Plan Review Notes
Plan Review Notes For Permit 07050729
Permit Number 07050729
Review Stop P
Sequence Number 1
Notes
Date Text
2007-07-05 18:57:39DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 BUILDING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 WEST PALM BEACH MUNICIPAL CODE
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. ALL SHEETS WITH B/R/R ARCHITECTURE SHALL HAVE THE
 FIRM LICENSE NUMBER, (CERTIFICATE OF AUTHORIZTION), IN
 THE TITLE BLOCK OF EACH SHEET AS WELL AS THE PRINTED
 NAME OF THE PERSON SEALING THE DOCUMENT. FAC
 61G1-16.004(2)(6) & FS 481.219, 481.2055. THE NUMBER
 SHOWN DOES NOT REFLECT THE NUMBER ON THE FLORIDA STATE
 DBPR WEBSITE. (SEE ATTACHED SHEET).
  
 2. SHT SP2.1 DETAILS 12 & 14 INDICATE DRAINAGE WORK BY
 BUILDING CONTRACTOR. THIS IS NOT IN THE SCOPE OF THE
 BUILDING CONTRACTOR, AND THE WORK SHALL BE BY THE
 PLUMBING CONTRACTOR. FS 489. PLEASE CHANGE REFERENCE IN
 DETAILS.
  
 3. SHT P2 DETAILS 5 & 6 SHOW THE SLOPE TO THE DRAIN.
 DETAIL 7B SHOWS NO DRAIN. PLEASE CLARIFY. SECTION
 106.1.1
  
 4. SHT A4 SUBMIT CALCULATIONS FOR PRIMARY & SECONDARY
 ROOF DRAINS. SHOW THE SQUARE FOOTAGE AREA FOR EACH
 DRAIN AS WELL AS 1/2 AREA OF ALL VERTICAL WALLS
 INCLUDING PARAPETS AND ANY AREA FROM ROOFS THAT DRAIN
 ONTO THE ROOF FROM ABOVE. SECTIONS 1106 & 1107 WITH ALL
 SUBSECTIONS AND TABLES.
  
 5. SHT A5.2 DETAIL 1 PHOTO LAB PLAN. SUBMIT THE MANUF
 SPECIFICATION SHEET FOR THE EYE WASH. SECTION 106.1.2.
 LISTING/APPROVAL REQUIRED PER SECTION 303.
  
 6. A NEUTRALIZER TANK MAY BE REQUIRED FOR THE PHOTO
 LAB. PLEASE CONTACT THE UTILITY DEPT. ENVIRONMENTAL
 COMPLIANCE DIVISION. CONTACT RODNEY COMPO, (561)
 822-2272, E-MAIL [email protected], OR CALVIN WILLIAMS
 (561) 822-2284, E-MAIL [email protected], OR FAX THEM
 (561) 822-2297. CITY CODE ARTICLE III SECTION 90-125.
  
 7. SHT A5.6 DETAILS 1, 3, 5 & 10 ARE SHOWING THE W/C
 1'7" OFF THE WALL TO THE CENTERLINE OF THE FIXTURE. THE
 CORRECT MEASUREMENT IS 1'6" AS SHOWN IN FIGURE 11-28.
 PLEASE CORRECT THE DETAIL WITH THE CORRECT CENTERLINE
 MEASUREMENT.
  
 8. SHT A5.6 DETAILS 1, 3 & 8 SHOW THE CLEAR FLOOR SPACE
 FOR THE LAVS IN THE ACCESSIBLE STALLS PER SECTION
 11-4.19.3.
  
 9. SHT A5.6 DETAIL 7. SHOW COMPLIANCE WITH THE
 FOLLOWING:
 A. 11-4.19.2 CLEARANCE
 B. 11-4.19.4 EXPOSED PIPES & SURFACES
 C. 11-4.19.5 FAUCETS
  
 10. SHT A-9 DETAIL 13. SHOW COMPLIANCE WITH THE
 FOLLOWING:
 A. 11-4.24.4 SINK DEPTH
 B. 11-4.24.5 CLEAR FLOOR SPACE
 C. 11-4.24.6 EXPOSED PIPES & SURFACES
 D. 11-4.24.7 FAUCETS.
  
 11. SHT PH-1 THE WATER CLOSET SHALL BE 1'6" OFF THE
 WALL TO THE CENTERLINE OF THE FIXTURE. FIGURE 28. IT IS
 SHOWN AS 1'6-1/2". PLEASE CORRECT THE MEASUREMENT TO
 THE CENTERLINE OF THE FIXTURE OFF THE WALL.
  
 12. SHT GA2 PRODUCE EQUIPMENT LEGEND. SUBMIT MANUF.
 SPECIFICATION SHEETS FOR P07 PRODUCE MISTING SYSTEM.
 INDICATE HOW IT CONNECTS TO POTABLE WATER SOURCE &
 INDICATE BACKFLOW PREVENTION MENTHOD REQUIRED IN
 SECTION 608.
  
 13. SHT GA2 MISC. GROCERY EQUIPMENT LEGEND. ITEMS #MG07
 & MG08 ARE NOT SHOWN ON THE FLOOR PLAN. PLEASE CLARIFY
 AND CORRELATE THE INFORMATION ON THE FLOOR PLAN AND THE
 EQUIPMENT LEGEND.
  
 14. SHT GA2 SERVICE DELI EQUIPMENT LEGEND #D28. MORE
 INFORMATION IS REQUIRED. WHAT TYPE OF FILTER IS IT AND
 WHAT DOES IT FILTER? PLEASE CLARIFY. IF THIS IS A WATER
 FILTER, THEN IT SHALL MEET THE REQUIREMENTS OF SECTION
 608. PLEASE SUBMIT MANUF. SPECIFICATIONS FOR THE
 FILTER. SECTION 106.1.2.
  
 15. SHT GA2 BAKERY EQUIPMENT LEGEND ITEM #B28. PLEASE
 INDICATE IF THERE IS PIPING FROM THE COMPRESSOR. PLEASE
 SUBMIT MANUF. SPECIFICATION SHEETS. SECTION 106.1.2.
  
 16. SWA SHEETS. ENGINEERS SHALL LEGIBLY INDICATE THEIR
 NAME, ADDRESS, AND LICENSE NUMBER ON EACH SHEET. IF
 PRACTICING THROUGH A DULY AUTHORIZED ENGINEERING
 BUSINESS. ENGINEERS SHALL LEGIBLY INDICATE THEIR NAME,
 AND LICENSE NUMBER, AS WELL AS, THE NAME, ADDRESS AND
 CERTIFICATE OF AUTHORIZATION NUMBER OF THE ENGINEERING
 BUSINESS ON EACH SHEET. FAC 61G15-23.002(2) & FS
 471.025.
  
 17. SWA1 PLANS SHALL BE ROUTED TO THE STATE OF FLORIDA,
 DEPT OF BUSINESS REGULATION, DIVISION OF BUSINESSAND
 RESTAURANT FOR REVIEW. A MINIMUM OF 3 SETS OF PLANS
 SHALL BE REVIEWED AND STAMPED BY DBR AND THE TWO PAGE
 "WORKSHEETS" SHALL BE ATTACHED TO THE STAMPED SHEETS
 PRIOR TO RESUBMITTING TO THE CITY FOR REVIEW. SECTION
 102.2.1.
  
 18. SHTS SWA 1 &2 GENERAL NOTES #2 THE WATER FILTER
 SHALL MEET THE REQUIREMENTS OF NSF 42. SUBMIT MANUF.
 SPECIFICATIONS SHOWING COMPLIANCE. SECTION 611.1
  
 19. SHT SWMP1 FLOOR DRAIN 3 & FLOOR DRAIN 8. FLOOR
 DRAINS ARE NOT APPROVED INDIRECT WASTE RECEPTORS. FLOOR
 SINKS AND HUB DRAINS ARE APPROVED PER SECTIONS 802.3 &
 802.3.2.
  
 20. SHT P-1 FD1 NEXT TO COL. LINE C/12. PLEASE INDICATE
 IF THE FLOOR DRAIN WILL BE USED TO DRAIN THE AQUARIUM.
 FLOOR DRAINS ARE NOT APPROVED INDIRECT WASTE RECEPTORS.
 A FLOOR SINK OR A HUB DRAIN IS REQUIRED PER SECTIONS
 802.3 & 802.3.2.
  
 21. SHT P1 INDICATE THE USE OF THE SAMPLING PORT ON THE
 SANITARY BULILING DRAIN AS IT EXITS THE BUILDING.
 SECTION 106.1.2. SUBMIT A DETAIL. SECTION 106.1.1.
  
 22. SHT P1 CONDENSATE CONNECTION BETWEEN COLS. 10 & 11
 IS NOT SHOWN TO DIRECT WASTE WITH THE FLOW AS REQUIRED
 IN SECTION 706.3. PLEASE CORRECT AND SHOW COMPLIANCE
 WITH CODE SECTION.
  
 23. SHT P1 SHOW THE FOUNDATION PIPING INDICATED ON
 DETAIL 14 SHEET P3. SECTION 106.1.1.
  
 24. SHT P2 VESTIBULE PLUMBING PLAN BY COL LINE 9 SHOWS
 4" SANITARY U/G CLEANOUT & 3" RISER WITH 3" SLOPED PIPE
 IN THE WALL TURNING INTO A VENT. WHAT IS THIS DRAINAGE
 - VENT PIPING FOR? WHAT WILL DRAIN INTO THIS 3" LINE?
 PLEASE CLARIFY. SECTION 106.1.2.(THIS ALSO IS SHOWN
 TWICE AT THE FUTURE BANK).
  
 25. SHT P2 WASH MACHINE BRANCH LINE CONNECTION TO THE
 BUILDING DRAIN SHALL BE INSTALLED TO GUIDE THE WASTE IN
 THE DIRECTION OF FLOW. SECTION 706.3. --THE
 BRANCH LINE SHALL BE 3" MINIMUM PER SECTION 406.3 AND A
 CLEANOUT IS REQUIRED ON THE STACK MINIMUM 4' ABOVE THE
 FLOOR PER SECTION 708.9. PLEASE SHOW COMPLIANCE ON BOTH
 THE FLOOR PLAN AND THE DWV RISER DIAGRAM.
  
 26. SHT P2 FLOOR PLAN & DWV RISER DIAGRAM SHOWS FLOOR
 DRAIN AT WATER HEATERS & ICE MAKER. FLOOR DRAINS ARE
 NOT APPROVED FOR INDIRECT WASTE. SECTIONS 802.3 &
 802.3.2. FLOOR SINKS OR HUB DRAINS ARE REQUIRED.
  
 27.SHT P2 DWV RISER DIAGRAM DOES NOT REFLECT THE
 FLOOR PLAN. THERE IS NO L8 FIXTURE SHOWN IN THE WOMENS
 TOILET ROOM ON THE FLOOR PLAN.--THE BRANCH LINE
 RUNS TO THE CENTER OF THE MIDDLE LAV & NO 4TH LAV SHOWN
 ON THE FLOOR PLAN, BUT SHOWS IT RUNNING TO A L8 &
 CONNECTING TO 3 L6 LAVS ON THE RISER. PLEASE CORRELATE
 FLOOR PLAN & RISER DIAGRAM. SECTION 106.1.1.
  
 28. SHT P2 DWV RISER. EACH LAV REQUIRES A TRAP PER
 SECTION 1002.1. THIS IS FOR BOTH MENS & WOMENS TOILET
 ROOMS. PLEASE SHOW TRAPS FOR EACH FIXTURE.
  
 29. SHT P2 THE VESTIBULE WATER RISER DIAGRAM. SHUT OFF
 VALVES ARE REQUIRED ON THE WATER SUPPLY TO EACH HOSE
 BIBB IN THE TOILET ROOMS. SECTION 606.2(2).
  
 30. SHT P2 DETAIL 3 VESTIBULEDOES NOT REFLECT THE
 FLOOR PLAN. TENANT WATER SUPPLY (15.102) IS NOT SHOWN
 ON THE RISER.--SHUT OFF VALVES ARE REQUIRED ON THE
 SUPPLY LINES TO EACH HOSE BIBB. SECTION 606.2(2).
 CORRELATE INFORMATION ON THE FLOOR PLAN AND THE RISER
 DIAGRAM. SECTION 106.1.1.
  
 31. SHT P3 REAR OFFICE DWV RISER. SEPARATE TRAPS
 REQUIRED TO EACH LAV FIXTURE. SECTION 1002.1. PLEASE
 SHOW TRAPS TO EACH FIXTURE.
  
 32. SHT P3 DETAIL 4 REAR OFFICE DWV RISER DOES NOT
 REFLECT THE FLOOR PLAN. ONLY 1 DRINKING FOUNTAIN IS
 SHOWN.--MEN & WOMEN ACCESSIBLE LAVS ARE MISSING IN
 THE STALLS. FIG 30E.
  
 33. SHT P3 DETAIL 3 PHOTO LAV PLUMBING RISERS. FLOOR
 DRAIN IS NOT AN APPROVED INDIRECT WASTE RECEPTOR.
 SECTIONS 802.3 & 802.3.2.--SHUT OFF VALVES ARE
 REQUIRED ON THE SUPPLY LINES TO EACH HOSE BIBB. SECTION
 606.2(2).
  
 34. SHT P3 THE GREASE INTERCEPTOR SHALL BE SIZED BY THE
 UTILITY DEPT. ENVIRONMENTAL COMPLIANCE DIVISION.
 CONTACT RODNEY COMPO, (561) 822-2272, E-MAIL
 [email protected], OR CALVIN WILLIAMS (561) 822-2284,
 E-MAIL [email protected], OR FAX THEM (561) 822-2297.
 CITY CODE ARTICLE III SECTION 90-125.
  
 35. SHT P3 SUBMIT MANUF. SPECIFICATIONS ON THE SUMP
 PUMP& THE PUMP FOR THE LIFT STATION. PUMPS SHALL BE
 LISTED. SECTION 303.4. (DETAILS 13 & 14).
  
 36. SHT P3 DETAIL 5 & SHT GP2 WATER DETAIL (1)
 DIELECTRIC UNIONS ARE NOT APPROVED FOR WATER SYSTEMS.
 DIELECTRIC COUPLINGS CAN BE USED. PLEASE CHANGE DETAIL
 REFERENCE.
  
 37. SHT MP1 PLEASE CLARIFY WHAT DRAINS INTO FS1 SHOWN
 ON FLOOR PLAN. SECTION 106.1.2.
  
 38. SHT GP1 FLOOR DRAINS ARE NOT AN APPROVED INDIRECT
 WASTE RECEPTOR. SECTIONS 802.3 & 802.3.2.
  
 39. SHTS GP1 & GP2 THE SIZE OF THE DRAINAGE PIPING
 SHALL NOT BE REDUCED IN SIZE IN THE DIRECTION OF FLOW.
 SECTION 704.2. SEE SS LINE AS IT SHOWS 6" BY THE
 PRODUCE PREP, THEN 4" UPSTREAM PRIOR TO BREAK TO SHT
 GP2 & 4" ON GP2, THEN BACK TO 6" BEFORE THE OFFSET
 UPSTREAM.--THE GREASE LINE ON GP1 SHWS 6" AT THE
 OFFSET UPSTREAM OF THE PRODUCE PREP, BUT 4" UPSTREAM &
 DOWNSTREAM OF THE OFFSET. PLEASE CLARIFY.
  
 40. SHOWS 3" VENTS BELOW THE SLAB. THIS IS NOT APPROVED
 PER SECTION 905.4. DRY VENTS SHALL NOT BE OFFSET UNTILL
 THEY ARE 6" ABOVE THE FLOOD RIM LEVEL OF THE HIGHEST
 FIXTURE.
  
 41. SHTS GP1 & GP2 PLEASE INDICATE IN THE PLUMBING
 SYMBOLS WHAT THE ABBREVIATIONS CMV & VBF STAND FOR.
 SECTION 106.1.1.
  
 42. SHT GP2 A TWO-WAY CLEANOUT IS REQUIRED AT THE
 ENTRANCE TO THE FIRST GREASE INTERCEPTOR. UTILITY
 STANDARD FOR GREASE INTERCEPTORS.
  
 43. SHT GP2 THE FD-10 JUST OUTSIDE THE MEAT COOLER
 SHALL DISCHARGE INTO THE GREASE SYSTEM, NOT THE
 SANITARY SYSTEM.
  
 44. SHT GP2 DETAIL 4 THE BACKWATER VALVE IS NOT
 APPROVED PER SECTION 715.1. DELETE FROM DETAIL AND
 FLOOR PLAN.
  
 45. SHT GP2 DETAIL 4 THE AIR BREAK IS NOT APPROVED. A
 MINIMUM 8" AIR GAP IS REQUIRED PER SECTIONS 802.1.2 &
 802.2.1. PLEASE CORRECT THE DETAIL AND SHOW REQUIRED
 AIR GAP.
  
 46. SHT GP2 DETAIL 4 SUBMIT THE MANUF SPECIFICATION
 SHEETS FOR FS3 AS SHOWN. SPECS SHALL SHOW
 LISTING/APPROVAL. SECTION 303.
  
 47. SHT GP2 DETAIL 3 DRAIN IS NOT APPROVED. DELETE
 DRAIN FROM COMPACTOR DETAIL. THIS IS NOT APPROVED
 BECAUSE WE HAVE NO WAYTO REGULATE WHETHER OR NOT THE
 WATERTIGHT SEAL WILL BE IN PLACE DURING A RAIN STORM.
 STORM WATER IS NOT ALLOWED IN THE SANITARY SEWER PER
 MUNICIPAL CODE. ARTICLE III SECTION 90-125(5).
  
 48. SHT GP3 ROOF STORM RISER DIAGRAMS. INDICATE THE
 ROOF DRAIN SIZE FOR RISER AT COLUMN 8.5 - 9.5/B - K.
 SECTION 106.1.1 & TABLE 1106.3.
  
 49. SHT GP3 DETAIL 1 GROCERY DWV RISER DIAGRAM, FLOOR
 DRAINS ARE NOT APPROVED FOR INDIRECT WASTE RECEPTORS.
 SECTION 802.3 & 802.3.2--2 WAY CLEANOUT REQUIRED ON
 THE ENTRANCE TO 1ST GREASE INTERCEPTOR.--DELETE
 FLOOR DRAIN AT COMPACTOR.--BACKWATER VALVE NOT
 APPROVED AT THE DRAIN FROM THE DAIRY COOLER. SECTION
 715.1.--AN AIR GAP IS REQUIRED FOR THE DRAIN FROM
 THE DAIRY COOLER. SECTION 802.1.2.--FLOOR DRAIN 10
 AT THE ENTRANCE TO THE MEAT COOLER TO CONNECT TO THE
 GREASE SYSTEM, NOT THE SANITARY SYSTEM.--ALL
 HORIZONTAL DRY VENTS SHALL COMPLY WITH SECTION 905.4.
 (NO OFFSETS GREATER THAN 45 DEGREES UNTIL A MINIIMUM 6"
 ABOVE THE FLOOD RIM LEVEL OF THE HIGHEST FIXTURE.
  
 50. SHTS GP3 & GP4 SHOWS HOT WATER TO THE HOSE BIBBS.
 PLEASE CLARIFY. SECTION 106.1.2.
  
 51. SHT GP4 FIXTUREP07 SHOWS A SUPPLY PIPE LEAVING
 THE FIXTURE, BUT DOES NOT INDICATE WHERE THE PIPING IS
 GOING. PLEASE CLARIFY. SECTION 106.1.1.
  
 52. SHT GP4 DETAIL 2 VACUUM RELIEF VALVES ARE REQUIRED
 FOR ALL BOTTOM FED WATER HEATERS. SECTION 504.2. SHOW
 ON DETAIL.
  
 53. SHT GP4 GROCERY PLUMBING EQUIPMENT CONNECTION
 SCHEDULE. FIXTURES B36 & MG 21 CAN NOT BE FOUND. PLEASE
 CLARIFY AND CORRELATE THE SCHEDULE AND FLOOR PLAN.
 SECTION 106.1.1.
  
 54. SUBMIT MANUF SPECIFICATION SHEETS FOR THE REVERSE
 OSMOSIS FILTER. THE FILTER SHALL MEET THE REQUIREMENTS
 OF NSF 58. SECTION 611.2.
  
 55. SHT C1 PLUMBING FIXTURE COUNTS INDICATES 5 DRINKING
 FOUNTAINS AND ONE WATER COOLER. ONLY 3 DRINKING
 FOUNTAINS HAVE BEEN LOCATED. IF A HI-LOW DRINKING
 FOUNTAIN HAS ONLY ONE TRAP AND ONE WATER SUPPLY IT IS
 CONSIDERED ONE DRINKING FOUNTAIN, NOT TWO AS EACH
 FIXTURE IS REQUIRED TO HAVE ITS OWN TRAP AND WATER
 SUPPLY. PLEASE INDICATE THE LOCATION OF THE REQUIRED
 DRINKING FOUNTAINS AND THE REQUIRED WATER COOLER. TABLE
 403.1.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID
 SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY
 ON TOP OF THE COLLATED PLANS TO BE REVIEWED. ALSO TO
 HELP EXPEDITE YOUR PERMIT, SUBMIT MARKED UP SET OF
 PLUMBING SHEETS. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]