| Date |
Text |
| 2009-03-04 11:24:43 | DENIED |
| | REFERENCE: |
| | FBC-2004 PLUMBING |
| | FBC-2004 BUILDING |
| | FBC-2004 MECHANICAL |
| | FBC-2004 CHAPTER 1 |
| | |
| | 1. SHT P1 DETAILS 3 & 4 AS WELL AS THE PLAN VIEW. |
| | DETAIL 3 PLEASE INDICATE HOW THE BLOCKING WILL BE |
| | ATTACHED TO THE ROOF. SECTION M301.13. MECHANICAL |
| | EQUIPMENT, APPLIANCES AND SUPPORTS THAT ARE EXPOSED TO |
| | WIND SHALL BE DESIGNED AND INSTALLED TO RESIST THE WIND |
| | PRESSURES ON THE EQUIPMENT AND THE SUPPORTS AS |
| | DETERMINED IN ACCORDANCE WITH THE FLORIDA BUILDING CODE |
| | BUILDING. THIS SHOULD BE REVIEWED BY THE STRUCTURAL |
| | ENGINEER. SECTIONS P308.3 & P308.4. |
| | |
| | 2. SHT P1 DETAILS 3 & 4 AS WELL AS THE PLAN VIEW. SINCE |
| | THE PIPING IS ON THE ROOF AND EXPOSED TO THE SUN DURING |
| | THE DAY EXPANSION JOINT FITTINGS MAY BE REQUIRED. |
| | PLEASE INDICATE HOW THIS WILL BE ADDRESSED. SECTION |
| | 308.8. |
| | |
| | 3. SHT P1 DETAIL 3 SHOWS STAINLESS STEEL ADJUSTABLE |
| | HOSE CLAMPS (BOTH SIDES). PLEASE CLAIRFY. WHAT IS THE |
| | USE FOR THESE CLAMPS. SECTION 106.1.2. |
| | |
| | 4. SHT P1 INDICATE THE MATERIAL FOR THE CONDENSATE |
| | LINES. SECTION 106.1.2. |
| | |
| | 5. SECTION 314.2.2 CONDENSATE WASTE SHALL NOT DECREASE |
| | IN SIZE FROM THE DRAIN PAN CONNECTION. INDICATE ALL |
| | PIPE SIZES AND DRAIN PAN SIZES ON THE PIPE LAYOUT. |
| | |
| | 6. ALL HORIZONTAL SECTIONS OF DRAIN PIPING SHALL BE |
| | INSTALLED IN UNIFORM ALIGNMENT AND AT A UNIFORM SLOPE. |
| | SECTION 314.2.2. PLEASE INDICATE HOW THE SLOPE WILL BE |
| | ACHIEVED. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| | ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| | ONE SET OF THEM LOOSELY ON TOP OF THE |
| | COLLATED PLANS TO BE REVIEWED. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |