| 2007-08-26 15:28:02 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBCFLORIDA BUILDING CODE 2004 |
| | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING |
| | CODE |
| | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC* |
| | CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 FAC |
| | FLORIDA ADMINISTRATIVE CODE |
| | FSFLORIDA STATUTE |
| | |
| | 1.)SEE PREVIOUS LISTS.THE ANCHOR SPACING COLUMN WAS |
| | LEFT BLANK.THIS INFORMATION IS REQUIRED. |
| | |
| | 2.)8" AND 9" SHUTTER GLASS SEPARATION IS NOT POSSIBLE |
| | WITH AN 8" BLOCK WALL.PLEASE REVISE. |
| | |
| | 3.)8" AND "FLUSH" EDGE DISTANCE ARE NOT CORRECT. |
| | PLEASE SEE THE PRODUCT APPROVAL AND REVISE THE |
| | INSTALLATIN SCHEDULE. |
| | |
| | 4.)SHUTTER MOUNTING CONNECTION TYPE SHOULD BE C1 |
| | THROUGH C5, SEE SHEET 9 OF THE PRODUCT APPROVAL.NOTE |
| | THAT YOU SHOULD USE THE ANCHOR SCHEDULE ON SHEET 9 AS |
| | YOU HAVE STATED THAT THE SUBSTRATE IS BLOCK. |
| | |
| | 5.)SPANS ON INTALLATION SCHEDULE ARE NOT CORRECT. |
| | THIS SHOULD BE THE BLADE LENGTH, WHICH SHOULD CORRELATE |
| | WITH THE SHUTTER HEIGHT. |
| | |
| | 6)YOU'VE WRITTEN "NA" FOR WALL PRESSURES.WORST CASE |
| | FOR EXPOSURE B, ZONE 5, 10 SF IS -47.2.YOU MAY EITHER |
| | USE THE DESIGN PRESSURES IN THE BUILDING CODE FBC R301, |
| | OR USE THE ROW FOR -55PSF ON THE PRODUCT APPROVAL |
| | (WORST CASE FOR EXPOSURE B). |
| | |
| | 7.)ANCHOR TYPE SHOULD CORRELATE WITH PRODUCT |
| | APPROVAL. |
| | |