| 2008-05-27 16:45:27 | ** DENIED REVISIONS ** |
| | |
| | 1) NOTE: THE ARCHITECTURAL PLANS SUBMITTED DO NOT |
| | CONTAIN AN ORIGINAL SIGNATURE FROM THE ARCHITECT MR. |
| | BOYD WOODRU. IN FACT ALL THREE SETS CONTAIN A RAISED |
| | SEAL OVER "PHOTO-COPIED" SIGNATURES AND DATES.THIS |
| | HAS BEEN PLACED IN COMMENTS BEFORE PERMIT ISSUANCE FOR |
| | THIS SAME ITEM. THIS COMMENT HAS BEEN MADE BY THIS |
| | REVIEWER TO THIS SAME DESIGNER ON MORE THAN ONE REVIEW |
| | YET PLANS ARE STILL BEING SUBMITTED WITHOUT ORIGINAL |
| | SIGNATURE AND DATE. THIS IS IN VIOLATION OF FLORIDA |
| | STATUTES 481.221 AND THIS ARCHITECT HAS BEEN GIVEN |
| | NOTICE ON MORE THAN ONE OCCASION.THIS OFFICE IS BEING |
| | LEFT WITH NO CHOICE BUT TO TURN THESE SAID PLANS AND |
| | OTHER PREVIOUSLY RETAINED PLANS WITH SAME VIOLATION |
| | OVER TO THE FLORIDA BOARD OF ARCHITECTS LEGAL COUNSEL. |
| | I HAVE SPOKEN TO THE LAW FIRM WHO REPRESENTS THE BOARD |
| | OF ARCHITECTS ON MORE THAN ONE OCCASION. THIS IS A |
| | CLEAR VIOLATION OF THE STATUTES. THERE IS NO LOCATION |
| | IN THE CURRENT FLORIDA STATUTES WHICH PERMITS A RAISED |
| | SEAL TO BE PLACED OVER A ?PHOTO-COPIED? SIGNATURE. |
| | PLEASE KNOW ONCE ALL REVIEWS ARE COMPLETE THESE SAID |
| | PLANS WILL BE RETAINED BY THIS OFFICE. |
| | |
| | 2) NOTE:PLEASE SUBMIT THE MANUFACTURES SPECS/CUT |
| | SHEETS ON THE NEW PROPOSED SERVICE MANUAL TRANSFER |
| | SWITCH. PLEASE KNOW THIS EQUIPMENT BASED ON RISER IS |
| | REQUIRED TO BE SERVICE ENTRANCE RATED. NEC 110.3, 90.7, |
| | FBC 106.1.2 FOR ADDITIONAL INFORMATION. |
| | PLEASE ALSO SEE THE RISER AS THIS INDICATES A 500AMP |
| | MAIN BREAKER WHICH SERVES TO MEET 230.76, 230.79. HOW |
| | IS THIS POSSIBLE WHEN THE MAIN IS SHOWN AS 5000AMP? |
| | THIS MAY BE A MISPRINT. |
| | PLEASE PROVIDE MORE DETAILS ON THE ACTUAL SECTIONS. THE |
| | POWER PLANS SHOW SECTIONS 1 AND 2 YET THE RISER SHEET |
| | MSB SHOWS SECTION #3. |
| | PLEASE COORDINATE. |
| | PLEASE SEE THE LINE DIAGRAM ALSO SHOWS THIS MSB/MAIN |
| | OUTSIDE THE EDC. WHERE IS THE MAIN LOCATED? |
| | |
| | ** RESPONSE LETTER MENTIONS SERVICE IS APPROVED BY THE |
| | LOCAL UTILITY, HOWEVER PLEASE KNOW THE SERVICE |
| | EQUIPMENT OF THE BUILDING IS NOT GOVERNED BY THE LOCAL |
| | UTILITY COMPANY.THIS IS THE SAME FOR THE UTILITY |
| | EQUIPMENT WHICH IS EXEMPT AND IS NOT COVERED BY THE |
| | NEC. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW. IF |
| | THERE ARE ANY QUESTIONS OR COMMENTS PLEASE DO NOT |
| | HESITATE IN CONTACTING THIS OFFICE. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |