Plan Review Notes
Plan Review Notes For Permit 07050729
Permit Number 07050729
Review Stop P
Sequence Number 3
Notes
Date Text
2007-12-03 14:48:39DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 BUILDING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 WEST PALM BEACH MUNICIPAL CODE
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 ****FROM PREVIOUS REVIEW. COMMENT NUMBERS TO REMAIN THE
 SAME.
 ******FROM PREVIOUS REVIEW:
  
 1. OK
 2. OK
 3. OK
 4. OK
 5. OK
 6. OK
 7. OK
 8. OK
  
 9. OK
 10. OK
 11. OK
 12. OK
 13. OK
 14. OK
 15. OK
 16. OK
  
 17. SWA1 PLANS SHALL BE ROUTED TO THE STATE OF FLORIDA,
 DEPT OF BUSINESS REGULATION, DIVISION OF BUSINESSAND
 RESTAURANT FOR REVIEW. A MINIMUM OF 3 SETS OF PLANS
 SHALL BE REVIEWED AND STAMPED BY DBR AND THE TWO PAGE
 "WORKSHEETS" SHALL BE ATTACHED TO THE STAMPED SHEETS
 PRIOR TO RESUBMITTING TO THE CITY FOR REVIEW. SECTION
 102.2.1.
 ****RESPONSE NOTED, BUT THIS SHALL BE ADDRESSED PRIOR
 TO APPROVAL FOR PERMIT.
 ******RESPONSE NOTED, BUT THERE WERE NO SHEETS FOUND
 WITH THE DBPR PLAN REVIEW STAMP ON THEM. PLEASE SUBMIT
 A STAMPED SHEET IN EACH OF THE THREE SETS OF PLANS
 SUBMITTED FOR REVIEW IF THE PLANS FOR THE SUBWAY ARE TO
 BE THE PLANS FOR THE BUILD-OUT.
  
 18. OK
 19. OK
 20. OK
 21. OK
 22. OK
 23. OK
 24. OK
 25. OK
 26. OK
 27. OK
 28. OK
 29. OK
 30. OK
 31. OK
 32. OK
 33. OK
 34. OK
 35. OK
 36. OK
 37. OK
 38. OK
 39. OK
 40. OK
 41. OK
 42. OK
 43. OK
 44. OK
 45. OK
  
 46. SHT GP2 DETAIL 4 SUBMIT THE MANUF SPECIFICATION
 SHEETS FOR FS3 AS SHOWN. SPECS SHALL SHOW
 LISTING/APPROVAL. SECTION 303.
 ****RESPONSE NOTED, BUT NOTHING IS SHOWN TO INDICATE
 THE REFERENCE STANDARD TO WHICH THE FS3 FLOOR SINK IS
 MANUFACTURED ON THE MANUF. SHEETS. NO APPROVAL FOR
 FIXTURE WITH EXTENTION.
 ******RESPONSE NOTED, BUT THE TRENCH DRAIN IS STILL
 SHOW IN THE MILK COOLER. PLEASE CLARIFY. PLEASE DELETE
 THE TRENCH DRAIN IF THERE IS NOT CONNECTION TO THE
 SANITARY SYSTEM.
  
 47. OK
 48. OK
 49. OK
 50. OK
 51. OK
 52. OK
 53. OK
 54. OK
 55. OK - ALL INDIVIDUAL D.F'S
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID
 SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY
 ON TOP OF THE COLLATED PLANS TO BE REVIEWED. ALSO TO
 HELP EXPEDITE YOUR PERMIT, SUBMIT MARKED UP SET OF
 PLUMBING SHEETS. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 ****NO RESPONSE, MARKED UP PLUMBING SHEETS HAVE NOT
 BEEN RESUBMITTED.
  
 **********NEW COMMENTS**********
  
 1B. SHT GP2 DETAIL 4 CONNECTION TO THE EXTENDED SUMP
 FOR THE FLOOR SINK IS NOT APPROVED. PER SECTION 303.2
 ALL MATERIALS USED SHALL BE INSTALLED IN STRICT
 ACCORDANCE WITH THE STANDARDS UNDER WHICH THE MATERIALS
 ARE ACCEPTED AND APPROVED. ALSO PER SECTION 706.1 ALL
 CONNECTIONS AND CHANGED IN DIRECTION OF THE SANITARY
 DRAINAGE SYSTEM SHALL BE MADE WITH APPROVED DRAINAGE
 FITTINGS. CUTTING A HOLE IN THE PIPE AND GLUING A
 REPAIR COUPLING TO IT DOES NOT HAVE AN APPROVAL]
 ******RESPONSE NOTED, BUT THE TRENCH DRAIN IS STILL
 SHOW IN THE MILK COOLER. PLEASE CLARIFY. PLEASE DELETE
 THE TRENCH DRAIN IF THERE IS NOT CONNECTION TO THE
 SANITARY SYSTEM.
  
 REVIEW BY KEN STEVENS