Plan Review Notes
Plan Review Notes For Permit 07050729
Permit Number 07050729
Review Stop P
Sequence Number 2
Notes
Date Text
2007-08-30 08:57:16DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 BUILDING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 WEST PALM BEACH MUNICIPAL CODE
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 ****FROM PREVIOUS REVIEW. COMMENT NUMBERS TO REMAIN THE
 SAME.
  
 1. OK
 2. OK
  
 3. SHT P2 DETAILS 5 & 6 SHOW THE SLOPE TO THE DRAIN.
 DETAIL 7B SHOWS NO DRAIN. PLEASE CLARIFY. SECTION
 106.1.1.
 ****RESPONSE NOTED, BUT THE SLOPE TO THE DRAIN IS NOT
 INDICATED ON DETAILS 5 & 6.
  
 4. OK
 5. OK
 6. OK
 7. OK
 8. OK
  
 9. SHT A5.6 DETAIL 7. SHOW COMPLIANCE WITH THE
 FOLLOWING:
 A. 11-4.19.2 OK
 B. 11-4.19.4 EXPOSED PIPES & SURFACES ****NOT
 ADDRESSED
 C. 11-4.19.5 FAUCETS ****NOT ADDRESSED
  
 10. SHT A-9 DETAIL 13. SHOW COMPLIANCE WITH THE
 FOLLOWING:
 A. 11-4.24.4 SINK DEPTH ****NOT ADDRESSED
 B. 11-4.24.5 CLEAR FLOOR SPACE ****NOT SHOWN ON THE
 FLOOR PLAN
 C. 11-4.24.6 OK
 D. 11-4.24.7 OK
  
 11. OK
 12. OK
 13. OK
 14. OK
 15. OK
 16. OK
  
 17. SWA1 PLANS SHALL BE ROUTED TO THE STATE OF FLORIDA,
 DEPT OF BUSINESS REGULATION, DIVISION OF BUSINESSAND
 RESTAURANT FOR REVIEW. A MINIMUM OF 3 SETS OF PLANS
 SHALL BE REVIEWED AND STAMPED BY DBR AND THE TWO PAGE
 "WORKSHEETS" SHALL BE ATTACHED TO THE STAMPED SHEETS
 PRIOR TO RESUBMITTING TO THE CITY FOR REVIEW. SECTION
 102.2.1.
 ****RESPONSE NOTED, BUT THIS SHALL BE ADDRESSED PRIOR
 TO APPROVAL FOR PERMIT.
  
 18. OK
 19. OK
 20. OK
 21. OK
 22. OK
  
 23. SHT P1 SHOW THE FOUNDATION PIPING INDICATED ON
 DETAIL 14 SHEET P3. SECTION 106.1.1.
 ****RESPONSE NOTED, BUT THE PIPING SHALL BE SHOWN ON
 THE PLANS. PLEASE INDICATE WHERE THE PIPING WILL BE
 RUN.
  
 24. OK
 25. OK
 26. OK
  
 27.SHT P2 DWV RISER DIAGRAM DOES NOT REFLECT THE
 FLOOR PLAN. THERE IS NO L8 FIXTURE SHOWN IN THE WOMENS
 TOILET ROOM ON THE FLOOR PLAN.--THE BRANCH LINE
 RUNS TO THE CENTER OF THE MIDDLE LAV & NO 4TH LAV SHOWN
 ON THE FLOOR PLAN, BUT SHOWS IT RUNNING TO A L8 &
 CONNECTING TO 3 L6 LAVS ON THE RISER. PLEASE CORRELATE
 FLOOR PLAN & RISER DIAGRAM. SECTION 106.1.1.
 ****RESPONSE NOTED, BUT NOW THE FLOOR PLAN SHOWS ONE
 L-8WITH THE OTHERS L-6. THE RISER DIAGRAM SHOWS ALL
 L-6. PLEASE CLARIFY.
  
 28. OK
 29. OK
 30. OK
 31. OK
  
 32. SHT P3 DETAIL 4 REAR OFFICE DWV RISER DOES NOT
 REFLECT THE FLOOR PLAN. ONLY 1 DRINKING FOUNTAIN IS
 SHOWN.--MEN & WOMEN ACCESSIBLE LAVS ARE MISSING IN
 THE STALLS. FIG 30E.
 ****RESPONSE NOTED, BUT THE PRODUCT LITERATURE UNDER
 EXHIBIT TAB #13 SHOWS ONLY ONE TRAP. PLEASE SUBMIT
 MANUF. SPECIFICATIONS THAT SHOW EACH DRINKING FOUNTAIN
 SEPARATELY TRAPPED.
  
 33. SHT P3 DETAIL 3 PHOTO LAV PLUMBING RISERS. FLOOR
 DRAIN IS NOT AN APPROVED INDIRECT WASTE RECEPTOR.
 SECTIONS 802.3 & 802.3.2.--SHUT OFF VALVES ARE
 REQUIRED ON THE SUPPLY LINES TO EACH HOSE BIBB. SECTION
 606.2(2).
 ****RESPONSE NOTED, BUT THE HOSE BIBB SHUT OFF VALVES
 HAVE NOT BEEN ADDRESSED.
  
 34. SHT P3 THE GREASE INTERCEPTOR SHALL BE SIZED BY THE
 UTILITY DEPT. ENVIRONMENTAL COMPLIANCE DIVISION.
 CONTACT RODNEY COMPO, (561) 822-2272, E-MAIL
 [email protected], OR CALVIN WILLIAMS (561) 822-2284,
 E-MAIL [email protected], OR FAX THEM (561) 822-2297.
 CITY CODE ARTICLE III SECTION 90-125.
 ****RESPONSE NOTED. I WILL GET VERIFICATION FROM MR.
 WILLIAMS.
  
 35. SHT P3 SUBMIT MANUF. SPECIFICATIONS ON THE SUMP
 PUMP& THE PUMP FOR THE LIFT STATION. PUMPS SHALL BE
 LISTED. SECTION 303.4. (DETAILS 13 & 14). ****RESPONSE
 NOTED, BUT MANUF. SPECIFICATIONS FOR THE PUMPS WITH THE
 REQUIRED LISTINGS HAS NOT BEEN FOUND.
  
 36. OK
 37. OK
 38. OK
 39. OK
 40. OK
 41. OK
 42. OK
 43. OK
 44. OK
  
 45. SHT GP2 DETAIL 4 THE AIR BREAK IS NOT APPROVED. A
 MINIMUM 8" AIR GAP IS REQUIRED PER SECTIONS 802.1.2 &
 802.2.2.1. PLEASE CORRECT THE DETAIL AND SHOW REQUIRED
 AIR GAP.
 ****RESPONSE NOTED, BUT WITH THE TRENCH DRAIN OUTLET
 BELOW THE TOP OF THE FLOOD RIM LEVEL OF THE EXTENTION,
 THERE IS NO AIR BREAK. THIS WOULD ONLY BE AN AIR BREAK
 IF THE FLOOD RIM LEVEL IS BELOW THE TRENCH DRAIN
 OUTLET.
  
 46. SHT GP2 DETAIL 4 SUBMIT THE MANUF SPECIFICATION
 SHEETS FOR FS3 AS SHOWN. SPECS SHALL SHOW
 LISTING/APPROVAL. SECTION 303.
 ****RESPONSE NOTED, BUT NOTHING IS SHOWN TO INDICATE
 THE REFERENCE STANDARD TO WHICH THE FS3 FLOOR SINK IS
 MANUFACTURED ON THE MANUF. SHEETS. NO APPROVAL FOR
 FIXTURE WITH EXTENTION.
  
 47. OK
  
 48. SHT GP3 ROOF STORM RISER DIAGRAMS. INDICATE THE
 ROOF DRAIN SIZE FOR RISER AT COLUMN 8.5 - 9.5/B - K.
 SECTION 106.1.1 & TABLE 1106.3.
 ****RESPONSE NOTED, BUT THE ROOF DRAIN SIZE IS STILL
 NOT INDICATED.
  
 49. OK
 50. OK
 51. OK
 52. OK
  
 53. SHT GP4 GROCERY PLUMBING EQUIPMENT CONNECTION
 SCHEDULE. FIXTURES B36 & MG 21 CAN NOT BE FOUND. PLEASE
 CLARIFY AND CORRELATE THE SCHEDULE AND FLOOR PLAN.
 SECTION 106.1.1.
 ****RESPONSE NOTED, BUT TWO STOCK ROOMS WERE FOUND ON
 SHT GP5 AND NO MG21 WAS LOCATED IN EITHER. PLEASE
 INDICATE SHEET AND LOCATION OF THIS FIXTURE.
  
 54. SUBMIT MANUF SPECIFICATION SHEETS FOR THE REVERSE
 OSMOSIS FILTER. THE FILTER SHALL MEET THE REQUIREMENTS
 OF NSF 58. SECTION 611.2.
 ****RESPONSE NOTED, BUT NO INDICATION THAT THE RO
 FILTER MEETS NSF 58 IS SHOWN.
  
 55. SHT C1 PLUMBING FIXTURE COUNTS INDICATES 5 DRINKING
 FOUNTAINS AND ONE WATER COOLER. ONLY 3 DRINKING
 FOUNTAINS HAVE BEEN LOCATED. IF A HI-LOW DRINKING
 FOUNTAIN HAS ONLY ONE TRAP AND ONE WATER SUPPLY IT IS
 CONSIDERED ONE DRINKING FOUNTAIN, NOT TWO AS EACH
 FIXTURE IS REQUIRED TO HAVE ITS OWN TRAP AND WATER
 SUPPLY. PLEASE INDICATE THE LOCATION OF THE REQUIRED
 DRINKING FOUNTAINS AND THE REQUIRED WATER COOLER. TABLE
 403.1.
 ****RESPONSE NOTED, BUT THE MANUF. SPECIFICATION SHEETS
 SHOWS THE UNIT WITH ONLY ONE TRAP PER HI/LOW. PLEASE
 SUBMIT MANUF. SPECIFICATIONS SHOWING SEPARATE TRAPS TO
 EACH UNIT. ALSO PLEASE INDICATE THE LOCATION OF THE
 BOTTLE WATER COOLER ON THE PLANS AND INDICATE THE
 LOCATION IN THE COMMENT RESPONSE.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID
 SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY
 ON TOP OF THE COLLATED PLANS TO BE REVIEWED. ALSO TO
 HELP EXPEDITE YOUR PERMIT, SUBMIT MARKED UP SET OF
 PLUMBING SHEETS. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 ****NO RESPONSE, MARKED UP PLUMBING SHEETS HAVE NOT
 BEEN RESUBMITTED.
  
 **********NEW COMMENTS**********
  
 1B. SHT GP2 DETAIL 4 CONNECTION TO THE EXTENDED SUMP
 FOR THE FLOOR SINK IS NOT APPROVED. PER SECTION 303.2
 ALL MATERIALS USED SHALL BE INSTALLED IN STRICT
 ACCORDANCE WITH THE STANDARDS UNDER WHICH THE MATERIALS
 ARE ACCEPTED AND APPROVED. ALSO PER SECTION 706.1 ALL
 CONNECTIONS AND CHANGED IN DIRECTION OF THE SANITARY
 DRAINAGE SYSTEM SHALL BE MADE WITH APPROVED DRAINAGE
 FITTINGS. CUTTING A HOLE IN THE PIPE AND GLUING A
 REPAIR COUPLING TO IT DOES NOT HAVE AN APPROVAL.
  
 REVIEW BY KEN STEVENS