| 2007-06-21 07:42:20 | *** UNSAT2ND REVIEW *** |
| | |
| | ** PLEASE SEE SOME COMMENTS FROM PREVIOUS REVIEW NEED |
| | TO BE ADDRESSED ALONG WITH NEW COMMENTS BASED ON |
| | INFORMATION AND/OR CHANGES NOW ON PLANS. |
| | |
| | 1) NOTE:PLEASE SEE NOT ALL CODES AS LISTED ARE SHOWN |
| | ON PLANS. PLEASE SEE THE YEAR OF THE CODE DOES NEED TO |
| | BE STATED. ONLY THE FBC WAS ADDED WITH THE CORRECT YEAR |
| | AND AMENDMENTS. |
| | ** PREVIOUS NOTE** |
| | PLEASE SEE THE SUBMITTED DOCUMENTS REQUIRE THE CODES TO |
| | BE STATED ON PLANS. |
| | PLEASE SEE THE FOLLOWING ARE REQUIRED FOR ELECTRICAL |
| | AND OTHERS WILL BE REQUIRED FOR OTHER TRADES. PLEASE |
| | KNOW AS OF DECEMBER 8TH, 2006 THE STATE ADOPTED THE |
| | 2006 REVISIONS TO THE 2004 FBC AND THE 2005 NFPA-70. |
| | PLEASE LIST THE FOLLOWING |
| | 2004 FBC W/ 2006 REVISIONS. |
| | 2005 NFPA-70 |
| | 2003 NFPA-101 |
| | 2002 NFPA-72 |
| | |
| | 2) NOTE:PLEASE DO NOT REFERENCE LICENSURE UNDER FS |
| | 481.229 AS THIS SECTION OF THE FS IS FOR ARCHITECTS AND |
| | EXEMPTIONS. THE STATUTE IN WHICH THE CONTRACTOR MAY |
| | SIGN FOR THIS SCOPE OF WORK DOES NOT NEED TO BE ON |
| | PLANS. |
| | |
| | 3) NOTE: PLEASE SEE THE PREVIOUS NOTE MENTIONED THAT |
| | EITHER SMOKE ALARMS OR SMOKE DETECTORS WOULD NEED TO BE |
| | BROUGHT UP TO CODE AND WOULD NEED TO BE SHOWN DEPENDING |
| | ON THE SYSTEM BEING INSTALLED. PLEASE SEE THE PLANS AND |
| | NOTES INDICATE THESE AS SD FOR SMOKE DETECTORS, YET THE |
| | NOTES MENTIONS THESE AS 120V WITH BATTERY BACK UP? |
| | PLEASE KNOW SMOKE ALARMS ARE DEVICE WHICH NOT ONLY |
| | DETECT BUT ALSO SOUND AN ALARM. IF INSTALLING SMOKE |
| | ALARMS AS SHOWN, THESE DEVICES ONLY DETECT AND SIGNAL |
| | FOR ALARM. NO SOUNDING, HORN DEVICES WERE LOCATED ON |
| | PLANS. PLEASE BE SURE THE SYSTEM IN WHICH IS BEING |
| | PROPOSED IS COMPLETE. IF THESE ARE 120V W/ BATTERY BACK |
| | UP WHICH DETECT AND SOUND, PLEASE CHANGE TO SA AND |
| | SMOKE ALARM DESIGNATION? PLEASE ALSO SEE 210.12 FOR |
| | REQUIRED ARC FAULT AS CIRCUITING AS NEEDED IS NOT ON |
| | PLANS OR THE BRIEF PANEL SCHEDULE SUBMITTED. NFPA-72 |
| | 11.5.1.1, 11.8.3. |
| | |
| | 4) NOTE: PLEASE SEE THE PANEL SCHEDULE AS SUBMITTED IS |
| | ONLY INDICATING NEW CIRCUITS HOWEVER THESE IS MISSING |
| | CONDUCTOR SIZE FOR OVEN AND NO BREAKER SIZE OR WIRE |
| | SIZE IS BEING SHOWN FOR THE NEW COOK-TOP? |
| | PLEASE SUBMIT THE COMPLETED PANEL SCHEDULE FOR NEW AND |
| | EXISTING CIRCUITS IN THESE AREAS BEING RENOVATED. |
| | 408.4, 240.4, 310.16 |
| | |
| | 5) NOTE:PLEASE SEE THAT NO HAND WRITTEN ITEMS ARE |
| | PERMITTED ON PLANS IN PEN OR PENCIL. PLEASE SEE LIGHTS |
| | OVER KITCHEN COUNTER WHICH WERE ADDED IN PEN. |
| | FBC ADMIN SECT 106.1, 106.3.5.1.2 |
| | |
| | 6) NOTE: PLEASE SEE 210.70A1AS THE SWITCHES FOR BATH |
| | ROOM LIGHTING SHOULD BE IN THE BATHROOM. |
| | (1) HABITABLE ROOMS AT LEAST ONE WALL SWITCH-CONTROLLED |
| | LIGHTING OUTLET SHALL BE INSTALLED IN EVERY HABITABLE |
| | ROOM AND BATHROOM. |
| | |
| | ** PLEASE KNOW THE RESPONSES TO COMMENTS NEED NOT BE ON |
| | PLANS ONLY THE NEEDED DETAIL FOR CONSTRUCTION OR CODE |
| | COMPLIANCE. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |