2007-08-26 15:28:02****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 FAC
 FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.)SEE PREVIOUS LISTS.THE ANCHOR SPACING COLUMN WAS
 LEFT BLANK.THIS INFORMATION IS REQUIRED.
  
 2.)8" AND 9" SHUTTER GLASS SEPARATION IS NOT POSSIBLE
 WITH AN 8" BLOCK WALL.PLEASE REVISE.
  
 3.)8" AND "FLUSH" EDGE DISTANCE ARE NOT CORRECT.
 PLEASE SEE THE PRODUCT APPROVAL AND REVISE THE
 INSTALLATIN SCHEDULE.
  
 4.)SHUTTER MOUNTING CONNECTION TYPE SHOULD BE C1
 THROUGH C5, SEE SHEET 9 OF THE PRODUCT APPROVAL.NOTE
 THAT YOU SHOULD USE THE ANCHOR SCHEDULE ON SHEET 9 AS
 YOU HAVE STATED THAT THE SUBSTRATE IS BLOCK.
  
 5.)SPANS ON INTALLATION SCHEDULE ARE NOT CORRECT.
 THIS SHOULD BE THE BLADE LENGTH, WHICH SHOULD CORRELATE
 WITH THE SHUTTER HEIGHT.
  
 6)YOU'VE WRITTEN "NA" FOR WALL PRESSURES.WORST CASE
 FOR EXPOSURE B, ZONE 5, 10 SF IS -47.2.YOU MAY EITHER
 USE THE DESIGN PRESSURES IN THE BUILDING CODE FBC R301,
 OR USE THE ROW FOR -55PSF ON THE PRODUCT APPROVAL
 (WORST CASE FOR EXPOSURE B).
  
 7.)ANCHOR TYPE SHOULD CORRELATE WITH PRODUCT
 APPROVAL.
  