| Date |
Text |
| 2007-06-03 15:23:40 | ** UNSAT** |
| | |
| | 1) NOTE: PLEASE SEE THE SUBMITTED DOCUMENTS REQUIRE THE |
| | CODES TO BE STATED ON PLANS. |
| | PLEASE SEE THE FOLLOWING ARE REQUIRED FOR ELECTRICAL |
| | AND OTHERS WILL BE REQUIRED FOR OTHER TRADES. PLEASE |
| | KNOW AS OF DECEMBER 8TH, 2006 THE STATE ADOPTED THE |
| | 2006 REVISIONS TO THE 2004 FBC AND THE 2005 NFPA-70. |
| | PLEASE LIST THE FOLLOWING |
| | 2004 FBC W/ 2006 REVISIONS. |
| | 2005 NFPA-70 |
| | 2003 NFPA-101 |
| | 2002 NFPA-72 |
| | |
| | 2) NOTE: PLEASE SEE THE MISSING PRINTED NAME AND |
| | SIGNATURE OF THE DESIGNER OF RECORD IF MEETING THE |
| | EXCEPTIONS UNDER FS 481.229, AND 471.003 |
| | FBC 106.1.2, 106.3.5.1.2 |
| | |
| | 3) NOTE: PLEASE SEE FBC 2004 W/ 2006 REVISIONS R313 |
| | WHICH REQUIRES ALL SMOKE ALARMS OR DETECTORS TO BE |
| | BROUGHT UP TO CODE IF THE EXISTING DOES NOT MEET CODE. |
| | PLEASE INDICATE WHICH TYPE OF DEVICES ARE TO BE |
| | INSTALLED, EXISTINGAND LOCATIONS PER NFPA-72 |
| | 11.5.1.1, 11.8.3. |
| | |
| | 4) NOTE: PLEASE INDICATE THE MINIMUM CIRCUITS IN |
| | KITCHEN IF NEW OR EXISTING. SMALL APPLIANCE(S), 20AMP |
| | #12 PER 210.52B1, 210.11C1, 220.53. |
| | |
| | 5) NOTE: PLEASE INDICATE THE MINIMUM REQUIRED BATH |
| | DEDICATED CIRCUITS PER 210.52D, 210.11C3. |
| | MUST BE 20AMP AND #12. |
| | |
| | 6) NOTE: PLEASE SHOW LOCATION OF THE EXISTING PANEL. |
| | 110.26, 408.7, 240.24. |
| | FBC 106.1.2. |
| | |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |