| Plan Review Notes For Permit 07050729 |
| Permit Number |
07050729 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2007-08-21 11:26:17 | REVIEW #: 2 | | | STATUS: PENDING | | | | | | ALL PREVIOUS REVIEW COMMENTS HAVE BEEN | | | ADDRESSED/CORRECTED WITH THE EXCEPTION OF THE | | | FOLLOWING: | | | | | | COMMENT #4: THE ROOF TYPE AND R-VALUE SHOWN ON | | | CALCULATIONS WAS NOT CORRECTED FROM PREVIOUS | | | CALCULATIONS. PLEASE CORRECT AND RESUBMIT. | | | COMMENT #5: PROVIDE INSTALLATION INSTRUCTIONS FOR RTU | | | CLIPS USED TO FASTEN UNITS TO CURBS SHOWING NUMBER AND | | | LOCATION OF CLIPS AND SCREWS. | | | | | | IF THERE ARE NO OTHER OUTSTANDING ISSUES RELATED TO | | | PERMIT ISSUANCE AFTER THE REMAINING REVIEW STOPS, | | | AMENDED CALCULATIONS MAY BE SUBMITTED TO SATISFY | | | COMMENT #4. OTHERWISE, PROVIDE CORRECTED CALCULATIONS | | | AND INSTALLATION INSTRUCTIONS FOR A SATISFACTORY | | | COMPLETION OF THIS REVIEW. | | | | | | RONALD J REGUEIRO | | | 561.805.6719 | | | [email protected] |
|