Plan Review Notes
Plan Review Notes For Permit 07050729
Permit Number 07050729
Review Stop P
Sequence Number 13
Notes
Date Text
2009-03-18 19:16:21DENIED
 REFERENCE:
 FBC-2004 PLUMBING
 FBC-2004 BUILDING
 FBC-2004 MECHANICAL
 FBC-2004 CHAPTER 1
  
 ****FROM PREVIOUS REVISION REVIEW:
  
 1. OK
  
 2. SHT P1 DETAILS 3 & 4 AS WELL AS THE PLAN VIEW. SINCE
 THE PIPING IS ON THE ROOF AND EXPOSED TO THE SUN DURING
 THE DAY EXPANSION JOINT FITTINGS MAY BE REQUIRED.
 PLEASE INDICATE HOW THIS WILL BE ADDRESSED. SECTION
 308.8.
 ****NO RESPONSE, COMMENT NOT ADDRESSED.
  
 3. SHT P1 DETAIL 3 SHOWS STAINLESS STEEL ADJUSTABLE
 HOSE CLAMPS (BOTH SIDES). PLEASE CLAIRFY. WHAT IS THE
 USE FOR THESE CLAMPS. SECTION 106.1.2.
 ****NO RESPONSE, COMMENT NOT ADDRESSED.
  
 4. OK
  
 5. SECTION 314.2.2 CONDENSATE WASTE SHALL NOT DECREASE
 IN SIZE FROM THE DRAIN PAN CONNECTION. INDICATE ALL
 PIPE SIZES AND DRAIN PAN SIZES ON THE PIPE LAYOUT.
 ****NO RESPONSE, COMMENT NOT ADDRESSED.
  
 6. OK
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  