| 2007-06-24 15:23:34 | |
| | |
| | *** UNSAT *** |
| | |
| | WAL-MART |
| | SUPERCENTER. |
| | |
| | 1A) NOTE: PLEASE KNOW ONCE THE ADDRESS HAS BEEN |
| | CONFIRMED THE ADDRESS FOR THE LOCATION OF THIS PROJECT |
| | SHALL BE SHOWN IN TITLE BLOCKS. |
| | FAC 61G1-16.004, 61G15-23.002 |
| | |
| | 1B) NOTE: PLEASE SEE PLANS WERE ONLY SUBMITTED FOR |
| | *PLAN REVIEW* AND HAVE NOT BEEN SUBMITTED OR PERMIT. |
| | PLEASE KNOW EVEN ONCE ALL COMMENTS FOR CODE COMPLIANCE |
| | ARE MET AND PERMIT APPLICATION HAS NOT BEEN MADE THE |
| | REVIEW(S) WILL STILL GO INTO A FAILED STATUES. PLEASE |
| | KNOW THERE ARE SEVERAL ITEMS WHICH ARE TO BE VERIFIED |
| | ONCE APPLICATION HAS BEEN MADE. PLEASE KNOW IF THERE |
| | ARE ANY CODE CHANGES ADOPTED BY THE STATE BEFORE PERMIT |
| | APPLICATION IS MADE WILL REQUIRED DESIGNS UNDER NEW |
| | CODES. |
| | ALL LICENSING WILL BE REVIEWED BEFORE ISSUANCE. |
| | |
| | 2) NOTE:PLEASE KNOW THAT ANY PERMIT APPLICATIONS |
| | WHICH ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES |
| | PROJECTS UNDER THE NEW CODES ADOPTED BY THE STATE. |
| | PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO |
| | THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70. |
| | PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY |
| | AFFECT DESIGNS FOR ALL TRADES.SOME OF THESE ARE |
| | STATED ON PLANS HOWEVER NOT ALL AND NOT ALL CURRENT PER |
| | STATE ADOPTED CODES. |
| | PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETSAND |
| | ARCHITECTURAL COVER SHEET FOR THIS REVIEWER AT A |
| | MINIMUM. |
| | 2004 FBC W/ 2006 REVISIONS |
| | 2005 NFPA-70 |
| | 2002 NFPA-72 |
| | 2003 NFPA-101 |
| | 2003 NFPA-20 |
| | |
| | ** PLEASE SEE SOME OF THE CODES REFLECTED ON PLANS ARE |
| | NOT CURRENT. |
| | ** PLEASE ALSO SEE COMMENTS FROM OTHER TRADES WHICH MAY |
| | REQUESTED OTHER CODES TO BE STATED. |
| | |
| | 3) NOTE: PLEASE SEE THE ARCHITECTURAL SHEETS DO NOT ALL |
| | CONTAIN ORIGINAL SIGNATURES AS REQUIRED PER FS 481.221. |
| | PLEASE SEE ONLY THE COVER SHEET CONTAINS AN ORIGINAL |
| | SIGNATURE.SHEETS ARE RAISED SEALS OVER PHOTO-COPIED |
| | SIGNATURES. |
| | ALL THREE SETS CONTAIN AN IDENTICAL SIGNATURE ON ALL |
| | SHEETS. THIS COMMENT IS FOR THE ARCHITECT ONLY. PLEASE |
| | KNOW ONE SET OF PLANS ARE BEING RETAINED BY THIS |
| | OFFICE. |
| | |
| | 4) NOTE: PLEASE TITLE BLOCKS FOR ARCHITECTURAL FIRM ARE |
| | INCOMPLETE WITH REQUIRED INFORMATION PER FAC |
| | 61G1-16.004 AND FS 481.219. |
| | PLEASE SEE MISSING PRINTED NAME, PRINTED LICENSE NUMBER |
| | AND MISSING CERTIFICATE OF AUTHORIZATION NUMBER. THIS |
| | IS REQUIRED OF ALL SHEETS AND FOR ALL TRADES WHETHER OR |
| | NOT COMMENT IS MADE BY OTHER TRADES. |
| | |
| | 5) NOTE: PLEASE SEE *S* SHEETS WHICH IS ALSO MISSING |
| | REQUIRED INFORMATION PER FAC 61G15-23.002 AND FS |
| | 471.023 |
| | PLEASE SEE MISSING PRINTED NAME, PRINTED LICENSE NUMBER |
| | AND PRINTED FIRM LICENSE NUMBER ALSO KNOW AS THE |
| | ENGINEERING BUSINESS LICENSE NUMBER OR CERTIFICATE OF |
| | AUTHORIZATION NUMBER AS STATED IN THE FLORIDA |
| | STATUTES. |
| | ** THIS IS REQUIRED WHETHER OR NOT COMMENT IS MADE BY |
| | OTHER TRADE REVIEWER(S). |
| | |
| | 6) NOTE: PLEASE SEE ELECTRICAL PLANS AND FP SHEETS |
| | APPEAR TO BE SIGNED WITH INITIALS, IF THIS IS INDEED |
| | THE LEGAL SIGNATURE PLEASE SUBMIT SIGNATURE |
| | VERIFICATION LETTERS WHICH WILL BE REQUIRED TO BE |
| | SIGNED, DATED, SEALED AND NOTARIZED. |
| | ** PLEASE KNOW THESE WILL BE PLACED IN OUR SIGNATURE |
| | FILE FOR FUTURE REFERENCE AND WILL NTO NEED TO TURN |
| | THIS IN FOR FUTURE PROJECTS. |
| | FS 471.025 |
| | |
| | 7) NOTE: PLEASE SEE THE ENERGY CALCULATIONS ARE |
| | REQUIRED TO BE SIGNED, DATED SEALED AND CONTAIN ALL |
| | INFORMATION FOR ALL TRADES FOR CERTIFICATION PER FBC |
| | 2004 W/2006 REVISIONS TO 13-103.1.1.1 |
| | PLEASE ALSO SEE THE OWNER AGENT IS NOT SIGNED ON SHEET |
| | 2 AS NEED. |
| | |
| | 8) NOTE: PLEASE SEE 2004 FBC AS COMPLIANCE WITH CHAPTER |
| | 13 THE FLORIDA ENERGY CODE CAN NOT BE VERIFIED. PLEASE |
| | SEE 13-415.1.ABC.1.1, .1.2 AND .1.3. |
| | PLEASE SEE 13-415.1.AB.1.1, 13-415.2, 13-415.2.ABC.1.2, |
| | 13-415.1.ABC.2 ETC. PLEASE SEE CHAPTER 13. |
| | A) PLEASE SEE NOT ENOUGH INFORMATION WAS SUBMITTED FOR |
| | LIGHTING CONTROL SYSTEMS. |
| | B) PLEASE SEE NO TIME SCHEDULING FOR PROPOSED |
| | SYSTEM(S). |
| | C) PLEASE SEE LAYOUT FOR ZONES OF CONTROLS AND THE |
| | REQUIRED MULTIPLE SYSTEMS DUE TO THE SQ FT INVOLVED |
| | COULD NOT BE LOCATED. PLEASE SEE SEPARATE SPACES ALSO |
| | LIKE THE INTERIORS SUBWAY BUILDOUT. |
| | D) PLEASE SEE NO TIMES FOR ALL OVER RIDE DEVICES AND OS |
| | TYPE DEVICES COULD BE LOCATED ON PLANS. |
| | E) PLEASE SEE SOME AREAS WHERE DEVICES COULD NOT BE |
| | LOCATED AS THESE ARE SEPARATE SPACES CONTAINING FLOOR |
| | TO CEILING HEIGHTS PARTITIONS. |
| | F) PLEASE PROVIDE MORE INFORMATION ON OS DEVICES AND |
| | TYPE(S) OF DEVICES TO BE INSTALLED. PLEASE SEE THE |
| | BATHROOMS WHICH ARE NOT OF A SINGLE POINT OF USE AND |
| | THE DEVICES AS SHOWN WHICH MAY NOT PROVIDE THE COVERAGE |
| | AS NEEDED. ARE THESE ULTRA-SONIC? |
| | G) PLEASE SEE A FIXTURE LEGEND COULD NOT BE LOCATED FOR |
| | COORDINATED REVIEW OF THE ENERGY CALCULATIONS AS |
| | SUBMITTED. PLEASE SEE THE FOLLOWING COMMENT FOR THIS. |
| | H) PLEASE SEE OTHER COMMENTS AS LIGHTING ON PLANS HAS |
| | NOT BEEN COMPLETED FOR CIRCUITING AND DESIGNATIONS AT |
| | THIS TIME. |
| | I) PLEASE SEE THE ENERGY CALCULATIONS STATES *MANUAL |
| | ON/OFF* WHICH IS NOT POSSIBLE IF THESE ARE ALL PRT OF |
| | AUTOMATED LIGHTING CONTROLS ETC. PLEASE VERIFY THIS. J) |
| | PLEASE PROVIDE WORST CASE VOLTAGE DROP FOR BRANCH |
| | CIRCUITS AND FEEDERS PER 13-413.1.ABC.1 |
| | ** PLEASE KNOW AS THERE ARE SEVERAL ITEMS WHICH |
| | INFORMATION IS STILL NEEDED FOR REVIEW A COMPLETE |
| | REVIEW FOR CODE COMPLIANCE CAN NOT BE DONE AT THIS |
| | TIME. |
| | |
| | 9) NOTE: PLEASE COMPLETE PLANS AS SUBMITTED. PLEASE SEE |
| | THERE ARE NUMEROUS LIGHTING LUMINARIES WHICH DOE NOT |
| | SHOW ANY CONNECTIONS FOR CIRCUITING, CONTROLS ETC. |
| | PLEASE PROVIDE A DETAILED FIXTURE LEGEND WHICH |
| | COORDINATES NOT ONLY WITH THE ENERGY CALCULATIONS FOR |
| | THE NUMBER, TYPE, WATTAGE ETC OF FIXTURES BUT ALSO FOR |
| | THE DESIGNATIONS OF THESE LUMINARIES ON PLANS. REVIEW |
| | OF THESE CAN NOT BE DONE AT THIS TIME. |
| | FBC 106.1.2, 106.3.5.1.2 |
| | FBC 13-415 |
| | |
| | 10) NOTE: PLEASE SUBMIT THE MANUFACTURES SPECS/CUT |
| | SHEETS FOR THE FIRE PUMP/FIRE PUMP CONTROLLER. IT IS |
| | KNOW THAT THE FS WORK WILL BE UNDER A SEPARATE PERMIT |
| | HOWEVER THESE ARE REQUIRED IN BASE BUILDING PLANS AND |
| | FOR REVIEW. |
| | PLEASE SUPPLY THE INFORMATION OF FS PLANS FOR THE |
| | MINIMUM TIMES FOR FIRE PUMP RUNNING AT 100%. PLEASE SEE |
| | NFPA-20 11.4.1, 11.4.3, 11.4.5 (ALL). PLEASE SEE OTHER |
| | TRADES FOR REVIEW OF SYSTEMS FOR FIRE PUMP. |
| | 110.3, 90.7, FBC 106.1.2, 106.3.5.1.2 |
| | |
| | 11) NOTE: PLEASE SEE THE RISER INDICATES A *KIRK KEYED* |
| | INTERLOCK SYSTEM WHICH DOES NOT MEET 702.6. |
| | PLEASE KNOW AS QUESTIONNAIRE WAS E-MAILED TO THIS AHJ |
| | BY THE DESIGN TEAM ON 3/6/07 WHERE ONE OF THE QUESTIONS |
| | ON THE FORM WHICH APPEARS TO BE SENT OUT NATION-WIDE |
| | WAS WHETHER OR NOT THIS AHJ ALLOWS THE USE OF THESE. |
| | THE INFORMATION WAS SENT BACK TO THE DESIGNER AS THIS |
| | JURISDICTION AND OTHER LOCALLY HAVE HAD HAD SEVERAL |
| | INSTANCES WHERE MORE THAN ONE KEY IS INSTALLED, |
| | DELIVERED, MADE FOR THE SAME EQUIPMENT WHICH WOULD |
| | ALLOW THE INADVERTENT CONNECTION OF POWER FROM BOTH THE |
| | UTILITY AND THE ALTERNATE POWER SOURCE. PLEASE KNOW |
| | THIS IS OF GREAT CONCERN TO MANY JURISDICTIONS IN THIS |
| | AREA WHERE THERE IS NOT MECHANICAL INTERLOCK OF |
| | FAIL-SAFE MECHANISM WHICH PREVENTS THIS. THIS IS A LIFE |
| | SAFETY AND PROPERTY HAZARD. |
| | |
| | 12) NOTE: PLEASE SUBMIT AND COMPLETE THE AIC RATINGS |
| | AND AVAILABLE FAULT CURRENT FIGURES ON PLANS AT THIS |
| | TIME. PLEASE SEE THE RISER IS MISSING MOST OF THESE AND |
| | ARE SHOWN WITH XX, XXX ETC. |
| | 110.9 |
| | FBC 106.1.2 |
| | |
| | 13) NOTE: PLEASE SUBMIT THE MANUFACTURES SPECS/CUT |
| | SHEETS FOR THE PROPOSED UPS. |
| | PLEASE SE NO DISCONNECT COULD BE LOCATED ON THE LOAD |
| | SIDE OF THE UPS OR LINE SIDE PF THE PANEL LIU. PLEASE |
| | CLARIFY AS THE USE OF CORD AND PLUGS AS SHOWN IN |
| | DETAILS MAY ONLY BE SUED FOR SOME INSTANCES. PLEASE SEE |
| | 110.3, 645.11, 685, 692 ETC AS TYPES ARE NOT CLEAR AT |
| | THIS TIME. |
| | |
| | 14) NOTE: PLEASE KNOW THE FOLLOWING WILL BE REQUIRED TO |
| | BE UNDER SEPARATE PERMITS AND FEES. SOME MY ALSO NEED |
| | PLANS. THIS NOTE IS FOR INFORMATION PURPOSE ONLY. LOW |
| | VOLTAGE PERMITS: |
| | A) CATV, PHONE, SOUND SYSTEM, MAY ALL BE ON ONE |
| | SEPARATE PERMIT WITH FEES FOR THIS SCOPE OF WORK. THE |
| | MAIN PLANS MAY BE USED FOR REFERENCE AND A TURNAROUND |
| | PERMIT WILL BE ISSUED. |
| | B) THE FIRE ALARM SYSTEM MUST ALSO BE SUBMITTED UNDER |
| | SEPARATE PERMIT WITH PLANS EVEN THOUGH THE BASE |
| | BUILDING PLANS SHOW BASE SYSTEM/ SHOP DRAWINGS AND |
| | THESE PLANS WILL GO TO THE FIRE MARSHAL FOR REVIEW. C) |
| | ANY SECURITY ALARM SYSTEMS ARE SEPARATE PERMIT. THOSE |
| | OTHER TYPES OF SURVEILLANCE CAMERAS, ACCESS CONTROLS |
| | MAY BE PART OF THE MAIN PLANS, HOWEVER CAN BE DONE ON |
| | THEIR OWN PERMIT OR UNDER THECATC, PHONE ETC. |
| | ** ANY LOW VOLTAGE SYSTEMS WHICH ARE NOT SHOWN ON THESE |
| | BASE BUILDING PLANS WILL REQUIRE SEPARATE PLANS TO BE |
| | SUBMITTED WHEN SUBMITTING FOR PERMIT. |
| | |
| | 15) NOTE: PLEASE SUBMIT ALL INFORMATION FOR WIND LOADS |
| | FOR THE SITE LIGHTING POLES. MUST MEET FBC 140 MPH |
| | MINIMUM 3SEC GUST. |
| | PLEASE KNOW AS THE SITE PLANS WITH ALL ELECTRICAL PLANS |
| | ARE NOT COMPLETED IN SETS, THESE MAY BE DONE UNDER |
| | SEPARATE PERMIT. |
| | FBC 106.1.2 |
| | |
| | 16) NOTE: PLEASE SEE SOME PANEL AND EQUIPMENT ON PLANS |
| | DO NOT SEEM TO MEET 110.26 FOR MINIMUM WIDTHS OF |
| | WORKING CLEARANCE. |
| | PLEASE SEE PANEL(S) WHICH BASED ON SCALE HAVE LESS THEN |
| | 30INCHES FOR WIDTH. |
| | PLEASE SEE H1A2/MSB2 ON E2.4 WHICH APPEARS TO BE SHOWN |
| | DIRECTLY IN FRONT OF DOOR WAY? |
| | ** PLEASE VERIFY ALL EQUIPMENT, FOR REQUIRED ROOMS. ** |
| | PLEASE PROVIDE A SHEET FOR LAYOUT OF ELECTRICAL ROOMS |
| | (ENLARGED) FOR REVIEW. THE LAYOUT AS SHOWN IS NOT CLEAR |
| | FOR REVIEW. |
| | ** PLEASE VERIFY THE ACCESS TO THE MAIN ELECTRICAL ROOM |
| | WITH THE FIRE MARSHAL*S OFFICE. PLEASE KNOW A DIRECT |
| | ACCESS IS REQUIRED WITHOUT BRINGING THE FIRE PERSONNEL |
| | INTO THE BUILDING IN AN EMERGENCY. PLEASE SEE THE DOORS |
| | AS SHOWN MAY NEED TO BE RE-CONFIGURED. PLEASE ALSO KNOW |
| | THAT THE KNOX-BOX LOCATION WILL BE DETERMINED BY THE |
| | FIRE MARSHAL*S OFFICE. |
| | 110.26, 230.70A. THE NEC DOES NOT PROVIDE THE DISTANCE, |
| | THIS IS TO BE DETERMINED BY THE AHJ. |
| | |
| | 17) NOTE: PLEASE PROVIDE NOTES FOR COLOR CODING FOR |
| | 277/480V SYSTEMS AS BROWN, PURPLE, YELLOW. |
| | THE NEC DOES NOT GIVE THE COLOR CODING AND *ORANGE* IS |
| | FOR A HIGH-LEG SYSTEM WHICH THIS IS NOT. |
| | FBC 104.6, 90.4. |
| | |
| | 18) NOTE: PLEAS SUBMIT MORE DETAILS ON LOAD SUMMARY OF |
| | SERVICE AND PANELS. |
| | PLEASE SHOW ALL CONTINUOUS LOADS AT 125%. |
| | 220,215.3,230.42 ETC |
| | FBC 106.1.2 ADMIN SECTION. |
| | |
| | 19) NOTE: PLEASE SEE THE FA SHEETS NEED TO STATE THE |
| | FBC 2004 11-4.28.1, .2 AND .3(4) FOR DEVICES. |
| | THE LEVELS APPEAR TO BE OK AT THIS TIME HOWEVER ONLY |
| | NFPA-72 WAS STATED AND THE FBC HAS MORE STRINGENT |
| | REQUIREMENTS. |
| | |
| | 20) NOTE: PLEASE VERIFY MAINS WITH A NOTE THAT EACH |
| | CONTAIN A MANUAL MEANS OF DISCONNECT TO MEET 230.76, |
| | 230.79. |
| | |
| | 21) NOTE: PLEASE SEE THE RISER AS THE TAPS FROM T1D TO |
| | L1D2 COULD NOT LOCATED. PLEASE SEE 240.4, 310.16, AND |
| | 240.21 |
| | (AREA APPEARS TO ONLY HAVE MISPRINT). |
| | |
| | 22) NOTE: PLEASE VERIFY ALL OCP FOR AHU/HEAT PER |
| | 424.3B. |
| | PLEASE SEE SOME OF THESE SEEM A LITTLE LOW TO MEET THIS |
| | 125%. |
| | PLEASE ADJUST THE CONDUCTORS/OCP AS NEEDED. |
| | |
| | 23) NOTE: PLEASE COMPLETE PANEL SCHEDULES FOR CONDUCTOR |
| | SIZES. PLEASE SEE PREVIOUS COMMENT WITH RESPECT TO |
| | VOLTAGE DROP. |
| | 408.4, 310.16, 240.4. |
| | FBC ADMIN SECTION 106.1.2, 106.3.5.1.2 |
| | |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | ** PLEASE BE SURE TO SEE ANY COMMENTS FROM OTHER TRADES |
| | WHICH MAY AFFECT ELECTRICAL PLANS AND DESIGN CHANGES. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| 2007-06-24 12:22:06 | 2007-06-24 12:22:06 |
| | REVIEW IN PROGRESS. |
| 2007-06-23 21:04:13 | 2007-06-23 21:04:13 |
| | ONE ROLL IN ELECTRICAL FOR REVIEW. REVIEW IN PROGRESS. |