| Date |
Text |
| 2008-11-18 11:28:31 | SHOP DRAWING SUBMITTING STILL NEED *SHOP DRAWING | | | REVIEW* STAMP AND SIGNATURE FROM THE DEISGNER OF | | | RECORD. | | | MAIN AND MTS SHALL BE VERIFIED TO BE SERVICE ENTRANCE | | | RATED. 230.76, 230.79 |
|