| 2007-10-15 10:32:17 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & | | | REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST | | | PALM BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA | | | ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES | | | (F.S.). | | | | | | *** DENIED *** | | | 1) PLEASE SUBMITCOOLING LOAD CALCULATIONS, PER 2004 | | | FBC 13-607.1.ABC.1. | | | | | | 2)SEE YELLOW HIGH LIGHT ON MECHANICAL PLAN PAGE A102 | | | RETURN AIR DUCT AND GRILL NEED TO BE SIZED. SEE 2004 | | | FBC/R M1602.4. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729 | | | E-MAIL; [email protected] |
|