Plan Review Notes For Permit 07050787
Permit Number 07050787
Review Stop M
Sequence Number 2
Notes
Date Text
2007-10-15 10:32:17PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST
 PALM BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) PLEASE SUBMITCOOLING LOAD CALCULATIONS, PER 2004
 FBC 13-607.1.ABC.1.
  
 2)SEE YELLOW HIGH LIGHT ON MECHANICAL PLAN PAGE A102
 RETURN AIR DUCT AND GRILL NEED TO BE SIZED. SEE 2004
 FBC/R M1602.4.
  
 MECHANICAL PLAN REVIEW BY;