Plan Review Notes
Plan Review Notes For Permit 07050729
Permit Number 07050729
Review Stop E
Sequence Number 6
Notes
Date Text
2008-05-27 16:45:27** DENIED REVISIONS **
  
 1) NOTE: THE ARCHITECTURAL PLANS SUBMITTED DO NOT
 CONTAIN AN ORIGINAL SIGNATURE FROM THE ARCHITECT MR.
 BOYD WOODRU. IN FACT ALL THREE SETS CONTAIN A RAISED
 SEAL OVER "PHOTO-COPIED" SIGNATURES AND DATES.THIS
 HAS BEEN PLACED IN COMMENTS BEFORE PERMIT ISSUANCE FOR
 THIS SAME ITEM. THIS COMMENT HAS BEEN MADE BY THIS
 REVIEWER TO THIS SAME DESIGNER ON MORE THAN ONE REVIEW
 YET PLANS ARE STILL BEING SUBMITTED WITHOUT ORIGINAL
 SIGNATURE AND DATE. THIS IS IN VIOLATION OF FLORIDA
 STATUTES 481.221 AND THIS ARCHITECT HAS BEEN GIVEN
 NOTICE ON MORE THAN ONE OCCASION.THIS OFFICE IS BEING
 LEFT WITH NO CHOICE BUT TO TURN THESE SAID PLANS AND
 OTHER PREVIOUSLY RETAINED PLANS WITH SAME VIOLATION
 OVER TO THE FLORIDA BOARD OF ARCHITECTS LEGAL COUNSEL.
 I HAVE SPOKEN TO THE LAW FIRM WHO REPRESENTS THE BOARD
 OF ARCHITECTS ON MORE THAN ONE OCCASION. THIS IS A
 CLEAR VIOLATION OF THE STATUTES. THERE IS NO LOCATION
 IN THE CURRENT FLORIDA STATUTES WHICH PERMITS A RAISED
 SEAL TO BE PLACED OVER A ?PHOTO-COPIED? SIGNATURE.
 PLEASE KNOW ONCE ALL REVIEWS ARE COMPLETE THESE SAID
 PLANS WILL BE RETAINED BY THIS OFFICE.
  
 2) NOTE:PLEASE SUBMIT THE MANUFACTURES SPECS/CUT
 SHEETS ON THE NEW PROPOSED SERVICE MANUAL TRANSFER
 SWITCH. PLEASE KNOW THIS EQUIPMENT BASED ON RISER IS
 REQUIRED TO BE SERVICE ENTRANCE RATED. NEC 110.3, 90.7,
 FBC 106.1.2 FOR ADDITIONAL INFORMATION.
 PLEASE ALSO SEE THE RISER AS THIS INDICATES A 500AMP
 MAIN BREAKER WHICH SERVES TO MEET 230.76, 230.79. HOW
 IS THIS POSSIBLE WHEN THE MAIN IS SHOWN AS 5000AMP?
 THIS MAY BE A MISPRINT.
 PLEASE PROVIDE MORE DETAILS ON THE ACTUAL SECTIONS. THE
 POWER PLANS SHOW SECTIONS 1 AND 2 YET THE RISER SHEET
 MSB SHOWS SECTION #3.
 PLEASE COORDINATE.
 PLEASE SEE THE LINE DIAGRAM ALSO SHOWS THIS MSB/MAIN
 OUTSIDE THE EDC. WHERE IS THE MAIN LOCATED?
  
 ** RESPONSE LETTER MENTIONS SERVICE IS APPROVED BY THE
 LOCAL UTILITY, HOWEVER PLEASE KNOW THE SERVICE
 EQUIPMENT OF THE BUILDING IS NOT GOVERNED BY THE LOCAL
 UTILITY COMPANY.THIS IS THE SAME FOR THE UTILITY
 EQUIPMENT WHICH IS EXEMPT AND IS NOT COVERED BY THE
 NEC.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW. IF
 THERE ARE ANY QUESTIONS OR COMMENTS PLEASE DO NOT
 HESITATE IN CONTACTING THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]