| 2007-07-12 09:47:00 | *****DENIED***** |
| | |
| | |
| | 01.THE NUMERICAL ADDRESS SHALL BE IN THE TITLE BLOCK |
| | OF EACH SUBMITTED PLAN SHEET. |
| | |
| | 02.NFPA 101, LIFE SAFETY CODE, 2003 EDITION SHALL BE |
| | REFERENCED. |
| | |
| | 03. ON THE APPROPIATE EXTERIOR ELEVATION, POST THE |
| | NUMERICAL ADDRESS ON THE BUILDING VISIBLE FORM 45TH |
| | STREET.AS PER WEST PALM BEACH CODE, THOSE NUMBERS |
| | SHALL BE NO LESS THAN 6" IN HEIGHT AND NO LESS THAN1" |
| | IN WIDTH.IN ADDITION,THE NUMERICAL ADDRESS SHALL BE |
| | ON THE MONUMENT SIGN. |
| | |
| | 04.THE STORAGE OF TIRES (CHAPTER 8) AND BATTERIES |
| | SHALL COMPLY WITH NFPA 230 - 2003 EDITION. |
| | |
| | 05.COMMERCIAL COOKING EQUIPMENT SHALL BE IN |
| | ACCORDANCE WITH NFPA 96 - 2001 EDITION.SEPARATE PLANS |
| | AND PERMIT WILL BE REQUIRED FOR BOTH THE COOKING HOOD'S |
| | INSTALLATION AND THE HOOD'S SUPPRESSION SYSTEM. |
| | |
| | 06.ON SHEET SWE1, IT APPEARS THAT THERE ARE TWO |
| | EGRESS DOORS BUT ONLY ONE IS MARKED AS AN EXIT.PLEASE |
| | EXPLAIN. |
| | |
| | 07.ON SHEET FP-1,VERIFY THE WATER SUPPLY |
| | INFORMATION DERIVED FROM A WATER REPORT SUPPLIED DURING |
| | A WATER FLOW TEST CONDUCTED ON JULY 13TH, 2007.PLEASE |
| | BE ADVISED THAT THE DATE OF THIS WRITING IS JULY 12TH, |
| | 2007. |
| | |
| | 08.SEPARATE PLANS AND PERMIT WILL BE REQUIRED FOR THE |
| | FIRE SPRINKLER SYSTEM. |
| | |
| | 09.SEPARATE PLANS AND PERMIT WILL BE REQUIRED FOR THE |
| | FIRE ALARM SYSTEM. |
| | |
| | 10. THE FIRE ALARM SYSTEM SHALL BE MONITORED BY A UL |
| | CERTIFICATED CENTRAL STATION SERVICE. |
| | |
| | 11.ON SHEET EFP-1, AMEND NOTE 8 TO REFLECT THAT DUCT |
| | SMOKE DETECTORS SHALL INITIATE A GENERAL FIRE ALARM AS |
| | PER WEST PALM BEACH FIRE PREVENTION. |
| | |
| | 12.ON SHEET EFP-2, AMEND NOTE 8 AND THE SEQUENCE OF |
| | OPERATION TO REFLECT THAT DUCT SMOKE DETECTORS SHALL |
| | INITIATE A GENERAL FIRE ALARM. |
| | |
| | 13.KNOX-BOX SHALL BE REQUIRED SO THAT FIRE RESCUE CAN |
| | GAIN ACCESS TO THE BUILDING.DISPLAY LOCATION OF THIS |
| | KNOX-BOX.FOR APPLICATIONS, CONTACT 561-804-4724. |
| | |
| | 14.KNOX LOCKING CAP DEVICES SHALL BE REQUIRED FOR THE |
| | FIRE DEPARTMENT CONNECTION.FOR APPLICATIONS, CONTACT |
| | 561-804-4724. |
| | |
| | 15.IN ADDITION TO ELECTRONIC SWITCHES, CHAIN AND LOCK |
| | WILL BE REQUIRED ON THE FIRE LINE BACK FLOW DEVICE. |
| | |
| | 16.PLEASE INDICATE THE WALL AND CEILING FINISH |
| | MATERIALS IN TERMS OF CLASS A OR CLASS B. |
| | |
| | 17.REQUIRED EXIT AISLE SHALL NOT BE LESS THAN 36" IN |
| | CLEAR WIDTH.IN CLASS A MERCANTILES, NOT LESS THAN ONE |
| | AISLE OF 60" MINIMUM WIDTH SHALL LEAD DIRECTLY TO AN |
| | EXIT. |
| | |
| | 18.CHECKOUT STANDS OR ASSOCIATED RAILINGS OR BARRIERS |
| | SHALL NOT OBSTRUCT EXITS, REQUIRED AISLES, OR |
| | APPROACHES THERETO. |
| | |
| | |
| | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE |
| | LETTER INDICATING WHERE ON THE PLANS EACH ITEM WAS |
| | ADDRESSED |
| | |
| | |