| 2007-12-03 14:48:39 | DENIED |
| | REFERENCE: FBC-2004 PLUMBING |
| | FBC-2004 BUILDING |
| | FBC-2004 CHAPTER 1 |
| | FBC-2004 CHAPTER 11 |
| | WEST PALM BEACH MUNICIPAL CODE |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | |
| | ****FROM PREVIOUS REVIEW. COMMENT NUMBERS TO REMAIN THE |
| | SAME. |
| | ******FROM PREVIOUS REVIEW: |
| | |
| | 1. OK |
| | 2. OK |
| | 3. OK |
| | 4. OK |
| | 5. OK |
| | 6. OK |
| | 7. OK |
| | 8. OK |
| | |
| | 9. OK |
| | 10. OK |
| | 11. OK |
| | 12. OK |
| | 13. OK |
| | 14. OK |
| | 15. OK |
| | 16. OK |
| | |
| | 17. SWA1 PLANS SHALL BE ROUTED TO THE STATE OF FLORIDA, |
| | DEPT OF BUSINESS REGULATION, DIVISION OF BUSINESSAND |
| | RESTAURANT FOR REVIEW. A MINIMUM OF 3 SETS OF PLANS |
| | SHALL BE REVIEWED AND STAMPED BY DBR AND THE TWO PAGE |
| | "WORKSHEETS" SHALL BE ATTACHED TO THE STAMPED SHEETS |
| | PRIOR TO RESUBMITTING TO THE CITY FOR REVIEW. SECTION |
| | 102.2.1. |
| | ****RESPONSE NOTED, BUT THIS SHALL BE ADDRESSED PRIOR |
| | TO APPROVAL FOR PERMIT. |
| | ******RESPONSE NOTED, BUT THERE WERE NO SHEETS FOUND |
| | WITH THE DBPR PLAN REVIEW STAMP ON THEM. PLEASE SUBMIT |
| | A STAMPED SHEET IN EACH OF THE THREE SETS OF PLANS |
| | SUBMITTED FOR REVIEW IF THE PLANS FOR THE SUBWAY ARE TO |
| | BE THE PLANS FOR THE BUILD-OUT. |
| | |
| | 18. OK |
| | 19. OK |
| | 20. OK |
| | 21. OK |
| | 22. OK |
| | 23. OK |
| | 24. OK |
| | 25. OK |
| | 26. OK |
| | 27. OK |
| | 28. OK |
| | 29. OK |
| | 30. OK |
| | 31. OK |
| | 32. OK |
| | 33. OK |
| | 34. OK |
| | 35. OK |
| | 36. OK |
| | 37. OK |
| | 38. OK |
| | 39. OK |
| | 40. OK |
| | 41. OK |
| | 42. OK |
| | 43. OK |
| | 44. OK |
| | 45. OK |
| | |
| | 46. SHT GP2 DETAIL 4 SUBMIT THE MANUF SPECIFICATION |
| | SHEETS FOR FS3 AS SHOWN. SPECS SHALL SHOW |
| | LISTING/APPROVAL. SECTION 303. |
| | ****RESPONSE NOTED, BUT NOTHING IS SHOWN TO INDICATE |
| | THE REFERENCE STANDARD TO WHICH THE FS3 FLOOR SINK IS |
| | MANUFACTURED ON THE MANUF. SHEETS. NO APPROVAL FOR |
| | FIXTURE WITH EXTENTION. |
| | ******RESPONSE NOTED, BUT THE TRENCH DRAIN IS STILL |
| | SHOW IN THE MILK COOLER. PLEASE CLARIFY. PLEASE DELETE |
| | THE TRENCH DRAIN IF THERE IS NOT CONNECTION TO THE |
| | SANITARY SYSTEM. |
| | |
| | 47. OK |
| | 48. OK |
| | 49. OK |
| | 50. OK |
| | 51. OK |
| | 52. OK |
| | 53. OK |
| | 54. OK |
| | 55. OK - ALL INDIVIDUAL D.F'S |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID |
| | SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY |
| | ON TOP OF THE COLLATED PLANS TO BE REVIEWED. ALSO TO |
| | HELP EXPEDITE YOUR PERMIT, SUBMIT MARKED UP SET OF |
| | PLUMBING SHEETS. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | ****NO RESPONSE, MARKED UP PLUMBING SHEETS HAVE NOT |
| | BEEN RESUBMITTED. |
| | |
| | **********NEW COMMENTS********** |
| | |
| | 1B. SHT GP2 DETAIL 4 CONNECTION TO THE EXTENDED SUMP |
| | FOR THE FLOOR SINK IS NOT APPROVED. PER SECTION 303.2 |
| | ALL MATERIALS USED SHALL BE INSTALLED IN STRICT |
| | ACCORDANCE WITH THE STANDARDS UNDER WHICH THE MATERIALS |
| | ARE ACCEPTED AND APPROVED. ALSO PER SECTION 706.1 ALL |
| | CONNECTIONS AND CHANGED IN DIRECTION OF THE SANITARY |
| | DRAINAGE SYSTEM SHALL BE MADE WITH APPROVED DRAINAGE |
| | FITTINGS. CUTTING A HOLE IN THE PIPE AND GLUING A |
| | REPAIR COUPLING TO IT DOES NOT HAVE AN APPROVAL] |
| | ******RESPONSE NOTED, BUT THE TRENCH DRAIN IS STILL |
| | SHOW IN THE MILK COOLER. PLEASE CLARIFY. PLEASE DELETE |
| | THE TRENCH DRAIN IF THERE IS NOT CONNECTION TO THE |
| | SANITARY SYSTEM. |
| | |