| | ** DENIED 2ND REVIEW ** |
| | |
| | WAL-MART |
| | SUPERCENTER |
| | 4225 45TH ST |
| | |
| | **PLEASE SEE THERE ARE SOME COMMENTS FROM PREVIOUS |
| | REVIEW WHICH ARE STILL IN NEED OF ADDRESSING. |
| | |
| | **PLEASE ALSO SEE THERE ARE SOME NEW COMMENTS BASED ON |
| | PLANS SUBMITTED AND INFORMATION PROVIDED. |
| | |
| | ** THIS IS THE FIRST REVIEW UNDER PERMIT APPLICATION. |
| | |
| | 1) NOTE: PLEASE SEE PREVIOUS NOTE #2 WITH RESPECT TO |
| | THE CODES TO BE STATED ON PLANS. |
| | PLEASE SEE THE COVER SHEET WHICH INDICATES 2002 |
| | NATIONAL ELECTRICAL CODE W/2006 REVISIONS. THIS MUST BE |
| | A MISPRINT AS THERE IS NO 2002 W/ 2006 REVISIONS OF THE |
| | NEC. PLEASE SEE THE NFPA-70 2005 IS ALREADY LISTED. |
| | |
| | |
| | 2) NOTE: PLEASE SEE PREVIOUS REVIEW NOTE #7. PLEASE BE |
| | SURE THE CERTIFICATION SHEETS ON THE ENERGY |
| | CALCULATIONS ARE FILLED OUT. PLEASE SEE THE OWNER AGENT |
| | IS MISSING, THE *PREPARED BY:* ETC. |
| | PLEASE SEE THE ENERGY CALCULATIONS ARE REQUIRED TO BE |
| | SIGNED, DATED SEALED AND CONTAIN ALL INFORMATION FOR |
| | ALL TRADES FOR CERTIFICATION PER FBC 2004 W/2006 |
| | REVISIONS TO 13-103.1.1.1, FAC 61G15-23.002 |
| | |
| | |
| | 3) NOTE: PLEASE SEE 2004 FBC AS COMPLIANCE WITH CHAPTER |
| | 13 THE FLORIDA ENERGY CODE IS NOT COMPLETED AT THIS |
| | TIME. MUCH OF THE PREVIOUS COMMENTS WERE ADDRESSED BY |
| | THE FACT THIS FACILITY IS NOTED AS A 24HR STORE. PLEASE |
| | KNOW SOME AREAS IN THIS STORE FOR 24HR OPERATION STILL |
| | NEEDS TO BE VERIFIED. PLEASE SEE 13-415.1.ABC.1.1, |
| | .1.2. |
| | PLEASE SEE AREAS FOR EXAMPLE, THE SUBWAY, OPTICAL |
| | STORE, LAB ROOM, WAITING AREAS, THE BANK, THE PHARMACY, |
| | THE SALON ETC. THESE ARE ALL LOCATIONS WHICH WOULD |
| | REQUIRE AUTOMATED SHUTTING DOWN OF LIGHTING. PLEASE |
| | KNOW THE PLANS DO NOT INCLUDE INFORMATION THAT THESE |
| | FACILITIES ARE OPEN 24HRS.MANY STORES DO NOT HAVE |
| | THESE INTERIOR *TENANT* AREAS OPERATING 24HRS WHICH |
| | WILL REQUIRE LIGHTING CONTROLS. |
| | PLEASE ADJUST AS NEEDED AND PROVIDE CONTROLS, ETC. |
| | |
| | |
| | 4) NOTE: PLEASE SEE THE SUBMITTED ENERGY CALCULATIONS |
| | NEED TO COORDINATE WITH THE PLANS AND THE LIGHTING |
| | LEGEND FOR THE NUMBER OF FIXTURES, THE WATTAGE OF |
| | FIXTURES ETC. |
| | PLEASE SEE FOR EXAMPLE, THE EXTERIOR LIGHTING IN THE |
| | INPUT DATA REPORT DOES NOT MATCH WITH THE PLANS. PLEASE |
| | ALSO SEE THE PLANS ARE MISSING LIGHTING IN THE FRONT OF |
| | THE STORE FOR ENTRANCE/CANOPY AREA SIDE WALK ETC THESE |
| | COULD NOT BE VERIFIED. |
| | PLEASE SEE THERE ARE AREAS ON THE PLANS WHERE THE |
| | NUMBER OF FIXTURES AS INDICATED ARE SHOWN WITH A |
| | DIFFERENT FIXTURE COUNT ON THE ENERGY CALCULATIONS. |
| | PLEASE GO OVER ALL OF THESE FOR FIXTURE COUNT AND |
| | WATTAGE.(EXAMPLE: VISION/OPTICAL STORE) |
| | PLEASE SEE FIXTURES SUCH AS FLAG POLE LIGHT WHICH COULD |
| | NOT BE LOCATED ON IDR. |
| | PLEASE SEE THE IDR WHICH CONTAINS FIXTURES AT WATTAGES |
| | FOR FIXTURES WHICH NEED TO COORDINATE WITH THE LEGEND. |
| | 13-415.1.B |
| | PLEASE SEE THE PLANS INDICATE TRACK LIGHTING TO BE |
| | INSTALLED IN SOME LOCATIONS: WHERE AND HOW ARE THESE |
| | LOCATED IN THE IDR AND MEET 13-415.2.ABC.1.2 (3)? |
| | |
| | |
| | 5) NOTE: PLEASE SEE THE SITE LIGHTING SHOWN ON E1.2 |
| | CONTAINS A NOTE TO SEE SITE/CIVIL PLANS FOR FIXTURE |
| | TYPE. AS THE SITE PLANS IN THIS ROLL DOES NOT CONTAIN |
| | THIS INFORMATION AND THE CIVIL PLANS ARE NOT IN THESE |
| | SETS SUBMITTED THE SPECIFIC INFORMATION FOR THESE |
| | FIXTURES COULD NOT BE LOCATED. |
| | PLEASE COMPLETE THIS INFORMATION ON THE ELECTRICAL |
| | PLANS SO THAT COORDINATION OF THE FIXTURES CAN BE DONE |
| | WITH THE ENERGY CALCULATIONS, LOAD CALCULATIONS, |
| | VOLTAGES, ETC. PLEASE SEE 13-415.2.ABC.1.3 |
| | FBC 106.1.2, 106.1.1 |
| | |
| | 6) NOTE: PLEASE SEE THE PREVIOUS REVIEW REQUESTED A |
| | WORST CASE VOLTAGE DROP CALCULATION FOR BRANCH CIRCUIT |
| | AND FEEDERS. THIS INFORMATION WAS LOCATED ON A SEPARATE |
| | SHEET LOCATED IN THE SUBMITTAL BOOK. THIS INFORMATION |
| | SHOULD BE ON THE PLANS WHICH ARE PART OF THE SIGNED, |
| | DATED AND SEALED RECORD PLANS. |
| | PLEASE ALSO VERIFY THE SITE LIGHTING VD FOR WORST CASE |
| | AT ROAD WITH THE #10 AS SHOWN FOR LIGHT POLES.) PLEASE |
| | PROVIDE WORST CASE VOLTAGE DROP FOR BRANCH CIRCUITS AND |
| | FEEDERS PER 13-413.1.ABC.1 |
| | |
| | |
| | 7) NOTE: PLEASE SEE THE RISER SHOWS BOTH COPPER AND |
| | ALUMINUM, THE SPECIFIC TYPE PF CONDUCTORS INSTALLED |
| | WILL BE REQUIRED TO BE REVISED ONCE THE INSTALLATION |
| | AND CHOICE HAS BEEN MADE. THIS DOES NOT NEED TO BE |
| | REVISED AT THIS TIME, HOWEVER BEFORE INSPECTION. |
| | |
| | |
| | 8) NOTE: PLEASE CLARIFY WHERE THE LIGHTING IS FOR |
| | OUTSIDE THE STORE ENTRANCES, OVERHEAD SIDEWALK AREA? IS |
| | THERE NOT GOING TO BE ANY LIGHTING OUTSIDE THE LENGTH |
| | OF THE STORE IN FRONT? |
| | FBC 106.3.5.1.2 |
| | |
| | |
| | 9) NOTE: PLEASE SEE THE PREVIOUS NOTE #10. THIS IS THE |
| | SAME COMMENT. THE SINGLE SHEET SUBMITTED DOES NOT MEET |
| | THE INFORMATION NEEDED FOR BOTH AS REQUESTED. THE |
| | PREVIOUS REVIEW ALSO REQUESTED THE MINIMUM RUNNING TIME |
| | BASED ON THE FUEL TO BE SUPPLIED TO BE STATED ON THE |
| | PLANS. THE RESPONSE LETTER MENTIONS NO MINIMUM TIMES |
| | ARE REQUIRED AND THAT EQUIPMENT WILL RUN AS LONG AS IT |
| | TAKES FOR READINGS, TESTING ETC. LETTER ALSO MENTIONS |
| | TO STATE A SPECIFIC CODE SECTION. PLEASE SEE THE |
| | PREVIOUS REVIEW NOTE WHICH GIVES NOT ONLY THE CODE |
| | EDITION, BUT SEVERAL SECTIONS OF THE CODE. |
| | PLEASE STATE THE RUNNING TIME WITH 100 PERCENT LOAD OF |
| | THE FIRE PUMP BASED ON THE ON-SITE FUEL BEING PROVIDED |
| | ON THE PLANS. IF THERE ARE QUESTIONS ON THIS PLEASE |
| | CALL. IF THE FIRE MARSHAL HAS ANY COMMENTS PLEASE BE |
| | SUE TO SEE THEIR REVIEW NOTES |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SUBMIT THE MANUFACTURES SPECS/CUT SHEETS FOR |
| | THE FIRE PUMP/FIRE PUMP CONTROLLER. IT IS KNOW THAT THE |
| | FS WORK WILL BE UNDER A SEPARATE PERMIT HOWEVER THESE |
| | ARE REQUIRED IN BASE BUILDING PLANS AND FOR REVIEW. |
| | PLEASE SUPPLY THE INFORMATION OF FS PLANS FOR THE |
| | MINIMUM TIMES FOR FIRE PUMP RUNNING AT 100%. PLEASE SEE |
| | NFPA-20 11.4.1, 11.4.3, 11.4.5 (ALL). PLEASE SEE OTHER |
| | TRADES FOR REVIEW OF SYSTEMS FOR FIRE PUMP. |
| | 110.3, 90.7, FBC 106.1.2, 106.3.5.1.2 |
| | |
| | |
| | 10) NOTE: PLEASE SEE PREVIOUS NOTE # WITH REGARD TO THE |
| | RISER WHICH INDICATED A *KIRK-KEY* INTERLOCK BREAKER |
| | SCENARIO. THE RESPONSE LETTER MENTIONS THIS WAS REMOVED |
| | HOWEVER NOTE ON THE RISER STILL INDICATES THIS *QC* |
| | BREAKER AND THE PLANS ARE STILL INDICATING PROVISIONS |
| | FOR A PORTABLE GENERATOR. |
| | PLEASE CLARIFY AS RESPONSE MENTIONS THIS WAS BEING |
| | REMOVED??? |
| | |
| | |
| | 11) NOTE:PLEASE SEE PREVIOUS NOTE #12 WHICH REQUESTED |
| | TO COMPLETE THE AVAILABLE FAULT CURRENT ON PLANS AND TO |
| | INDICATE THE RATINGS. PLEASE SEE THE RISER NOW SEEMS TO |
| | HAVE THE AVAILABLE FAULT CURRENT ON THE LINE SIDE OF |
| | THE EQUIPMENT AND SERVICE PANELS, HOWEVER NOT ALL |
| | ACTUAL MINIMUM RATINGS FOR THIS EQUIPMENT SERIES OR |
| | OTHER WISE ARE STATED ON PLANS. PLEASE SEE SOME PANEL |
| | GIVE THEIR RATINGS AND SOME DO NOT. PLEASE COMPLETE THE |
| | INFORMATION FOR MAINS, PANELS, BREAKERS ETC. 110.9. |
| | FBC 106.3.5.1.2, 106.1.2, 106.1.1 |
| | |
| | |
| | 12) NOTE: PREVIOUS NOTE #13. |
| | PLEASE SUBMIT THE MANUFACTURES SPECS/CUT SHEETS FOR |
| | THE PROPOSED UPS. A SHEET WAS SUBMITTED HOWEVER LISTING |
| | FOR USE COULD NOT BE LOCATED/VERIFIED. |
| | IS THERE NO DISCONNECT ON THE LOAD SIDE OF THE UPS OR |
| | LINE SIDE PF THE PANEL LIU? PLEASE CLARIFY AS THE USE |
| | OF CORD AND PLUGS AS SHOWN IN DETAILS MAY ONLY BE USED |
| | FOR SOME INSTANCES. PLEASE SEE 110.3, |
| | |
| | |
| | 13) NOTE: PLEASE SEE PREVIOUS NOTE #17 WITH RESPECT TO |
| | COLOR CODING OF CONDUCTORS. THE RESPONSE LETTER |
| | MENTIONS A *BOXED NOTE* WAS OR WOULD BE ADDED TO RISER |
| | SHEET E-4. THIS NOTE COULD NOT BE LOCATED. |
| | ** PREVIOUS REVIEW NOTE* |
| | PLEASE PROVIDE NOTES FOR COLOR CODING FOR 277/480V |
| | SYSTEMS AS BROWN, PURPLE, YELLOW. |
| | THE NEC DOES NOT GIVE THE COLOR CODING AND *ORANGE* IS |
| | FOR A HIGH-LEG SYSTEM WHICH THIS IS NOT. |
| | FBC 104.6, 90.4. |
| | |
| | |
| | 14) NOTE: PLEASE SEE THE FA SHEETS NEED TO STATE THE |
| | FBC 2004 11-4.28.1, .2 AND .3(4) FOR DEVICES. |
| | THE LEVELS APPEAR TO BE OK AT THIS TIME HOWEVER ONLY |
| | NFPA-72 WAS STATED AND THE FBC HAS MORE STRINGENT |
| | REQUIREMENTS. |
| | THIS WAS PREVIOUS NOTE #19, AND CODE SECTIONS WERE |
| | ADDED HOWEVER THE PLANS NOW STATE THE 2001 FBC WHEN |
| | THIS SHOULD BE THE 2004 FBC. PLEASE ADJUST AS PROJECT |
| | IS UNDER THE 2004. |
| | |
| | |
| | 15) NOTE: PLEASE SEE CODE SECTIONS NOTE DON MSB1 AND |
| | MSB2 ARE FROM THE 2002 NEC> |
| | PLEASE SEE THESE STATE 220.21 AND THIS IS 220.60 UNDER |
| | THE 2005 NEC. |
| | PLEASE REVISE AS PLANS ARE COMING BACK FOR OTHER |
| | CORRECTIONS AND CHANGES. |
| | |
| | |
| | 16) NOTE: PLEASE SEE THAT NOT ALL FIXTURES ON PLANS ARE |
| | ON THE FIXTURE LEGEND. |
| | PLEASE SEE SHEET SWE1 FOR EXAMPLE AS THERE IS A FIXTURE |
| | *10A* YET THIS COULD NOT BE FOUND ON LEGEND? PLEASE |
| | COORDINATE ALL FIXTURES ALSO AS NOTED ABOVE IN OTHER |
| | COMMENTS. FBC 106.1.2 |
| | |
| | |
| | 17) NOTE: PLEASE KNOW THAT ANY SIGNATURE VERIFICATION |
| | LETTERS NEED TO BE ORIGINAL AND NOT PHOTO-COPIES ALONG |
| | WITH NEEDING THE RAISED SEAL WHEN SIGNING AND DATING. |
| | PLEASE SEE ONE LETTER WAS ORIGINAL AND ONE WAS A |
| | PHOTO-COPY. |
| | THESE WILL BE PLACED IN OUR SIGNATURE FILE FOR |
| | REFERENCE. |
| | FBC 106.1.2, 106.5. FS 471.025, FAC 61G15-23.002 |
| | |
| | |
| | |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | ** PLEASE BE SURE TO SEE ANY COMMENTS FROM OTHER TRADES |
| | WHICH MAY AFFECT ELECTRICAL PLANS AND DESIGN CHANGES. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |