Plan Review Notes
Plan Review Notes For Permit 07050729
Permit Number 07050729
Review Stop E
Sequence Number 3
Notes
Date Text
2007-10-21 14:31:02*** DENIED 3RD REVIEW ***
  
 ** PLEASE SEE SOME OF THE ITEMS FROM PREVIOUS REVIEW
 STILL REMAIN. SOME OF THESE ITEMS BELOW CAN BE SET UP
 AS A *PROVISO* AS PREVIOUSLY GONE OVER IN MEETING HELD
 SEPTEMBER 28TH, 2007.
 SOME OF THESE MAY ALSO BE ADDRESSED AT THIS TIME AS
 PLANS ARE COMING BACK FOR SOME OF THE CORRECTIONS.
 PLEASE SEE THE MAIN COMMENT BELOW IS TO HAVE THE ENERGY
 CALCULATIONS COORDINATE AND COMMENTS WITH RESPECT TO
 FLORIDA STATUTES AND FLORIDA ADMINISTRATIVE CODE.
  
 1) NOTE: PLEASE SEE TWO OF THE THREE SETS OF ENERGY
 CALCULATIONS AS SUBMITTED CONTAIN A PHOTO-COPIED
 SIGNATURE FOR THE OWNER AGENT.
 NEEDS TO BE ORIGINAL. (ENGINEERS ARE OK) 13-103.1.1.1,
 FBC 106.5, ADDITIONAL INFORMATION FOR RECORDS.
  
 2) NOTE: PLEASE SEE ONE COPY OF THE FIRE PUMP
 CALCULATIONS WERE SUBMITTED IN PENCIL WHICH CAN NOT BE
 ACCEPTED.
 PLEASE ALSO SEE THIS SAME CALCULATION SHEET MUST
 CONTAIN THE COMPLETE TITLE BLOCK AND INFORMATION FOR
 DESIGNER/FIRM OF RECORD PER FAC 61G15-23.002. (ALL
 THREE SETS DO NOT CONTAIN THE NEEDED TITLE BLOCK).
  
 3) NOTE: PLEASE SEE SEPARATE SPACES IN AREAS WHICH ARE
 NOT 24HRS FOR LIGHTING CONTROLS IS STILL IN QUESTION.
 THIS IS FOR AREAS SUCH AS OPTICAL STORE, ETC. RESPONSE
 MENTIONS TO SEE EM-1 FOR OVER RIDES. THE EM-1 SHEET
 DOES CONTAIN THE ROP FOR THE OVER RIDE PANEL AT THESE
 LOCATIONS, HOWEVER IN THESE SPACES THERE ARE AREAS
 WHICH CONTAIN FLOOR TO CEILING HEIGHT PARTITIONS WHICH
 ARE CONSIDERED SEPARATE SPACES. BASED ON THE PLANS AND
 THE SWITCHING SYMBOLS UTILIZED, THESE ARE STANDARD
 SWITCHES WHICH DO NOT PROVIDE ANY AUTOMATION. PLEASE
 EXPLAIN HOW THE ENERGY CALCULATIONS INPUT DATA REPORT
 INDICATES *MANUAL ON/OFF* WHEN SOME OF THESE LOCATIONS
 INDEED ARE REQUIRED OR HAVE AUTOMATED LIGHTING
 CONTROLS.
 13-415.1.ABC.1.1, .1.2.
  
 4) NOTE: PLEASE SEE PREVIOUS REVIEW NOTES REQUESTED FOR
 COORDINATION BETWEEN THE INPUT DATA REPORT, ENERGY
 CALCULATIONS, PLANS AND LIGHTING FIXTURE LEGEND. THIS
 WAS GONE OVER ON THE PHONE CONFERENCE CALLS AND WAS
 MENTIONED SPECIFICALLY SEVERAL TIMES IN MEETING BEFORE
 PLANS WERE RE-SUBMITTED. IT WAS ALSO MENTIONED THAT
 AFTER THE MEETING THAT THE CALCULATIONS SHOULD BE GONE
 OVER AND THAT IF THERE WERE ANY ITEMS WHICH NEEDED TO
 BE ADDRESSED THAT THE REVISE CALCULATIONS AND INPUT
 DATA REPORTS COULD BE BROUGHT IN AND SUBMITTED AS LONG
 AS REVIEW HAD NOT COMMENCED.
 ** FUTURE REFERENCES BELOW TO THE INPUT DATA REPORT
 WILL BE IDR.
 PLEASE SEE THE SUMMARY SHEET FOR EXTERIOR LIGHTING AND
 THE IDR INFORMATION FOR EXTERIOR LIGHTING DO NOT
 CORRELATE.
 PLEASE SEE THESE NUMBERS HAVE BEEN REVISED ONCE AGAIN
 FROM THE PREVIOUS REVIEWED SHEETS AS THE SUMMARY
 WATTAGE DESIGN AND ALLOWANCES HAVE CHANGED
 SUBSTANTIALLY.
 PLEASE SEE THE WATTAGE ON THE IDR SHEET #28 FOR
 EXTERIOR LIGHTING ADDS UP TO DIFFERENT NUMBER THAN WHAT
 IS SHOWN ON THE SUMMARY SHEET #5. PLEASE ALSO SEE THE
 WATTAGE WHICH ADDS UP ON THE SUMMARY SHEET #5 IS
 DIFFERENT FROM THE TOTAL DESIGNED AND ALLOWANCE. PLEASE
 EXPLAIN HOW THESE NUMBERS ARE DIFFERENT AND WHY THE DO
 NOT SEEM TO CORRELATE.
  
 ** PLEASE SEE THE EXTERIOR LIGHTING PLANS/LEGEND FOR
 FIXTURES INDICATES PHOTO-SENSOR CONTROL YET PLEASE
 INDICATE WHERE THIS IS ON PLANS.
 THIS PART OF THE COMMENT STEMS FROM 13-415.2.ABC.1.3
 WHICH ONLY EXEMPT SIGN LIGHTING SUCH AS THE LIGHTING ON
 THE MONUMENT SIGN *IF* THESE LIGHTING FIXTURES ARE
 CONTROLLED SEPARATELY FROM THE OTHER SITE/PARKING LOT
 LIGHTING.
 PLEASE CLARIFY WHERE THE TYPE #42 FIXTURES ARE ON
 PLANS. THESE ARE IN QUESTION AS THEY COULD NOT BE FOUND
 ON E-1/E1.2. (ARE THESE FIXTURES ON THE IDR MEANT TO BE
 THE MONUMENT SIGN FIXTURES?)
  
 **PLEASE SEE THE INTERIOR LIGHTING IDR. PLEASE SEE PAGE
 13 *IN ZONE: GROCERY SALES AHU1,2 WHICH INDICATES
 14-234 WATT FIXTURES WHICH APPEARS TO BE TYPE #46 ON
 FIXTURE LEGEND. PLEASE CLARIFY WHERE THESE FIXTURES ARE
 ON PLANS E1.
  
 ALL OLD ENERGY CALCULATIONS WHICH WERE IN NEW BOOKS
 WERE REMOVED. ONE COPY OF THE OLD CALCULATIONS AND NEW
 CALCULATIONS WERE RETAINED.
  
 AS MENTIONED PREVIOUSLY PLEASE GO OVER ALL LIGHTING ON
 PLANS AND COORDINATE WITH THE ENERGY CALCULATIONS AND
 INPUT DATA REPORT.
 IF THERE IS CLARIFICATION WHICH CAN BE GIVEN, PLEASE
 CONTACT THIS REVIEWER.
  
 5) NOTE: AS GONE OVER IN MEETING, AIC RATINGS WILL BE
 REQUIRED TO BE STATED ON PLANS BEFORE INSPECTION. THIS
 WILL BE PART OF A PROVISO.
  
 6) NOTE: AS GONE OVER IN MEETING, COPPER AND ALUMINUM
 CONDUCTORS WILL NEED TO BE REVISED BASED ON ACTUAL
 INSTALLATION BEFORE INSPECTION. THIS WILL BE PART OF A
 PROVISO.
  
 7) NOTE: PLEASE SEE THAT SOME OF THE SIGNATURE
 VERIFICATION LETTERS IN BOOKS ARE STILL COPIES HOWEVER
 ONLY ONE COPY IS NEEDED TO BE ORIGINAL FOR OUR RECORDS.
 WE WILL RETAIN BOOK ONCE PERMIT IS ISSUED WITH ORIGINAL
 SIGNATURES.
 * THIS IS NOTED ONLY FOR INFORMATION.
  
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]