| Plan Review Notes For Permit 07050758 |
| Permit Number |
07050758 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2007-06-11 15:01:48 | *****DENIED***** | | | | | | | | | | | | 1.THE NUMERICAL ADDRESS, INCLUDING THE SUITE NUMBER, | | | SHALL BE IN THE TITLE BLOCK OF EACH SUBMITTED PLAN | | | SHEET. | | | | | | 2.THE REMOVAL, REPLACEMENT, AND/OR STOCKING OF NEW | | | BUILDING MATERIALS & SUPPLIES SHALL IN NO WAY BLOCK, | | | INTERFERE, OR HINDER ACCESS TO OR EGRESS FROM THE SAID | | | BUILDING FLOOR OR OTHER FLOORS IN THE BUILDING | | | (INCLUDING EXITS, EXIT AISLE CORRIDORS). | | | | | | 3.SPECIFY THE MATERIAL FINISH MATERIAL CLASSIFICATION | | | FOR THE RISE ENTRANCE CEILING AS CLASS A, CLASS B, OR | | | CLASS C. | | | | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE ARESPONSE | | | LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED | | | | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|