 ** DENIED REVISIONS **
  
  
  
  
 1) NOTE:THE NEW SUBMITTAL AND EXPLANATION MENTIONS
 LARGER SERVICE ENTRANCE CONDUCTORS THAN SHOWN ON RISER.
 ONE SHOWS 500MCM AND THE OTHER 750MCM
 PLEASE COORDINATE.
 310.16.
 FBC 106.1.1 FOR COORDINATION OF PLANS.
  
 2) NOTE: THE SUBMITTAL OF THE NEW PROPOSED SERVICE
 EQUIPMENT NEEDS TO COORDINATE. AS NOTED IN RESPONSE
 LETTER SOME SHEETS INDICATE *AUTOMATIC TRANSFER SWITCH*
 AND SOME INDICATE *MANUAL TRANSFER SWITCH* IN EITHER
 CASE THERE IS NO PRODUCT LISTING SHOWN WHICH
 COORDINATES TO ANY LISTED TRANSFER SWITCH WHETHER
 MANUAL OR AUTOMATIC. IN FACT THE PRODUCT LISTING IS FOR
 SWITCH GEAR STANDARDS ETC. THERE IS NO INDICATION OF
 THIS EQUIPMENT BEING SERVICE ENTRANCE RATED TRANSFER
 SWITCH. THIS OFFICE IS UNCLEAR HOW AND WHY THIS IS
 STILL AN ISSUE AS THIS WAS NOTED IN MANY OF THE
 ORIGINAL REVIEWS. THE FACT ISTHERE ARE LISTED SERVICE
 RATED TRANSFER SWITCHES ON THE MARKET YET OTHER PRODUCT
 WHICH DO NOT CONTAIN THIS LISTING ARE STILL BEING
 PROPOSED.*IF * THIS PROPOSED EQUIPMENT IS INDEED
 LISTED AS SERVICE ENTRANCE RATED AND A TRANSFER SWITCH,
 PLEASE SUBMIT THE PRODUCT DATA/SPEC SHEETS WHICH
 INDICATE THIS. THESE WILL BE VERIFIED WITH THE
 MANUFACTURE AND THE LISTING AGENCY.
 110.3, 90.7.
 PLEASE ALSO COORDINATE THE OTHER INFORMATION SUCH AS
 ANY BREAKERS WHICH ARE SHOWN ON EQUIPMENT SHEETS AS ONE
 SIZE YET PLANS SHOW A LOWER OVER CURRENT PROTECTION.
 THE RESPONSE LETTER DOES MENTION A *DIALING DOWN* OF
 THE RATING HOWEVER THE PLANS NEED TO SHOW THE RATING OF
 THE BREAKER AND THEN THE SETTING.
  
 **ALL REVISIONS ON PLANS NEED TO HAVE CURRENT
 CLOUDS/REVISION TRIANGLES.
  
 3)NOTE: SHEETS 1.2,2.1, 4.2 AND EM1 ARE OK, HOWEVER
 WILL NEED TO BE BROUGHT BACK ONCE OTHER COMMENTS ARE
 ADDRESSED.
  
  
  
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANOR PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved