| 2007-09-06 16:53:30 | CONSTRUCTION SERVICES DEPARTMENT |
| | 200 SECOND STREET, 3RD FLOOR, WEST PALM BEACH, |
| | FLORIDA33401 |
| | TEL:561-805-6713FAX: |
| | 561-805-6731 |
| | |
| | JAMES JOHNSTON,CBO PERMIT NO. 07050729 |
| | BUILDING PLAN EXAMINERII |
| | PROJECT WAL-MART SUPERCENTER |
| | E-MAIL:JJOHNSTON @WPB.ORG ADDRESS |
| | 422545 STREET |
| | CONTRACTOR: |
| | DATE: SEPTEMBER 6, 2007 |
| | |
| | PLANREVIEW |
| | |
| | |
| | 6) THE MECHANICAL ENGINEER IS MISSING THE FOLLOWING |
| | INFORMATION IN THEIR TITLE BLOCK, |
| | CERTIFICATE OF AUTHORIZATION NUMBER AS PERF.S. |
| | 489.219 |
| | 61G15-23.002 THE PRINTED NAME AND LICENSE NUMBER |
| | AND THE FIRMS CERTIFICATE OF AUTHORIZATION. |
| | |
| | 15) SHEETR-4 & R-5 SIGNATURE AND SEAL NOT LEGIBLE |
| | PLANS, SPECIFICATIONS REPORTS OR OTHER DOCUMENTS |
| | PREPARED BY THE DESIGN PROFESSIONAL AND BEING FILED FOR |
| | PUBLIC RECORD SHALL HAVE |
| | THE SIGNATURE AND SEAL OF THE DESIGN PROFESSIONAL |
| | AFFIXED. |
| | |
| | (17-A) FIRE-RATED CORRIDOR162 |
| | THIS CORRIDOR LEADS INTO THE STOCK ROOM. |
| | ISOLATE THE STOCK ROOM FROM THE CORRIDOR, THEN THE |
| | CORRIDOR WILL HAVE A DIRECT FIRE RATED ACCESS PATH TO |
| | THE EXTERIOR EXITS. |
| | |
| | 19) 11-4.35 DRESSING AND FITTING ROOMS |
| | PROVIDE ARCHITECTURAL PLAN OF DRESSING ROOMS WITH H.C. |
| | ACCESSIBLE DETAILS AS PER THE PREVIOUS REQUEST |
| | |
| | (21) FBCTABLE 414.2.4CONTROLLED AREA |
| | ALLOWS MATERIALS TO EXCEED THE ALLOWABLE QUANTITY |
| | PROVIDED THEY ARE DISPLAYED AND STORED IN A CONTROLLED |
| | AREA.DEFINE QUANTITIES ON HAZARDOUS MATERIAL PLAN |
| | |
| | 23) FLORIDA PRODUCT APPROVALS MUST BE DATED 2004 |
| | PRODUCT APPROVALS SUBMITTED WITH PERMIT APPLICATION |
| | AFTER OCTOBER 1, 2003 ARE REQUIRED TO COMPLY WITH THE |
| | FLORIDA PRODUCT APPROVAL SYSTEM. FOR INFORMATION PLEASE |
| | SEE THE STATE WEBSITE AT WWW.FLORIDABUILDING.ORG. |
| | PRODUCTS WITH STATEWIDE APPROVAL ARE REQUIRED TO BE |
| | SUBMITTED WITH A COVER SHEET THAT LISTS THE PRODUCT |
| | IDENTITY NUMBER FROM THE STATE. IF THE PRODUCT DOES NOT |
| | HAVESTATEWIDE APPROVAL, SUBMIT AN APPLICATION FOR |
| | LOCAL PRODUCT APPROVAL OR SITE SPECIFIC FORM PER RULE |
| | 9B-72.WWW.FLORIDABUILDING.ORG |
| | |
| | PLACE THE FLORIDA PRODUCT APPROVAL WITH THE MIAMI DADE |
| | NOA FOR EACH PRODUCT |
| | |
| | (23-A) MIAMI DADE NOA BY KAWNNER |
| | PRODUCT APPROVAL NO 04-0211.11 HAVE ENGINEER VERIFY |
| | ANCHOR CONNECTIONS TO THE FBC 2004 |
| | OLDER NOAUSES 1.33 INCREASE . NOT ALLOWED UNDER FBC |
| | 2004 |
| | |
| | 24) WPB ADMINISTRATIVE CODEPRODUCT APPROVALS. THOSE |
| | PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | |
| | 25) 1707.4.5.1 MULLIONS |
| | LOCATED BETWEEN WINDOW AND GLASS DOOR ASSEMBLIES ARE |
| | REQUIRED TO BE ENGINEERED BY AN APPROVED TESTING |
| | LABORATORY, THEY ARE NOT PART OF THE WINDOW SYSTEM |
| | |
| | 26) 1707.4.5.2 MULLIONS SHALL BE DESIGNED TO TRANSFER |
| | THE DESIGN PRESSURE LOADS |
| | APPLIED BY THE WINDOW OR DOOR ASSEMBLIES TO THE ROUGH |
| | OPENING SUBSTRATE. |
| | |
| | (32) SHEETSP2.2 DETAIL 15 |
| | IDENTIFY LENGTH OF EACH CONCRETE CAP AND TYPE OF |
| | EXPANDING ADHESIVE WITH ADHESIVE SPECIFICATIONS FOR |
| | UP-LIFT |
| | |
| | (33) A 4.1 DETAIL 2 |
| | SPECIFY WATERPROOFING MEMBRANE AND SUBMIT DATA SHEETS |
| | REVIEWED AND SIGNED BY ARCHITECT FOR ACCEPTANCE. |
| | |
| | (34) S-6.1VESTIBULE ROOF FRAMING PLAN |
| | FURNISH BAR JOIST DESIGN FOR WALL RESTING ON JOIST |
| | GRID 6.5 TO 9. FOUR JOIST REQUESTED. |
| | |
| | (35) A-6.1 WALL TYPES |
| | ON RATED WALLS IDENTIFY THE WALL TO UNDER ROOF |
| | CONNECTION AND THE FLEXIBLE FIRE RATED JOINT |
| | |
| | (36) FLOOR PLAN A-1 |
| | IDENTIFY ALL ROOMS AND AREAS ON FLOOR PLANA-1 |
| | |
| | (37) VESTIBULE ROOF |
| | IDENTIFY THE ROOF TILE AND SYSTEM WITH ALL ATTACHMENTS |
| | FOR UP-LIFT |
| | |
| | (38) IMPACT FEES |
| | MUST BE PAID BEFORE PERMIT ISSUANCE |
| | |
| | |