2007-06-24 15:23:34 
  
 *** UNSAT ***
  
 WAL-MART
 SUPERCENTER.
  
 1A) NOTE: PLEASE KNOW ONCE THE ADDRESS HAS BEEN
 CONFIRMED THE ADDRESS FOR THE LOCATION OF THIS PROJECT
 SHALL BE SHOWN IN TITLE BLOCKS.
 FAC 61G1-16.004, 61G15-23.002
  
 1B) NOTE: PLEASE SEE PLANS WERE ONLY SUBMITTED FOR
 *PLAN REVIEW* AND HAVE NOT BEEN SUBMITTED OR PERMIT.
 PLEASE KNOW EVEN ONCE ALL COMMENTS FOR CODE COMPLIANCE
 ARE MET AND PERMIT APPLICATION HAS NOT BEEN MADE THE
 REVIEW(S) WILL STILL GO INTO A FAILED STATUES. PLEASE
 KNOW THERE ARE SEVERAL ITEMS WHICH ARE TO BE VERIFIED
 ONCE APPLICATION HAS BEEN MADE. PLEASE KNOW IF THERE
 ARE ANY CODE CHANGES ADOPTED BY THE STATE BEFORE PERMIT
 APPLICATION IS MADE WILL REQUIRED DESIGNS UNDER NEW
 CODES.
 ALL LICENSING WILL BE REVIEWED BEFORE ISSUANCE.
  
 2) NOTE:PLEASE KNOW THAT ANY PERMIT APPLICATIONS
 WHICH ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES
 PROJECTS UNDER THE NEW CODES ADOPTED BY THE STATE.
 PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO
 THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70.
 PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY
 AFFECT DESIGNS FOR ALL TRADES.SOME OF THESE ARE
 STATED ON PLANS HOWEVER NOT ALL AND NOT ALL CURRENT PER
 STATE ADOPTED CODES.
 PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETSAND
 ARCHITECTURAL COVER SHEET FOR THIS REVIEWER AT A
 MINIMUM.
 2004 FBC W/ 2006 REVISIONS
 2005 NFPA-70
 2002 NFPA-72
 2003 NFPA-101
 2003 NFPA-20
  
 ** PLEASE SEE SOME OF THE CODES REFLECTED ON PLANS ARE
 NOT CURRENT.
 ** PLEASE ALSO SEE COMMENTS FROM OTHER TRADES WHICH MAY
 REQUESTED OTHER CODES TO BE STATED.
  
 3) NOTE: PLEASE SEE THE ARCHITECTURAL SHEETS DO NOT ALL
 CONTAIN ORIGINAL SIGNATURES AS REQUIRED PER FS 481.221.
 PLEASE SEE ONLY THE COVER SHEET CONTAINS AN ORIGINAL
 SIGNATURE.SHEETS ARE RAISED SEALS OVER PHOTO-COPIED
 SIGNATURES.
 ALL THREE SETS CONTAIN AN IDENTICAL SIGNATURE ON ALL
 SHEETS. THIS COMMENT IS FOR THE ARCHITECT ONLY. PLEASE
 KNOW ONE SET OF PLANS ARE BEING RETAINED BY THIS
 OFFICE.
  
 4) NOTE: PLEASE TITLE BLOCKS FOR ARCHITECTURAL FIRM ARE
 INCOMPLETE WITH REQUIRED INFORMATION PER FAC
 61G1-16.004 AND FS 481.219.
 PLEASE SEE MISSING PRINTED NAME, PRINTED LICENSE NUMBER
 AND MISSING CERTIFICATE OF AUTHORIZATION NUMBER. THIS
 IS REQUIRED OF ALL SHEETS AND FOR ALL TRADES WHETHER OR
 NOT COMMENT IS MADE BY OTHER TRADES.
  
 5) NOTE: PLEASE SEE *S* SHEETS WHICH IS ALSO MISSING
 REQUIRED INFORMATION PER FAC 61G15-23.002 AND FS
 471.023
 PLEASE SEE MISSING PRINTED NAME, PRINTED LICENSE NUMBER
 AND PRINTED FIRM LICENSE NUMBER ALSO KNOW AS THE
 ENGINEERING BUSINESS LICENSE NUMBER OR CERTIFICATE OF
 AUTHORIZATION NUMBER AS STATED IN THE FLORIDA
 STATUTES.
 ** THIS IS REQUIRED WHETHER OR NOT COMMENT IS MADE BY
 OTHER TRADE REVIEWER(S).
  
 6) NOTE: PLEASE SEE ELECTRICAL PLANS AND FP SHEETS
 APPEAR TO BE SIGNED WITH INITIALS, IF THIS IS INDEED
 THE LEGAL SIGNATURE PLEASE SUBMIT SIGNATURE
 VERIFICATION LETTERS WHICH WILL BE REQUIRED TO BE
 SIGNED, DATED, SEALED AND NOTARIZED.
 ** PLEASE KNOW THESE WILL BE PLACED IN OUR SIGNATURE
 FILE FOR FUTURE REFERENCE AND WILL NTO NEED TO TURN
 THIS IN FOR FUTURE PROJECTS.
 FS 471.025
  
 7) NOTE: PLEASE SEE THE ENERGY CALCULATIONS ARE
 REQUIRED TO BE SIGNED, DATED SEALED AND CONTAIN ALL
 INFORMATION FOR ALL TRADES FOR CERTIFICATION PER FBC
 2004 W/2006 REVISIONS TO 13-103.1.1.1
 PLEASE ALSO SEE THE OWNER AGENT IS NOT SIGNED ON SHEET
 2 AS NEED.
  
 8) NOTE: PLEASE SEE 2004 FBC AS COMPLIANCE WITH CHAPTER
 13 THE FLORIDA ENERGY CODE CAN NOT BE VERIFIED. PLEASE
 SEE 13-415.1.ABC.1.1, .1.2 AND .1.3.
 PLEASE SEE 13-415.1.AB.1.1, 13-415.2, 13-415.2.ABC.1.2,
 13-415.1.ABC.2 ETC. PLEASE SEE CHAPTER 13.
 A) PLEASE SEE NOT ENOUGH INFORMATION WAS SUBMITTED FOR
 LIGHTING CONTROL SYSTEMS.
 B) PLEASE SEE NO TIME SCHEDULING FOR PROPOSED
 SYSTEM(S).
 C) PLEASE SEE LAYOUT FOR ZONES OF CONTROLS AND THE
 REQUIRED MULTIPLE SYSTEMS DUE TO THE SQ FT INVOLVED
 COULD NOT BE LOCATED. PLEASE SEE SEPARATE SPACES ALSO
 LIKE THE INTERIORS SUBWAY BUILDOUT.
 D) PLEASE SEE NO TIMES FOR ALL OVER RIDE DEVICES AND OS
 TYPE DEVICES COULD BE LOCATED ON PLANS.
 E) PLEASE SEE SOME AREAS WHERE DEVICES COULD NOT BE
 LOCATED AS THESE ARE SEPARATE SPACES CONTAINING FLOOR
 TO CEILING HEIGHTS PARTITIONS.
 F) PLEASE PROVIDE MORE INFORMATION ON OS DEVICES AND
 TYPE(S) OF DEVICES TO BE INSTALLED. PLEASE SEE THE
 BATHROOMS WHICH ARE NOT OF A SINGLE POINT OF USE AND
 THE DEVICES AS SHOWN WHICH MAY NOT PROVIDE THE COVERAGE
 AS NEEDED. ARE THESE ULTRA-SONIC?
 G) PLEASE SEE A FIXTURE LEGEND COULD NOT BE LOCATED FOR
 COORDINATED REVIEW OF THE ENERGY CALCULATIONS AS
 SUBMITTED. PLEASE SEE THE FOLLOWING COMMENT FOR THIS.
 H) PLEASE SEE OTHER COMMENTS AS LIGHTING ON PLANS HAS
 NOT BEEN COMPLETED FOR CIRCUITING AND DESIGNATIONS AT
 THIS TIME.
 I) PLEASE SEE THE ENERGY CALCULATIONS STATES *MANUAL
 ON/OFF* WHICH IS NOT POSSIBLE IF THESE ARE ALL PRT OF
 AUTOMATED LIGHTING CONTROLS ETC. PLEASE VERIFY THIS. J)
 PLEASE PROVIDE WORST CASE VOLTAGE DROP FOR BRANCH
 CIRCUITS AND FEEDERS PER 13-413.1.ABC.1
 ** PLEASE KNOW AS THERE ARE SEVERAL ITEMS WHICH
 INFORMATION IS STILL NEEDED FOR REVIEW A COMPLETE
 REVIEW FOR CODE COMPLIANCE CAN NOT BE DONE AT THIS
 TIME.
  
 9) NOTE: PLEASE COMPLETE PLANS AS SUBMITTED. PLEASE SEE
 THERE ARE NUMEROUS LIGHTING LUMINARIES WHICH DOE NOT
 SHOW ANY CONNECTIONS FOR CIRCUITING, CONTROLS ETC.
 PLEASE PROVIDE A DETAILED FIXTURE LEGEND WHICH
 COORDINATES NOT ONLY WITH THE ENERGY CALCULATIONS FOR
 THE NUMBER, TYPE, WATTAGE ETC OF FIXTURES BUT ALSO FOR
 THE DESIGNATIONS OF THESE LUMINARIES ON PLANS. REVIEW
 OF THESE CAN NOT BE DONE AT THIS TIME.
 FBC 106.1.2, 106.3.5.1.2
 FBC 13-415
  
 10) NOTE: PLEASE SUBMIT THE MANUFACTURES SPECS/CUT
 SHEETS FOR THE FIRE PUMP/FIRE PUMP CONTROLLER. IT IS
 KNOW THAT THE FS WORK WILL BE UNDER A SEPARATE PERMIT
 HOWEVER THESE ARE REQUIRED IN BASE BUILDING PLANS AND
 FOR REVIEW.
 PLEASE SUPPLY THE INFORMATION OF FS PLANS FOR THE
 MINIMUM TIMES FOR FIRE PUMP RUNNING AT 100%. PLEASE SEE
 NFPA-20 11.4.1, 11.4.3, 11.4.5 (ALL). PLEASE SEE OTHER
 TRADES FOR REVIEW OF SYSTEMS FOR FIRE PUMP.
 110.3, 90.7, FBC 106.1.2, 106.3.5.1.2
  
 11) NOTE: PLEASE SEE THE RISER INDICATES A *KIRK KEYED*
 INTERLOCK SYSTEM WHICH DOES NOT MEET 702.6.
 PLEASE KNOW AS QUESTIONNAIRE WAS E-MAILED TO THIS AHJ
 BY THE DESIGN TEAM ON 3/6/07 WHERE ONE OF THE QUESTIONS
 ON THE FORM WHICH APPEARS TO BE SENT OUT NATION-WIDE
 WAS WHETHER OR NOT THIS AHJ ALLOWS THE USE OF THESE.
 THE INFORMATION WAS SENT BACK TO THE DESIGNER AS THIS
 JURISDICTION AND OTHER LOCALLY HAVE HAD HAD SEVERAL
 INSTANCES WHERE MORE THAN ONE KEY IS INSTALLED,
 DELIVERED, MADE FOR THE SAME EQUIPMENT WHICH WOULD
 ALLOW THE INADVERTENT CONNECTION OF POWER FROM BOTH THE
 UTILITY AND THE ALTERNATE POWER SOURCE. PLEASE KNOW
 THIS IS OF GREAT CONCERN TO MANY JURISDICTIONS IN THIS
 AREA WHERE THERE IS NOT MECHANICAL INTERLOCK OF
 FAIL-SAFE MECHANISM WHICH PREVENTS THIS. THIS IS A LIFE
 SAFETY AND PROPERTY HAZARD.
  
 12) NOTE: PLEASE SUBMIT AND COMPLETE THE AIC RATINGS
 AND AVAILABLE FAULT CURRENT FIGURES ON PLANS AT THIS
 TIME. PLEASE SEE THE RISER IS MISSING MOST OF THESE AND
 ARE SHOWN WITH XX, XXX ETC.
 110.9
 FBC 106.1.2
  
 13) NOTE: PLEASE SUBMIT THE MANUFACTURES SPECS/CUT
 SHEETS FOR THE PROPOSED UPS.
 PLEASE SE NO DISCONNECT COULD BE LOCATED ON THE LOAD
 SIDE OF THE UPS OR LINE SIDE PF THE PANEL LIU. PLEASE
 CLARIFY AS THE USE OF CORD AND PLUGS AS SHOWN IN
 DETAILS MAY ONLY BE SUED FOR SOME INSTANCES. PLEASE SEE
 110.3, 645.11, 685, 692 ETC AS TYPES ARE NOT CLEAR AT
 THIS TIME.
  
 14) NOTE: PLEASE KNOW THE FOLLOWING WILL BE REQUIRED TO
 BE UNDER SEPARATE PERMITS AND FEES. SOME MY ALSO NEED
 PLANS. THIS NOTE IS FOR INFORMATION PURPOSE ONLY. LOW
 VOLTAGE PERMITS:
 A) CATV, PHONE, SOUND SYSTEM, MAY ALL BE ON ONE
 SEPARATE PERMIT WITH FEES FOR THIS SCOPE OF WORK. THE
 MAIN PLANS MAY BE USED FOR REFERENCE AND A TURNAROUND
 PERMIT WILL BE ISSUED.
 B) THE FIRE ALARM SYSTEM MUST ALSO BE SUBMITTED UNDER
 SEPARATE PERMIT WITH PLANS EVEN THOUGH THE BASE
 BUILDING PLANS SHOW BASE SYSTEM/ SHOP DRAWINGS AND
 THESE PLANS WILL GO TO THE FIRE MARSHAL FOR REVIEW. C)
 ANY SECURITY ALARM SYSTEMS ARE SEPARATE PERMIT. THOSE
 OTHER TYPES OF SURVEILLANCE CAMERAS, ACCESS CONTROLS
 MAY BE PART OF THE MAIN PLANS, HOWEVER CAN BE DONE ON
 THEIR OWN PERMIT OR UNDER THECATC, PHONE ETC.
 ** ANY LOW VOLTAGE SYSTEMS WHICH ARE NOT SHOWN ON THESE
 BASE BUILDING PLANS WILL REQUIRE SEPARATE PLANS TO BE
 SUBMITTED WHEN SUBMITTING FOR PERMIT.
  
 15) NOTE: PLEASE SUBMIT ALL INFORMATION FOR WIND LOADS
 FOR THE SITE LIGHTING POLES. MUST MEET FBC 140 MPH
 MINIMUM 3SEC GUST.
 PLEASE KNOW AS THE SITE PLANS WITH ALL ELECTRICAL PLANS
 ARE NOT COMPLETED IN SETS, THESE MAY BE DONE UNDER
 SEPARATE PERMIT.
 FBC 106.1.2
  
 16) NOTE: PLEASE SEE SOME PANEL AND EQUIPMENT ON PLANS
 DO NOT SEEM TO MEET 110.26 FOR MINIMUM WIDTHS OF
 WORKING CLEARANCE.
 PLEASE SEE PANEL(S) WHICH BASED ON SCALE HAVE LESS THEN
 30INCHES FOR WIDTH.
 PLEASE SEE H1A2/MSB2 ON E2.4 WHICH APPEARS TO BE SHOWN
 DIRECTLY IN FRONT OF DOOR WAY?
 ** PLEASE VERIFY ALL EQUIPMENT, FOR REQUIRED ROOMS. **
 PLEASE PROVIDE A SHEET FOR LAYOUT OF ELECTRICAL ROOMS
 (ENLARGED) FOR REVIEW. THE LAYOUT AS SHOWN IS NOT CLEAR
 FOR REVIEW.
 ** PLEASE VERIFY THE ACCESS TO THE MAIN ELECTRICAL ROOM
 WITH THE FIRE MARSHAL*S OFFICE. PLEASE KNOW A DIRECT
 ACCESS IS REQUIRED WITHOUT BRINGING THE FIRE PERSONNEL
 INTO THE BUILDING IN AN EMERGENCY. PLEASE SEE THE DOORS
 AS SHOWN MAY NEED TO BE RE-CONFIGURED. PLEASE ALSO KNOW
 THAT THE KNOX-BOX LOCATION WILL BE DETERMINED BY THE
 FIRE MARSHAL*S OFFICE.
 110.26, 230.70A. THE NEC DOES NOT PROVIDE THE DISTANCE,
 THIS IS TO BE DETERMINED BY THE AHJ.
  
 17) NOTE: PLEASE PROVIDE NOTES FOR COLOR CODING FOR
 277/480V SYSTEMS AS BROWN, PURPLE, YELLOW.
 THE NEC DOES NOT GIVE THE COLOR CODING AND *ORANGE* IS
 FOR A HIGH-LEG SYSTEM WHICH THIS IS NOT.
 FBC 104.6, 90.4.
  
 18) NOTE: PLEAS SUBMIT MORE DETAILS ON LOAD SUMMARY OF
 SERVICE AND PANELS.
 PLEASE SHOW ALL CONTINUOUS LOADS AT 125%.
 220,215.3,230.42 ETC
 FBC 106.1.2 ADMIN SECTION.
  
 19) NOTE: PLEASE SEE THE FA SHEETS NEED TO STATE THE
 FBC 2004 11-4.28.1, .2 AND .3(4) FOR DEVICES.
 THE LEVELS APPEAR TO BE OK AT THIS TIME HOWEVER ONLY
 NFPA-72 WAS STATED AND THE FBC HAS MORE STRINGENT
 REQUIREMENTS.
  
 20) NOTE: PLEASE VERIFY MAINS WITH A NOTE THAT EACH
 CONTAIN A MANUAL MEANS OF DISCONNECT TO MEET 230.76,
 230.79.
  
 21) NOTE: PLEASE SEE THE RISER AS THE TAPS FROM T1D TO
 L1D2 COULD NOT LOCATED. PLEASE SEE 240.4, 310.16, AND
 240.21
 (AREA APPEARS TO ONLY HAVE MISPRINT).
  
 22) NOTE: PLEASE VERIFY ALL OCP FOR AHU/HEAT PER
 424.3B.
 PLEASE SEE SOME OF THESE SEEM A LITTLE LOW TO MEET THIS
 125%.
 PLEASE ADJUST THE CONDUCTORS/OCP AS NEEDED.
  
 23) NOTE: PLEASE COMPLETE PANEL SCHEDULES FOR CONDUCTOR
 SIZES. PLEASE SEE PREVIOUS COMMENT WITH RESPECT TO
 VOLTAGE DROP.
 408.4, 310.16, 240.4.
 FBC ADMIN SECTION 106.1.2, 106.3.5.1.2
  
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 ** PLEASE BE SURE TO SEE ANY COMMENTS FROM OTHER TRADES
 WHICH MAY AFFECT ELECTRICAL PLANS AND DESIGN CHANGES.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2007-06-24 12:22:062007-06-24 12:22:06
 REVIEW IN PROGRESS.
2007-06-23 21:04:132007-06-23 21:04:13
 ONE ROLL IN ELECTRICAL FOR REVIEW. REVIEW IN PROGRESS.