| Plan Review Notes For Permit 07050746 |
| Permit Number |
07050746 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2007-05-22 14:23:46 | BUILDING REVIEW CHECKLIST: | | | | | | 1-AS PER PHONE CONVERSATION WITH CONTRACTOR,ROOF | | | WAS DONE AFTER THE STORM.ACCORDING TO CITY RECORDS, | | | THERE WAS NOT PERMIT APPLIED FOR SUCH RE-ROOF. PICTURE | | | SUBMITTED CLEARLY SHOWS THAT ROOF WAS NOT DONE PROPERLY | | | AND THAT'S WHYWATER IS APROBLEM.NEED TO DO A | | | COMPLETE RE-ROOF JOB AND PROPER INSPECTIONS PERFORMED. | | | SEC. 1510.3 FBC 2004. | | | | | | 2- NOA 06-1031.06 SUBMITTED IS FOR RECOVERY | | | APPLICATIONS. ACCORDING TO EXISTING ROOF PICTURE | | | SUBMITTED AND SEC. 1510.3 FBC 2004 NEED TO DO A | | | RE-ROOF, NOT ROOF RECOVERY.ROOF IS FULL OF STANDING | | | WATER.PROVIDEPRODUCT APPROVAL AS REQUIRED BY DCA | | | RULE 9B-72 FOR A NEW ROOF ASSEMBLY. SEE ATTACHED COPY | | | OF CITY POLICY FOR ROOFING PERMITS FOR REQUIRED | | | INFORMATION AND PROVIDE COMPLETE INFORMATION. ***NOTE: | | | MAKE SURE PROPER ASSEMBLY IS SELECTED AND SPECIFIC BASE | | | SHEET FASTENING OPTION IS SPECIFIED. ALSO,CHECK IF | | | SELECTED SYSTEM IS LIMITED BY GENERAL LIMITATION #7 OR | | | #9. COMPLY WITH GENERAL LIMITATION AS REQUIRED. | | | | | | 3- VALUATION DECLARED IN THEPERMIT APPLICATION IS TOO | | | LOW. UPDATE AS REQUIRED BY SEC. 108.3 OF CITY | | | AMENDMENTS TO FBC 2004. | | | | | | 4- NEED RECORDED NOTICE OF COMMENCEMENT AS REQUIRED BY | | | SEC. 713.13 FLORIDA STATUTE. | | | | | | JULIO GOMEZ | | | BUILDING PLANS EXAMINER | | | (561)805-6712 |
|