| 2009-03-18 19:16:21 | DENIED |
| | REFERENCE: |
| | FBC-2004 PLUMBING |
| | FBC-2004 BUILDING |
| | FBC-2004 MECHANICAL |
| | FBC-2004 CHAPTER 1 |
| | |
| | ****FROM PREVIOUS REVISION REVIEW: |
| | |
| | 1. OK |
| | |
| | 2. SHT P1 DETAILS 3 & 4 AS WELL AS THE PLAN VIEW. SINCE |
| | THE PIPING IS ON THE ROOF AND EXPOSED TO THE SUN DURING |
| | THE DAY EXPANSION JOINT FITTINGS MAY BE REQUIRED. |
| | PLEASE INDICATE HOW THIS WILL BE ADDRESSED. SECTION |
| | 308.8. |
| | ****NO RESPONSE, COMMENT NOT ADDRESSED. |
| | |
| | 3. SHT P1 DETAIL 3 SHOWS STAINLESS STEEL ADJUSTABLE |
| | HOSE CLAMPS (BOTH SIDES). PLEASE CLAIRFY. WHAT IS THE |
| | USE FOR THESE CLAMPS. SECTION 106.1.2. |
| | ****NO RESPONSE, COMMENT NOT ADDRESSED. |
| | |
| | 4. OK |
| | |
| | 5. SECTION 314.2.2 CONDENSATE WASTE SHALL NOT DECREASE |
| | IN SIZE FROM THE DRAIN PAN CONNECTION. INDICATE ALL |
| | PIPE SIZES AND DRAIN PAN SIZES ON THE PIPE LAYOUT. |
| | ****NO RESPONSE, COMMENT NOT ADDRESSED. |
| | |
| | 6. OK |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| | ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| | ONE SET OF THEM LOOSELY ON TOP OF THE |
| | COLLATED PLANS TO BE REVIEWED. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | REVIEW BY KEN STEVENS |