Plan Review Notes
Plan Review Notes For Permit 07050787
Permit Number 07050787
Review Stop P
Sequence Number 1
Notes
Date Text
2007-06-11 14:14:13DENIED
 REFERENCE:
 ** FBC-2004 PLUMBING.
 ** FBC-2004 CHAPTER 1, THE CITY OF
 WEST PALM BEACH AMENDMENTS.
 ** FLORIDA ADMINISTRATIVE CODE.
 ** FLORIDA STATUTES.
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE:
  
 1. SHEET A102 SANITARY ISOMETRIC RISER DIAGRAM:THE NEW
 LAV BY NEW TUB IS INDICATING A "S" TRAP. PER FBC-2004
 PLUMBING, SECTION 1002.3 (5),A "S" TRAP IS
 PROHIBITED. PLEASE PROVIDE A VENT PER FBC-2004
 PLUMBING, SECTION 901.2.1.
  
 2. SHEET A102 SANITARY ISOMETRIC RISER DIAGRAM: PLEASE
 INDICATE THAT THE DISHWASHER IS DRAINING CODE COMPLIANT
 PER ONE OF THE FOLLOWING METHODS. THE WAY IT IS
 INDICATED NOW IS NOT CODE COMPLIANT. IF IT IS THE
 INTENT TO DRAIN THE DISHWASHER THROUGH A STANDPIPE
 PLEASE INDICATE THE STANDPIPE AND THAT THE STANDPIPE
 SHALL HAVE ACCESS PER FBC-2004 PLUMBING, SECTION 802.4.
  
 (A) 802.1.6 DOMESTIC DISHWASHING MACHINES SHALL
 DISCHARGE INDIRECTLY THROUGH AN AIR GAP OR AIR BREAK
 INTO A STANDPIPE OR WASTE RECEPTOR IN ACCORDANCE WITH
 SECTION 802.2 OR DISCHARGE INTO A WYE-BRANCH FITTING ON
 THE TAILPIECE OF THE KITCHEN SINK OR THE DISHWASHER
 CONNECTION OF A FOOD WASTE GRINDER.
  
 3. SHEET A102 SANITARY ISOMETRIC RISER DIAGRAM: PLEASE
 INDICATE BOTH BOWLS OF EXISTING KITCHEN SINK.
  
 4. SHEET A102 SANITARY ISOMETRIC RISER DIAGRAM: THE
 EXISTING WASHING MACHINE IS INDICATING A "S" TRAP. PER
 FBC-2004 PLUMBING, SECTION 1002.3(5), A"S" TRAP IS
 PROHIBITED. PLEASE PROVIDE NEW CODE COMPLIANT PLUMBING
 FOR THE WASHING MACHINE PER THE FOLLOWING. (A) 406.3
 WASTE CONNECTIONS.THE TRAP AND
 FIXTURE DRAIN FOR AN AUTOMATIC CLOTHES
 WASHER SHALL BE A MINIMUM OF 2 INCHES
 (51MM) IN DIAMETER. THE AUTOMATIC
 CLOTHES WASHER FIXTURE DRAIN SHALL
 CONNECT TO A BRANCH DRAIN OR DRAINAGE
 STACK A MINIMUM OF 3 INCHES (76MM) IN
 DIAMETER. PLEASE CORRECT THE WASHING MACHINE DRAINAGE
 STACK ON THE RESUBMITTAL.
  
 (B) 802.4 STANDPIPES.STANDPIPES SHALL BE INDIVIDUALLY
 TRAPPED. STANDPIPES SHALL
 EXTEND A MINIMUM OF 18 INCHES (457MM)
 AND A MAXIMUM OF 42 INCHES (1066MM)
 ABOVE THE TRAP WEIR. ACCESS SHALL BE
 PROVIDED TO ALL STANDPIPES AND DRAINS
 FOR RODDING. PLEASE INDICATE THE STANDPIPE ON THE
 RESUBMITTAL.
  
 (C) 708.7 MINIMUM SIZE. CLEANOUTS SHALL
 BE THE SAME NOMINAL SIZE AS THE PIPE
 THEY SERVE UP TO 4 INCHES (102MM) CLEANOUT FOR THE
 WASHING MACHINE SHALL BE THREE INCH (3").
  
 (D) 708.9 ACCESS. ACCESS SHALL BE
 PROVIDED TO ALL CLEANOUTS. THE CLEANOUT FOR THE WASHING
 MACHINE SHALL BE LOCATED AT FOUR FEET ABOVE FINNISH
 FLOOR (4' A.F.F.).
  
 5. SHEET A102 SANITARY ISOMETRIC RISER DIAGRAM: THE
 NEW SHOWER NEEDS A VENT PER FBC-2004 PLUMBING, SECTION
 901.2.1. PLEASE CORRECT THIS ON THE RESUBMITTAL. NOTE:
 THE CLEANOUT BEING INDICATED FOR THE SHOWER NEEDS TO BE
 DELETED ON THE RESUBMITTAL.
  
 6. SHEET A102 SANITARY ISOMETRIC RISER DIAGRAM PLEASE
 INDICATE THE FOLLOWING PER FBC-2004 PLUMBING.
 (A) 708.3.5 BUILDING DRAIN AND BUILDING
 SEWER JUNCTION. THERE SHALL BE A
 TWO-WAY CLEANOUT NEAR THE JUNCTION OF THE
 BUILDING DRAIN AND THE BUILDING SEWER. PLEASE INDICATE
 THIS ON THE RESUBMITTAL.
  
 ********IMPORTANT INFORMATION********
 IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING,
 PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED, PLEASE INCLUDE A
 TRANSMITTAL LETTER INDICATING HOW EACH
 ITEM WAS ADDRESSED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY.
 NOTE: ONLY ONE CORRECTED DRAWING
 IN RED INK FOR REFERENCE FOR
 RESUBMITTAL.
  
 END OF COMMENTS:
  