR SIZES. PLEASE SEE NEW VERBIAGE FOR 2005 NEC: |
| | "THE IDENTIFICATION SHALL INCLUDE SUFFICIENT DETAIL TO |
| | ALLOW EACH CIRCUIT TO BE DISTINGUISHED FROM ALL |
| | OTHERS." |
| | |
| | 2} PER 110.9 AND 110.10: OBTAIN THE AVAILABLE FAULT |
| | CURRENT AT THE UTILITY AND CALCULATE THE SAME AT THE |
| | EQUIPMENT. INDICATE THE AIC RATING FOR THE EQUIPMENT IS |
| | EQUAL TO OR GREATER THAN THE AVAILABLE FAULT. |
| | |
| | 3} RECEPTACLE SPACING MUST COMPLY WITH 210.52(A)(1) AND |
| | 210.52(A)(2). 2005 NEC. SEE REVIEWED PLAN FOR |
| | DEFICIENCIES |
| | |
| | 4} LABEL THE ROOMS AS TO THEIR USE PER 106.1.2 FBC AS |
| | AMENDED. |
| | |
| | 5} THE VALUE ON THE APPLICATION MUST INCLUDE THE TOTAL |
| | COST OF LABOR AND MATERIAL. ADJUST THE VALUE AT THE |
| | PERMIT CLERK?S DESK, AND PAY THE DIFFERENCE IN FEES |
| | PRIOR TO RESUBMITTING. |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |
| | BILL TROBAUGH |
| | ELECTRICAL PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | 561/805-6718 |
| | [email protected] |