Plan Review Notes
Plan Review Notes For Permit 07050729
Permit Number 07050729
Review Stop E
Sequence Number 2
Notes
Date Text
2007-09-05 18:22:082007-09-05 18:22:08
  
 ** DENIED 2ND REVIEW **
  
 WAL-MART
 SUPERCENTER
 4225 45TH ST
  
 **PLEASE SEE THERE ARE SOME COMMENTS FROM PREVIOUS
 REVIEW WHICH ARE STILL IN NEED OF ADDRESSING.
  
 **PLEASE ALSO SEE THERE ARE SOME NEW COMMENTS BASED ON
 PLANS SUBMITTED AND INFORMATION PROVIDED.
  
 ** THIS IS THE FIRST REVIEW UNDER PERMIT APPLICATION.
  
 1) NOTE: PLEASE SEE PREVIOUS NOTE #2 WITH RESPECT TO
 THE CODES TO BE STATED ON PLANS.
 PLEASE SEE THE COVER SHEET WHICH INDICATES 2002
 NATIONAL ELECTRICAL CODE W/2006 REVISIONS. THIS MUST BE
 A MISPRINT AS THERE IS NO 2002 W/ 2006 REVISIONS OF THE
 NEC. PLEASE SEE THE NFPA-70 2005 IS ALREADY LISTED.
  
  
 2) NOTE: PLEASE SEE PREVIOUS REVIEW NOTE #7. PLEASE BE
 SURE THE CERTIFICATION SHEETS ON THE ENERGY
 CALCULATIONS ARE FILLED OUT. PLEASE SEE THE OWNER AGENT
 IS MISSING, THE *PREPARED BY:* ETC.
 PLEASE SEE THE ENERGY CALCULATIONS ARE REQUIRED TO BE
 SIGNED, DATED SEALED AND CONTAIN ALL INFORMATION FOR
 ALL TRADES FOR CERTIFICATION PER FBC 2004 W/2006
 REVISIONS TO 13-103.1.1.1, FAC 61G15-23.002
  
  
 3) NOTE: PLEASE SEE 2004 FBC AS COMPLIANCE WITH CHAPTER
 13 THE FLORIDA ENERGY CODE IS NOT COMPLETED AT THIS
 TIME. MUCH OF THE PREVIOUS COMMENTS WERE ADDRESSED BY
 THE FACT THIS FACILITY IS NOTED AS A 24HR STORE. PLEASE
 KNOW SOME AREAS IN THIS STORE FOR 24HR OPERATION STILL
 NEEDS TO BE VERIFIED. PLEASE SEE 13-415.1.ABC.1.1,
 .1.2.
 PLEASE SEE AREAS FOR EXAMPLE, THE SUBWAY, OPTICAL
 STORE, LAB ROOM, WAITING AREAS, THE BANK, THE PHARMACY,
 THE SALON ETC. THESE ARE ALL LOCATIONS WHICH WOULD
 REQUIRE AUTOMATED SHUTTING DOWN OF LIGHTING. PLEASE
 KNOW THE PLANS DO NOT INCLUDE INFORMATION THAT THESE
 FACILITIES ARE OPEN 24HRS.MANY STORES DO NOT HAVE
 THESE INTERIOR *TENANT* AREAS OPERATING 24HRS WHICH
 WILL REQUIRE LIGHTING CONTROLS.
 PLEASE ADJUST AS NEEDED AND PROVIDE CONTROLS, ETC.
  
  
 4) NOTE: PLEASE SEE THE SUBMITTED ENERGY CALCULATIONS
 NEED TO COORDINATE WITH THE PLANS AND THE LIGHTING
 LEGEND FOR THE NUMBER OF FIXTURES, THE WATTAGE OF
 FIXTURES ETC.
 PLEASE SEE FOR EXAMPLE, THE EXTERIOR LIGHTING IN THE
 INPUT DATA REPORT DOES NOT MATCH WITH THE PLANS. PLEASE
 ALSO SEE THE PLANS ARE MISSING LIGHTING IN THE FRONT OF
 THE STORE FOR ENTRANCE/CANOPY AREA SIDE WALK ETC THESE
 COULD NOT BE VERIFIED.
 PLEASE SEE THERE ARE AREAS ON THE PLANS WHERE THE
 NUMBER OF FIXTURES AS INDICATED ARE SHOWN WITH A
 DIFFERENT FIXTURE COUNT ON THE ENERGY CALCULATIONS.
 PLEASE GO OVER ALL OF THESE FOR FIXTURE COUNT AND
 WATTAGE.(EXAMPLE: VISION/OPTICAL STORE)
 PLEASE SEE FIXTURES SUCH AS FLAG POLE LIGHT WHICH COULD
 NOT BE LOCATED ON IDR.
 PLEASE SEE THE IDR WHICH CONTAINS FIXTURES AT WATTAGES
 FOR FIXTURES WHICH NEED TO COORDINATE WITH THE LEGEND.
 13-415.1.B
 PLEASE SEE THE PLANS INDICATE TRACK LIGHTING TO BE
 INSTALLED IN SOME LOCATIONS: WHERE AND HOW ARE THESE
 LOCATED IN THE IDR AND MEET 13-415.2.ABC.1.2 (3)?
  
  
 5) NOTE: PLEASE SEE THE SITE LIGHTING SHOWN ON E1.2
 CONTAINS A NOTE TO SEE SITE/CIVIL PLANS FOR FIXTURE
 TYPE. AS THE SITE PLANS IN THIS ROLL DOES NOT CONTAIN
 THIS INFORMATION AND THE CIVIL PLANS ARE NOT IN THESE
 SETS SUBMITTED THE SPECIFIC INFORMATION FOR THESE
 FIXTURES COULD NOT BE LOCATED.
 PLEASE COMPLETE THIS INFORMATION ON THE ELECTRICAL
 PLANS SO THAT COORDINATION OF THE FIXTURES CAN BE DONE
 WITH THE ENERGY CALCULATIONS, LOAD CALCULATIONS,
 VOLTAGES, ETC. PLEASE SEE 13-415.2.ABC.1.3
 FBC 106.1.2, 106.1.1
  
 6) NOTE: PLEASE SEE THE PREVIOUS REVIEW REQUESTED A
 WORST CASE VOLTAGE DROP CALCULATION FOR BRANCH CIRCUIT
 AND FEEDERS. THIS INFORMATION WAS LOCATED ON A SEPARATE
 SHEET LOCATED IN THE SUBMITTAL BOOK. THIS INFORMATION
 SHOULD BE ON THE PLANS WHICH ARE PART OF THE SIGNED,
 DATED AND SEALED RECORD PLANS.
 PLEASE ALSO VERIFY THE SITE LIGHTING VD FOR WORST CASE
 AT ROAD WITH THE #10 AS SHOWN FOR LIGHT POLES.) PLEASE
 PROVIDE WORST CASE VOLTAGE DROP FOR BRANCH CIRCUITS AND
 FEEDERS PER 13-413.1.ABC.1
  
  
 7) NOTE: PLEASE SEE THE RISER SHOWS BOTH COPPER AND
 ALUMINUM, THE SPECIFIC TYPE PF CONDUCTORS INSTALLED
 WILL BE REQUIRED TO BE REVISED ONCE THE INSTALLATION
 AND CHOICE HAS BEEN MADE. THIS DOES NOT NEED TO BE
 REVISED AT THIS TIME, HOWEVER BEFORE INSPECTION.
  
  
 8) NOTE: PLEASE CLARIFY WHERE THE LIGHTING IS FOR
 OUTSIDE THE STORE ENTRANCES, OVERHEAD SIDEWALK AREA? IS
 THERE NOT GOING TO BE ANY LIGHTING OUTSIDE THE LENGTH
 OF THE STORE IN FRONT?
 FBC 106.3.5.1.2
  
  
 9) NOTE: PLEASE SEE THE PREVIOUS NOTE #10. THIS IS THE
 SAME COMMENT. THE SINGLE SHEET SUBMITTED DOES NOT MEET
 THE INFORMATION NEEDED FOR BOTH AS REQUESTED. THE
 PREVIOUS REVIEW ALSO REQUESTED THE MINIMUM RUNNING TIME
 BASED ON THE FUEL TO BE SUPPLIED TO BE STATED ON THE
 PLANS. THE RESPONSE LETTER MENTIONS NO MINIMUM TIMES
 ARE REQUIRED AND THAT EQUIPMENT WILL RUN AS LONG AS IT
 TAKES FOR READINGS, TESTING ETC. LETTER ALSO MENTIONS
 TO STATE A SPECIFIC CODE SECTION. PLEASE SEE THE
 PREVIOUS REVIEW NOTE WHICH GIVES NOT ONLY THE CODE
 EDITION, BUT SEVERAL SECTIONS OF THE CODE.
 PLEASE STATE THE RUNNING TIME WITH 100 PERCENT LOAD OF
 THE FIRE PUMP BASED ON THE ON-SITE FUEL BEING PROVIDED
 ON THE PLANS. IF THERE ARE QUESTIONS ON THIS PLEASE
 CALL. IF THE FIRE MARSHAL HAS ANY COMMENTS PLEASE BE
 SUE TO SEE THEIR REVIEW NOTES
 ** PREVIOUS REVIEW NOTE **
 PLEASE SUBMIT THE MANUFACTURES SPECS/CUT SHEETS FOR
 THE FIRE PUMP/FIRE PUMP CONTROLLER. IT IS KNOW THAT THE
 FS WORK WILL BE UNDER A SEPARATE PERMIT HOWEVER THESE
 ARE REQUIRED IN BASE BUILDING PLANS AND FOR REVIEW.
 PLEASE SUPPLY THE INFORMATION OF FS PLANS FOR THE
 MINIMUM TIMES FOR FIRE PUMP RUNNING AT 100%. PLEASE SEE
 NFPA-20 11.4.1, 11.4.3, 11.4.5 (ALL). PLEASE SEE OTHER
 TRADES FOR REVIEW OF SYSTEMS FOR FIRE PUMP.
 110.3, 90.7, FBC 106.1.2, 106.3.5.1.2
  
  
 10) NOTE: PLEASE SEE PREVIOUS NOTE # WITH REGARD TO THE
 RISER WHICH INDICATED A *KIRK-KEY* INTERLOCK BREAKER
 SCENARIO. THE RESPONSE LETTER MENTIONS THIS WAS REMOVED
 HOWEVER NOTE ON THE RISER STILL INDICATES THIS *QC*
 BREAKER AND THE PLANS ARE STILL INDICATING PROVISIONS
 FOR A PORTABLE GENERATOR.
 PLEASE CLARIFY AS RESPONSE MENTIONS THIS WAS BEING
 REMOVED???
  
  
 11) NOTE:PLEASE SEE PREVIOUS NOTE #12 WHICH REQUESTED
 TO COMPLETE THE AVAILABLE FAULT CURRENT ON PLANS AND TO
 INDICATE THE RATINGS. PLEASE SEE THE RISER NOW SEEMS TO
 HAVE THE AVAILABLE FAULT CURRENT ON THE LINE SIDE OF
 THE EQUIPMENT AND SERVICE PANELS, HOWEVER NOT ALL
 ACTUAL MINIMUM RATINGS FOR THIS EQUIPMENT SERIES OR
 OTHER WISE ARE STATED ON PLANS. PLEASE SEE SOME PANEL
 GIVE THEIR RATINGS AND SOME DO NOT. PLEASE COMPLETE THE
 INFORMATION FOR MAINS, PANELS, BREAKERS ETC. 110.9.
 FBC 106.3.5.1.2, 106.1.2, 106.1.1
  
  
 12) NOTE: PREVIOUS NOTE #13.
 PLEASE SUBMIT THE MANUFACTURES SPECS/CUT SHEETS FOR
 THE PROPOSED UPS. A SHEET WAS SUBMITTED HOWEVER LISTING
 FOR USE COULD NOT BE LOCATED/VERIFIED.
 IS THERE NO DISCONNECT ON THE LOAD SIDE OF THE UPS OR
 LINE SIDE PF THE PANEL LIU? PLEASE CLARIFY AS THE USE
 OF CORD AND PLUGS AS SHOWN IN DETAILS MAY ONLY BE USED
 FOR SOME INSTANCES. PLEASE SEE 110.3,
  
  
 13) NOTE: PLEASE SEE PREVIOUS NOTE #17 WITH RESPECT TO
 COLOR CODING OF CONDUCTORS. THE RESPONSE LETTER
 MENTIONS A *BOXED NOTE* WAS OR WOULD BE ADDED TO RISER
 SHEET E-4. THIS NOTE COULD NOT BE LOCATED.
 ** PREVIOUS REVIEW NOTE*
 PLEASE PROVIDE NOTES FOR COLOR CODING FOR 277/480V
 SYSTEMS AS BROWN, PURPLE, YELLOW.
 THE NEC DOES NOT GIVE THE COLOR CODING AND *ORANGE* IS
 FOR A HIGH-LEG SYSTEM WHICH THIS IS NOT.
 FBC 104.6, 90.4.
  
  
 14) NOTE: PLEASE SEE THE FA SHEETS NEED TO STATE THE
 FBC 2004 11-4.28.1, .2 AND .3(4) FOR DEVICES.
 THE LEVELS APPEAR TO BE OK AT THIS TIME HOWEVER ONLY
 NFPA-72 WAS STATED AND THE FBC HAS MORE STRINGENT
 REQUIREMENTS.
 THIS WAS PREVIOUS NOTE #19, AND CODE SECTIONS WERE
 ADDED HOWEVER THE PLANS NOW STATE THE 2001 FBC WHEN
 THIS SHOULD BE THE 2004 FBC. PLEASE ADJUST AS PROJECT
 IS UNDER THE 2004.
  
  
 15) NOTE: PLEASE SEE CODE SECTIONS NOTE DON MSB1 AND
 MSB2 ARE FROM THE 2002 NEC>
 PLEASE SEE THESE STATE 220.21 AND THIS IS 220.60 UNDER
 THE 2005 NEC.
 PLEASE REVISE AS PLANS ARE COMING BACK FOR OTHER
 CORRECTIONS AND CHANGES.
  
  
 16) NOTE: PLEASE SEE THAT NOT ALL FIXTURES ON PLANS ARE
 ON THE FIXTURE LEGEND.
 PLEASE SEE SHEET SWE1 FOR EXAMPLE AS THERE IS A FIXTURE
 *10A* YET THIS COULD NOT BE FOUND ON LEGEND? PLEASE
 COORDINATE ALL FIXTURES ALSO AS NOTED ABOVE IN OTHER
 COMMENTS. FBC 106.1.2
  
  
 17) NOTE: PLEASE KNOW THAT ANY SIGNATURE VERIFICATION
 LETTERS NEED TO BE ORIGINAL AND NOT PHOTO-COPIES ALONG
 WITH NEEDING THE RAISED SEAL WHEN SIGNING AND DATING.
 PLEASE SEE ONE LETTER WAS ORIGINAL AND ONE WAS A
 PHOTO-COPY.
 THESE WILL BE PLACED IN OUR SIGNATURE FILE FOR
 REFERENCE.
 FBC 106.1.2, 106.5. FS 471.025, FAC 61G15-23.002
  
  
  
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 ** PLEASE BE SURE TO SEE ANY COMMENTS FROM OTHER TRADES
 WHICH MAY AFFECT ELECTRICAL PLANS AND DESIGN CHANGES.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2007-09-05 10:11:522007-09-05 10:11:52
 REVIEW IN PROGRESS
2007-08-29 16:12:162007-08-29 16:12:16
 ONE ROLL/SET OF PLANS IN ELEC FOR REVIEW.
 REVIEW HAS NOT YET COMMENCED.