Plan Review Notes
Plan Review Notes For Permit 07050729
Permit Number 07050729
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2007-07-12 09:47:00*****DENIED*****
  
  
 01.THE NUMERICAL ADDRESS SHALL BE IN THE TITLE BLOCK
 OF EACH SUBMITTED PLAN SHEET.
  
 02.NFPA 101, LIFE SAFETY CODE, 2003 EDITION SHALL BE
 REFERENCED.
  
 03. ON THE APPROPIATE EXTERIOR ELEVATION, POST THE
 NUMERICAL ADDRESS ON THE BUILDING VISIBLE FORM 45TH
 STREET.AS PER WEST PALM BEACH CODE, THOSE NUMBERS
 SHALL BE NO LESS THAN 6" IN HEIGHT AND NO LESS THAN1"
 IN WIDTH.IN ADDITION,THE NUMERICAL ADDRESS SHALL BE
 ON THE MONUMENT SIGN.
  
 04.THE STORAGE OF TIRES (CHAPTER 8) AND BATTERIES
 SHALL COMPLY WITH NFPA 230 - 2003 EDITION.
  
 05.COMMERCIAL COOKING EQUIPMENT SHALL BE IN
 ACCORDANCE WITH NFPA 96 - 2001 EDITION.SEPARATE PLANS
 AND PERMIT WILL BE REQUIRED FOR BOTH THE COOKING HOOD'S
 INSTALLATION AND THE HOOD'S SUPPRESSION SYSTEM.
  
 06.ON SHEET SWE1, IT APPEARS THAT THERE ARE TWO
 EGRESS DOORS BUT ONLY ONE IS MARKED AS AN EXIT.PLEASE
 EXPLAIN.
  
 07.ON SHEET FP-1,VERIFY THE WATER SUPPLY
 INFORMATION DERIVED FROM A WATER REPORT SUPPLIED DURING
 A WATER FLOW TEST CONDUCTED ON JULY 13TH, 2007.PLEASE
 BE ADVISED THAT THE DATE OF THIS WRITING IS JULY 12TH,
 2007.
  
 08.SEPARATE PLANS AND PERMIT WILL BE REQUIRED FOR THE
 FIRE SPRINKLER SYSTEM.
  
 09.SEPARATE PLANS AND PERMIT WILL BE REQUIRED FOR THE
 FIRE ALARM SYSTEM.
  
 10. THE FIRE ALARM SYSTEM SHALL BE MONITORED BY A UL
 CERTIFICATED CENTRAL STATION SERVICE.
  
 11.ON SHEET EFP-1, AMEND NOTE 8 TO REFLECT THAT DUCT
 SMOKE DETECTORS SHALL INITIATE A GENERAL FIRE ALARM AS
 PER WEST PALM BEACH FIRE PREVENTION.
  
 12.ON SHEET EFP-2, AMEND NOTE 8 AND THE SEQUENCE OF
 OPERATION TO REFLECT THAT DUCT SMOKE DETECTORS SHALL
 INITIATE A GENERAL FIRE ALARM.
  
 13.KNOX-BOX SHALL BE REQUIRED SO THAT FIRE RESCUE CAN
 GAIN ACCESS TO THE BUILDING.DISPLAY LOCATION OF THIS
 KNOX-BOX.FOR APPLICATIONS, CONTACT 561-804-4724.
  
 14.KNOX LOCKING CAP DEVICES SHALL BE REQUIRED FOR THE
 FIRE DEPARTMENT CONNECTION.FOR APPLICATIONS, CONTACT
 561-804-4724.
  
 15.IN ADDITION TO ELECTRONIC SWITCHES, CHAIN AND LOCK
 WILL BE REQUIRED ON THE FIRE LINE BACK FLOW DEVICE.
  
 16.PLEASE INDICATE THE WALL AND CEILING FINISH
 MATERIALS IN TERMS OF CLASS A OR CLASS B.
  
 17.REQUIRED EXIT AISLE SHALL NOT BE LESS THAN 36" IN
 CLEAR WIDTH.IN CLASS A MERCANTILES, NOT LESS THAN ONE
 AISLE OF 60" MINIMUM WIDTH SHALL LEAD DIRECTLY TO AN
 EXIT.
  
 18.CHECKOUT STANDS OR ASSOCIATED RAILINGS OR BARRIERS
 SHALL NOT OBSTRUCT EXITS, REQUIRED AISLES, OR
 APPROACHES THERETO.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE ON THE PLANS EACH ITEM WAS
 ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722