| 2008-08-26 10:06:48 | |
| | |
| | |
| | |
| | ** DENIED REVISIONS ** |
| | |
| | |
| | |
| | |
| | 1) NOTE:THE NEW SUBMITTAL AND EXPLANATION MENTIONS |
| | LARGER SERVICE ENTRANCE CONDUCTORS THAN SHOWN ON RISER. |
| | ONE SHOWS 500MCM AND THE OTHER 750MCM |
| | PLEASE COORDINATE. |
| | 310.16. |
| | FBC 106.1.1 FOR COORDINATION OF PLANS. |
| | |
| | 2) NOTE: THE SUBMITTAL OF THE NEW PROPOSED SERVICE |
| | EQUIPMENT NEEDS TO COORDINATE. AS NOTED IN RESPONSE |
| | LETTER SOME SHEETS INDICATE *AUTOMATIC TRANSFER SWITCH* |
| | AND SOME INDICATE *MANUAL TRANSFER SWITCH* IN EITHER |
| | CASE THERE IS NO PRODUCT LISTING SHOWN WHICH |
| | COORDINATES TO ANY LISTED TRANSFER SWITCH WHETHER |
| | MANUAL OR AUTOMATIC. IN FACT THE PRODUCT LISTING IS FOR |
| | SWITCH GEAR STANDARDS ETC. THERE IS NO INDICATION OF |
| | THIS EQUIPMENT BEING SERVICE ENTRANCE RATED TRANSFER |
| | SWITCH. THIS OFFICE IS UNCLEAR HOW AND WHY THIS IS |
| | STILL AN ISSUE AS THIS WAS NOTED IN MANY OF THE |
| | ORIGINAL REVIEWS. THE FACT ISTHERE ARE LISTED SERVICE |
| | RATED TRANSFER SWITCHES ON THE MARKET YET OTHER PRODUCT |
| | WHICH DO NOT CONTAIN THIS LISTING ARE STILL BEING |
| | PROPOSED.*IF * THIS PROPOSED EQUIPMENT IS INDEED |
| | LISTED AS SERVICE ENTRANCE RATED AND A TRANSFER SWITCH, |
| | PLEASE SUBMIT THE PRODUCT DATA/SPEC SHEETS WHICH |
| | INDICATE THIS. THESE WILL BE VERIFIED WITH THE |
| | MANUFACTURE AND THE LISTING AGENCY. |
| | 110.3, 90.7. |
| | PLEASE ALSO COORDINATE THE OTHER INFORMATION SUCH AS |
| | ANY BREAKERS WHICH ARE SHOWN ON EQUIPMENT SHEETS AS ONE |
| | SIZE YET PLANS SHOW A LOWER OVER CURRENT PROTECTION. |
| | THE RESPONSE LETTER DOES MENTION A *DIALING DOWN* OF |
| | THE RATING HOWEVER THE PLANS NEED TO SHOW THE RATING OF |
| | THE BREAKER AND THEN THE SETTING. |
| | |
| | **ALL REVISIONS ON PLANS NEED TO HAVE CURRENT |
| | CLOUDS/REVISION TRIANGLES. |
| | |
| | 3)NOTE: SHEETS 1.2,2.1, 4.2 AND EM1 ARE OK, HOWEVER |
| | WILL NEED TO BE BROUGHT BACK ONCE OTHER COMMENTS ARE |
| | ADDRESSED. |
| | |
| | |
| | |
| | |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANOR PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |
| | |
| | |