2007-07-05 09:26:22WALMART SUPERCENTER 4225 45TH ST
  
 BUILDING PLAN REVIEW
 PERMIT: 07050729
 ADD: 4225 45TH STREETBUILDING
 TYPE VB? SPRINKLED
 CONT:PLAN REVIEW507.2 UNLIMITED AREA
 TEL:
 BUILDING IMPORTANCE III / FACTOR 1.15
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 1STREVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 2)CONTRACTOR TO FILE: FL S S 713.13 NOTICE OF
 COMMENCEMENT, TO BE FILED WITH THE CLERK OF THE COURT.
 NOTE: 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLYCOMMENCED WITHIN 90 DAYS
 AFTER THE RECORDING THEREOF, SUCH NOTICE IS NULL &
 VOID. NOTE: 713.13(6) THE POSTING OF THE NOTICE OF
 COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST
 INSPECTION.
  
 3) PLEASE SEE THE ARCHITECTURAL SHEETS SIGNATURES ARE
 PHOTOCOPIES WITH A RAISED SEAL. SHEET TO SHEET THEY
 APPEAR DIFFERENT BUT WHEN COMPARED EACH SHEET
 INDIVIDUALLY ROLL TO ROLL PHOTOCOPIED.
 PLANS, SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS
 PREPARED BY THE DESIGN PROFESSIONAL AND BEING FILED FOR
 PUBLIC RECORD SHALL HAVE THE SIGNATURE AND SEAL OF THE
 DESIGN PROFESSIONAL AFFIXED TO THE DOCUMENT.
 FL STATE STAT: 61G15-23.002 ENGINEERS
 FL STATE STAT: 61G16.003 ARCHITECTS
  
 4) BRR ARCHITECTURAL FIRM IS MISSING THEIR CERTIFICATE
 OF AUTHORIZATION. 471.023 F.S.CERTIFICATE OF
 AUTHORIZATION.THE TITLE BLOCK FOR ANY SHEET BEARING
 THE NAME OF AN ENGINEER PRACTICING UNDER A FICTITIOUS
 NAME, A CORPORATION, OR A PARTNERSHIP, OFFERING
 ENGINEERING SERVICES, SHALL INCLUDE THE CERTIFICATE OF
 AUTHORIZATION NUMBER. ADD THE NUMBER TO EACH SHEET.
 THIS MAY BE ADDED BY HAND.
  
 5)ARCHITECTURAL SHEETS ARE MISSING THE PRINTED NAME
 OF THE DESIGN PROFESSIONAL IN THE TITLE BLOCK FL
 ADMINISTRATIVE CODE 61G1-16.004(6) PRINTED NAME AND
 LICENSE NUMBER OF PERSON SEALING THE DOCUMENT.
  
 6)THE STRUCTURAL SHEETS ARE ALSO MISSING THE
 FOLLOWING INFORMATION IN THEIR TITLE BLOCK:
 61G15-23.002 THE PRINTED NAME AND LICENSE NUMBER AND
 THE FIRMS CERTIFICATE OF AUTHORIZATION.
  
 7A)FBC* 105.3RESIDENT INSPECTOR. SUBMIT INSPECTOR
 RESUME' AND LICENSE DOCUMENTS TO HAROLD PISKURA,
 DIRECTOR OF THE RESIDENT INSPECTOR PROGRAM. THE
 RESIDENT INSPECTOR PROGRAM IS REQUIRED, ON THIS
 PROJECT, DUE TO ONE OR MORE OF THE FOLLOWING:
 - BUILDINGS/ADDITIONS OF TYPE I OR II
 CONSTRUCTION
 - ANY MAJOR STRUCTURAL ALTERATIONS
 - STRUCTURES IN WHICH THE CONCRETE
 DESIGN IS BASED ON COMPRESSIVE
 STRENGTH (F'C) IN EXCESS OF 3000 PSI
 - PILE DRIVING
 - BUILDINGS OVER 20,000 SQFT IN AREA
 - BUILDINGS OVER 2 STORIES IN HEIGHT
 - BUILDING/STRUCTURES OF UNUSUAL DESIGN
  
 7B) THIS JOB WILL REQUIRE THREE (3) SETS OF ALL
 DOCUMENTS SUBMITTED TO THE BUILDING DEPARTMENT, PLANS
 REPORTS, SUBMITTALS AND OR PRODUCT APPROVALS.
  
 8)FBC 1802.2.1 QUESTIONABLE SOILS,
 1802.2.1 QUESTIONABLE SOIL.
 WHERE THE SAFE-SUSTAINING POWER OF THE SOIL IS IN
 DOUBT, OR WHERE A LOAD-BEARING VALUE SUPERIOR TO THAT
 SPECIFIED IN THIS CODE IS CLAIMED, THE BUILDING
 OFFICIAL SHALL REQUIRE THAT THE NECESSARY INVESTIGATION
 BE MADE. SUCH INVESTIGATION SHALL COMPLY WITH THE
 PROVISIONS OF SECTIONS 1802.4 THROUGH 1802.6 .
  
 9)BUILDING TO BE LOCATED IN A FLOOD ZONE A8, MINIMUM
 FINISH FLOOR ELEVATION OF SLAB AND ANY ELECTRICAL OR
 MECHANICAL EQUIPMENT SLABS MUST ALSO MEET THIS
 REQUIREMENT. PROVIDE FLOOD ZONE ELEVATION CERTIFICATE
 FOR NEW CONSTRUCTION BEFORE CERTIFICATE OF OCCUPANCY
 WILL OCCUR. BASE FLOOD ELEVATION, CITY CODE REQUIRES AN
 ADDITIONAL 6" OR 15?-6?.
  
 10)SHEET SP1 IS LABELED SITE PLAN, PLEASE PROVIDE A
 SITE PLAN PROVIDING THE FOLLOWING:
 11-4.1.2 AN ACCESSIBLE SITE SHALL MEET THE FOLLOWING
 MINIMUM REQUIREMENTS:
 (1)AT LEAST ONE ACCESSIBLE ROUTE COMPLYING WITH
 SECTION 11-4.3 SHALL BE PROVIDED WITHIN THE BOUNDARY OF
 THE SITE FROM PUBLIC TRANSPORTATION STOPS, ACCESSIBLE
 PARKING SPACES, PASSENGER LOADING ZONES IF PROVIDED,
 AND PUBLIC STREETS OR SIDEWALKS, TO AN ACCESSIBLE
 BUILDING ENTRANCE.
 (2)AT LEAST ONE ACCESSIBLE ROUTE COMPLYING WITH
 SECTION 11-4.3 SHALL CONNECT ACCESSIBLE BUILDINGS,
 ACCESSIBLE FACILITIES, ACCESSIBLE ELEMENTS, AND
 ACCESSIBLE SPACES THAT ARE ON THE SAME SITE .
 (3)ALL OBJECTS THAT PROTRUDE FROM SURFACES OR
 POSTS INTO CIRCULATION PATHS SHALL COMPLY WITH SECTION
 11-4.4 .
 (4)GROUND SURFACES ALONG ACCESSIBLE ROUTES AND IN
 ACCESSIBLE SPACES SHALL COMPLY WITH SECTION 11-4.5 .
 (5)PARKING SPACES:
  
 11A) SHEET SP2 FRONT ENTRY, SHOW TRANSITION FROM THE
 CURB, AND CURB CUT TO THE WALKING SURFACE WILL THERE BE
 FLARED SIDES? 11-4.7.
  
 11B) ADDITIONAL COMMENTS MAY APPEAR ON THE SITE
 ACCESSIBILITY ISSUES, NOT HAVING A FULL SCALE SITE PLAN
 AVAILABLE. 11-4.6.2 LOCATION.
 ACCESSIBLE PARKING SPACES SERVING A PARTICULAR BUILDING
 SHALL BE LOCATED ON THE SHORTEST SAFELY ACCESSIBLE
 ROUTE OF TRAVEL FROM ADJACENT PARKING TO AN ACCESSIBLE
 ENTRANCE. IN PARKING FACILITIES THAT DO NOT SERVE A
 PARTICULAR BUILDING, ACCESSIBLE PARKING SHALL BE
 LOCATED ON THE SHORTEST ACCESSIBLE ROUTE OF TRAVEL TO
 AN ACCESSIBLE PEDESTRIAN ENTRANCE OF THE PARKING
 FACILITY. IN BUILDINGS WITH MULTIPLE ACCESSIBLE
 ENTRANCES WITH ADJACENT PARKING, ACCESSIBLE PARKING
 SPACES SHALL BE DISPERSED AND LOCATED CLOSEST TO THE
 ACCESSIBLE ENTRANCES.
 EACH PARKING SPACE MUST BE NO LESS THAN 12 FEET (3658
 MM) WIDE.
 (1)ALL SPACES MUST BE LOCATED ON AN ACCESSIBLE
 ROUTE NO LESS THAN 44 INCHES (1118 MM)WIDE SO THAT
 USERS WILL NOT BE COMPELLED TO WALK OR WHEEL BEHIND
 PARKED VEHICLES.
  
  
 12) SITE PLAN PLEASE PROVIDE A SITE PLAN WITH
 DIMENSIONS TO THE PROPERTY LINE. THIS PROJECT IS
 CLAIMING UNLIMITED AREA FOR A TYPE VB SPRINKLED
 BUILDING,507.2 REQUIRES 60? CLEAR OR PORTION MAY BE
 REDUCED WITH 3 HR WALLS AND OPENING PROTECTIVE, PROVIDE
 A SITE PLAN.
  
 13) ) 109.3.10* IMPACT OF CONSTRUCTION. ALL
 CONSTRUCTION ACTIVITY REGULATED BY THIS CODE SHALL BE
 PERFORMED IN A MANNER SO AS NOT TO ADVERSELY IMPACT THE
 CONDITION OF ADJACENT PROPERTY, UNLESS SUCH ACTIVITY IS
 PERMITTED TO AFFECT SAID PROPERTY PURSUANT TO A CONSENT
 BY THE APPLICABLE PROPERTY OWNER, UNDER TERMS &
 CONDITIONS AGREEABLE TO THE APPLICABLE PROPERTY OWNER.
 THIS INCLUDES BUT IS NOT LIMITED TO THE CONTROL OF
 DUST, NOISE, WATER OR DRAINAGE RUN-OFF, DEBRIS, AND THE
 STORAGE OF CONSTRUCTION MATERIALS. NEW CONSTRUCTION
 ACTIVITY SHALL NOT ADVERSELY IMPACT HISTORIC SURFACE
 WATER DRAINAGE FLOWS SERVING ADJACENT PROPERTIES, & MAY
 REQUIRE SPECIAL DRAINAGE DESIGN COMPLYING WITH
 ENGINEERING STANDARDS TO PRESERVE THE POSITIVE PATTERNS
 OF THE AFFECTED SITES. ACCORDINGLY, DEVELOPERS,
 CONTRACTORS, AND OWNERS OF ALL NEW RESIDENTIAL
 DEVELOPMENT, INCLUDING ADDITIONS, POOLS,
 PATIOS, DRIVEWAYS, DECKS, OR SIMILAR ITEMS, ON EXISTING
 PROPERTIES RESULTING IN A DECREASE IN EXCESS OF 800SQ
 FT OF PERMEABLE LAND AREA ON ANY PARCEL SHALL AS A
 PERMIT CONDITION, PROVIDE A PROFESSIONALLY PREPARED
 DRAINAGE PLAN CLEARLY INDICATING COMPLIANCE WITH THIS
 PARAGRAPH. UPON COMPLETION OF THE IMPROVEMENT, A
 CERTIFICATE FROM A LICENSED ENGINEER SHALL BE SUBMITTED
 TO THE INSPECTOR IN ORDER TO RECEIVE APPROVAL OF THE
 FINAL INSPECTION.
  
 14)109.3.10.1 HURRICANE PROTECTION. IT SHALL BE
 UNLAWFUL FOR ANY PERSON TO ALLOW CONSTRUCTION RELATED
 MATERIALS EQUIPMENT AND DEBRIS TO REMAIN LOOSE OR
 OTHERWISE UNSECURED AT A CONSTRUCTION SITE FROM 24 HRS.
 AFTER A HURRICANE WATCH HAS BEEN ISSUED UNTIL THE
 HURRICANE WATCH OR WARNING HAS BEEN LIFTED. ALL SUCH
 CONSTRUCTION MATERIALS,
 EQUIPMENT AND DEBRIS SHALL BE EITHER REMOVED FROM THE
 CONSTRUCTION SITE OR SECURED IN SUCH A MANNER AS TO
 MINIMIZE THE DANGER OF SUCH CONSTRUCTION MATERIALS,
 EQUIPMENT AND DEBRIS CAUSING DAMAGE TO PERSONS OR
 PROPERTY FROM HIGH WINDS. ANY PERSONS WHO FAILS TO
 COMPLY TO REMOVE OR SECURE THE CONSTRUCTION MATERIALS
 EQUIPMENT AND DEBRIS WITHIN
 24 HRS AFTER A HURRICANE WATCH HAS BEEN ISSUED SHALL BE
 SUBJECT TO A FINE NOT TO EXCEED $500.00.IN ADDITION
 TO THE ABOVE, A LICENSED CONTRACTOR WHO VIOLATES THIS
 SECTION SHALL BE SUBJECT TO DISCIPLINE PURSUANT TO
 SECTION 113 OF THIS CHAPTER.
  
 15) SHEET R-4 AND R-5 ARE NOT SIGNED NOR SEALED IN THE
 ROLL BEING REVIEWED.
 PLANS, SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS
 PREPARED BY THE DESIGN PROFESSIONAL AND BEING FILED FOR
 PUBLIC RECORD SHALL HAVE THE SIGNATURE AND SEAL OF THE
 DESIGN PROFESSIONAL AFFIXED
 TO THE DOCUMENT.
 FL STATE STAT: 61G15-23.002 ENGINEERS
 FL ATATE STAT: 61G16.003 ARCHITECTS
  
 16)SHEET C-1 INDICATES THIS BUILDING IS DECLARING
 ITSELF AS UNLIMITED IN AREA BY THE CODE SECTION507.2,
 NOTE THIS CAN NOT BE CONFIRMED AT THIS TIME SINCE THE
 SITE PLAN SP-2 IS ONLY OF THE BUILDING AND NOT TO THE
 PROPERTY LINE. THIS INFORMATION IS TO BE INCLUSIVE IN
 THIS SET OF DOCUMENTS! 106.1.2 ADDITIONAL INFORMATION
 AND 507.2.
  
 17)SHEET A-6:
 17A) THE BREAK ROOM, HAS AN OCCUPANT LOAD OF OVER 50
 CREATING AN A-2 OCCUPANCY, THE PLANS INDICATE A WALL
 TYPE A-3 AND A-6 WALL TYPE, THE WALL SCHEDULE ON A-6.1
 DOESN?T INDICATE THESE WALLS BEING FIRE RATED? TRUE
 THESE WALLS DO NOT NEED TO BE FIRE RATED IN ACCORDANCE
 WITH 302.3.2 BUT THERE IS AN A-2 OCCUPANCY IN THE BREAK
 ROOM THAT DOES REQUIRE 1 HOUR RATED CORRIDORS WHEN
 THERE IS AN OCCUPANT LOAD GREATER THAN 30 PEOPLE, SEE
 TABLE 1016, ASSEMBLY OCCUPANCY.
  
 17B) 106.1.2* ADDITIONAL INFORMATION REQUIRED ROOM 154
 EDC PLEASE PROVIDE WHAT THIS STANDS FOR?
  
 17C) NOTE THE EXTERIOR DOORS DO NOT HAVE IDENTIFICATION
 TAGS? 106.1.2*
  
 17D)DOOR 162-C PLANS INDICATE ONE PORTION OF THE WALL
 AS BEING FIRE RATED? DETAIL 18 OF
  
 18) SHEET A-5:
 18A) DETAIL# 1 INDICATE RATED WALLS BUT THERE ARE NO
 WALL TAG IDENTIFYING TYPE OF WALLS? 106.1.2* ADD INFO
 REQUIRED.
  
 18B) DETAIL# 1 ALSO LACKS DOOR IDENTIFICATION MARKERS,
 ADD INFO REQUIRED? 106.1.2*
  
 18C) DETAIL# 1 THE EXIT PASSAGEWAY BETWEEN THE WOMEN?S
 RESTROOM AND THE SALON IS MISSING IS MISSING A RATED
 WALL. WITH THE DOOR NOT MARKED, IT MAY ALSO BE MISSING
 A RATING?
  
 18D) THIS SAME EXITPASSAGEWAY THE DOOR LEADING FROM
 THE STORE IS MISSING THE 18? REQUIRED ON THE PULL SIDE.
 11-4.13.6 MANEUVERING CLEARENCES AT DOORS. MINIMUM
 MANEUVERING CLEARANCES AT DOORS THAT ARE NOT AUTOMATIC
 OR POWER-ASSISTED SHALL BE AS SHOWN IN FIG. 25. THE
 FLOOR OR GROUND AREA WITH IN THE REQUIRED CLEARANCES
 SHALL BE CLEAR & LEVEL.
  
 19) THE PLANS WERE NOT VERY EVIDENT WHERE THE DRESSING
 ROOMS WERE TO BE?
 11-4.35 DRESSING AND FITTING ROOMS.
  
 11-4.35.1 GENERAL.
 DRESSING AND FITTING ROOMS REQUIRED TO BE ACCESSIBLE BY
 SECTION 11-4.1 SHALL COMPLY WITH SECTION 11-4.35 AND
 SHALL BE ON AN ACCESSIBLE ROUTE.
  
 11-4.35.2 CLEAR FLOOR SPACE.
 A CLEAR FLOOR SPACE ALLOWING A PERSON USING A
 WHEELCHAIR TO MAKE A 180-DEGREE TURN SHALL BE PROVIDED
 IN EVERY ACCESSIBLE DRESSING ROOM ENTERED THROUGH A
 SWINGING OR SLIDING DOOR. NO DOOR SHALL SWING INTO ANY
 PART OF THE TURNING SPACE. TURNING SPACE SHALL NOT BE
 REQUIRED IN A PRIVATE DRESSING ROOM ENTERED THROUGH A
 CURTAINED OPENING AT LEAST 32 INCHES (815 MM) WIDE IF
 CLEAR FLOOR SPACE COMPLYING WITH SECTION 11-4.2 RENDERS
 THE DRESSING ROOM USABLE BY A PERSON USING A
 WHEELCHAIR.
  
 11-4.35.3 DOORS.
 ALL DOORS TO ACCESSIBLE DRESSING ROOMS SHALL BE IN
 COMPLIANCE WITH SECTION 11-4.13 .
  
 11-4.35.4 BENCH.
 EVERY ACCESSIBLE DRESSING ROOM SHALL HAVE A 24 INCHES
 BY 48 INCHES (610 MM BY 1219 MM) BENCH FIXED TO THE
 WALL ALONG THE LONGER DIMENSION. THE BENCH SHALL BE
 MOUNTED 17 INCHES TO 19 INCHES (430 MM TO 485 MM) ABOVE
 THE FINISH FLOOR. CLEAR FLOOR SPACE SHALL BE PROVIDED
 ALONGSIDE THE BENCH TO ALLOW A PERSON USING A
 WHEELCHAIR TO MAKE A PARALLEL TRANSFER ONTO THE BENCH.
 THE STRUCTURAL STRENGTH OF THE BENCH AND ATTACHMENTS
 SHALL COMPLY WITH SECTION 11-4.26.3 . WHERE INSTALLED
 IN CONJUNCTION WITH SHOWERS, SWIMMING POOLS, OR OTHER
 WET LOCATIONS, WATER SHALL NOT ACCUMULATE UPON THE
 SURFACE OF THE BENCH AND THE BENCH SHALL HAVE A
 SLIP-RESISTANT SURFACE.
  
 11-4.35.5 MIRROR.
 WHERE MIRRORS ARE PROVIDED IN DRESSING ROOMS OF THE
 SAME USE, THEN IN AN ACCESSIBLE DRESSING ROOM, A
 FULL-LENGTH MIRROR, MEASURING AT LEAST 18 INCHES WIDE
 BY 54 INCHES HIGH (460 MM BY 1370 MM), SHALL BE MOUNTED
 IN A POSITION AFFORDING A VIEW TO A PERSON ON THE BENCH
 AS WELL AS TO A PERSON IN A STANDING POSITION.
  
 20) SW1A PLEASE PROVIDE THE FOLLOWING INFORMATION:
 11-5.2 COUNTERS AND BARS.
 WHERE FOOD OR DRINK IS SERVED AT COUNTERS EXCEEDING 34
 INCHES (865 MM) IN HEIGHT FOR CONSUMPTION BY CUSTOMERS
 SEATED ON STOOLS OR STANDING AT THE COUNTER, A PORTION
 OF THE MAIN COUNTER WHICH IS 60 INCHES (1525 MM) IN
 LENGTH MINIMUM SHALL BE PROVIDED IN COMPLIANCE WITH
 SECTION 11-4.32 OR SERVICE SHALL BE AVAILABLE AT
 ACCESSIBLE TABLES WITHIN THE SAME AREA.
 11-5.5 FOOD SERVICE LINES.FOOD SERVICE LINES SHALL
 HAVE A MINIMUM CLEAR WIDTH OF 36 INCHES (915 MM), WITH
 A PREFERRED CLEAR WIDTH OF 42 INCHES (1065 MM) TO ALLOW
 PASSAGE AROUND A PERSON USING A WHEELCHAIR. TRAY SLIDES
 SHALL BE MOUNTED NO HIGHER THAN 34 INCHES (865 MM)
 ABOVE THE FLOOR (SEE FIGURE 53 ). IF SELF-SERVICE
 SHELVES ARE PROVIDED, AT LEAST 50 PERCENT OF EACH TYPE
 MUST BE WITHIN REACH RANGES SPECIFIED IN SECTIONS
 11-4.2.5 AND 11-4.2.6.
  
 11-5.6 TABLEWARE AND CONDIMENT AREAS.
 SELF-SERVICE SHELVES AND DISPENSING DEVICES FOR
 TABLEWARE, DISHWARE, CONDIMENTS, FOOD AND BEVERAGES
 SHALL BE INSTALLED TO COMPLY WITH SECTION 11-4.2 (SEE
 FIGURE 54 ).
  
 21) HAZARDOUS PRODUCT SUMMARY SHEET:
 A) PROPANE & OTHER LPG- 200 LBS, DOES THIS MEAN THERE
 WILL ONLY BE 10 20LB CYLINDERS OR
 LESS BECAUSE OF THE PROPANE TORCH AND CAMP STOVE
 EQUIPMENT AND THE MAPP GAS CYLINDERS? PLEASE PROVIDE AN
 ACCURATE ACCOUNTING OF QUANTITIES, PLACEMENT AND
 COMPLIANCE WITH TABLE 307.7.1. NOTE THE ALLOWANCE FOR
 INCREASES WITH FOOTNOTES D & E.
  
 B) PLEASE FOLLOW THE SAME OUTLINE ABOVE FOR ALL
 FLAMMABLE AND COMBUSTIBLE LIQUIDS.
 C) PLEASE PROVIDE THE MSDS SHEETS FOR THE PRODUCTS
 LISTED ON THE WALMART HAZARDOUS PRODUCTS.
 ONCE THIS INFORMATION IS OBTAINED WE WILL BE ABLE TO
 DETERMINE ALLOWABLE AMOUNTS OF PRODUCT WITHOUT BEING
 CONSIDERED A HAZARDOUS AREA.
  
 22) 1609.1.4 PROTECTION OF OPENINGS. IN WIND-BORNE
 DEBRIS REGIONS, EXTERIOR GLAZING THAT RECEIVES POSITIVE
 PRESSURE IN THE LOWER 60 FEET (18.3 M) IN BUILDINGS
 SHALL BE ASSUMED TO BE OPENINGS AND THE BALANCE OF
 GLAZED OPENINGS IN THE REST OF THE BUILDING SHALL BE
 ASSUMED TO BE ZERO UNLESS SUCH GLAZING THAT RECEIVES
 POSITIVE PRESSURE IS IMPACT RESISTANT OR PROTECTED WITH
 AN IMPACT RESISTANT COVERING MEETING THE REQUIREMENTS
 OF SSTD 12, ASTM E 1886 AND ASTM E 1996, OR MIAMI-DADE
 TAS 201, 202 AND 203 REFERENCED THEREIN AS FOLLOWS: 1.
 GLAZED OPENINGS LOCATED WITHIN 30 FEET (9.1 M) OF GRADE
 SHALL MEET THE REQUIREMENTS OF THE LARGE MISSILE TEST.
 2.GLAZED OPENINGS LOCATED MORE THAN 30 FEET (9.1
 M) ABOVE GRADE SHALL MEET THE PROVISIONS OF THE SMALL
 MISSILE TEST.
 FL BLD CODE 1609.1.4: COMPONENTS & CLADDING, PROVIDE 2
 COPIES(3 IF THRESHOLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS ,MISSING REPORTS ARE AS FOLLOWS:
 A) WINDOWS
 B) MULLIONS
 C) GLAZED DOORS SWING & AUTOMATIC BI-PASS
 D) EXTERIOR HOLLOW METAL DOORS, SINGLE & DOUBLE
 E) OVERHEAD, OR SECTION OR COIL DOORS
 F) EFIS SYSTEMS
 G) SKYLIGHT
 H) ROOF HATCH
 I) ROOF ASSEMBLIES, FLAT AS WELL AS ROOF TILE
 J) PRE-MANUFACTURED A/C STANDS
  
 23) PRODUCT APPROVALS SUBMITTED WITH PERMIT APPLICATION
 AFTER OCTOBER 1, 2003 ARE REQUIRED TO COMPLY WITH THE
 FLORIDA PRODUCT APPROVAL SYSTEM. FOR INFORMATION PLEASE
 SEE THE STATE WEBSITE AT WWW.FLORIDABUILDING.ORG.
 PRODUCTS WITH STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS THE PRODUCT
 IDENTITY NUMBER FROM THE STATE. IF THE PRODUCT DOES NOT
 HAVESTATEWIDE APPROVAL, SUBMIT AN APPLICATION FOR
 LOCAL PRODUCT APPROVAL OR SITE SPECIFIC FORM PER RULE
 9B-72.WWW.FLORIDABUILDING.ORG
  
 24) WPB ADMIN CODE 106.3* PRODUCT APPROVALS. THOSE
 PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 25) 1707.4.5.1 MULLIONS OCCURRING BETWEEN INDIVIDUAL
 WINDOW AND GLASS DOOR ASSEMBLIES. TESTING REPORTS ARE
 REQUIRED BY AN APPROVED TESTING LABORATORY OR BE
 ENGINEERED.
  
 26) 1707.4.5.2 MULLIONS SHALL BE DESIGNED TO TRANSFER
 THE DESIGN PRESSURE LOADS
 APPLIED BY THE WINDOW OR DOOR ASSEMBLIES TO THE ROUGH
 OPENING SUBSTRATE.
  
 27) THIS ROOF IS MISSING OR NOT INCOMPLIANCE WITH
 THE FOLLOW ITEMS:
 ___ CONTRACTOR DID NOT PROVIDE THE MEANROOF
 HEIGHT.
  
 ___ CONTRACTOR DID NOT INDICATE THE ROOF PITCH.
  
 _XX__ CONTRACTOR FAILED TO PROVIDE PRODUCT APPROVAL FOR
 THE TYPE OF ROOFING TO BE INSTALLED.
  
 _XX__ CONTRACTOR FAILED TO INDICATE WHICH SYSTEM TO BE
 USED.
  
 __XX_ THE SYSTEM PROVIDED HAS A LOW PRESSURE FOR ZONE
 _2&3__ .
  
 _XX__ THE SYSTEM PROVIDED STATESLIMITATION# 7,
 SHOULD THE FASTENERRESISTANCE BE LESS THAN THAT
 REQUIRED, AS DETERMINED BY THEBUILDING OFFICIAL, A
 REVISED FASTENER SPACING, PREPARED , SIGNED AND SEALED
 BY A FLORIDA REGISTERED PROFESSIONAL ENGINEER,
 REGISTEREDARCHITECT OR REGISTERED ROOF CONSULTANT MAY
 BE SUBMITTED.
  
 ___ THE SYSTEM PROVIDED INDICATES LIMITATION# 9, NO
 ENHANCED FASTENING ALLOWED.
  
 28)THE STRUCTURAL SHEETS FAILED TO IDENTIFY THE
 FOLLOWING:
 2004 FL. BLD CODE 1603.1.4 THEFOLLOWING INFORMATION
 RELATED TO WIND
 SHALL BE SHOWN ON THE CONSTRUCTION DRAWINGS,
 1)- BASIC WIND SPEED, MPH
 2)- WIND IMPORTANCE FACTOR, & BUILDING
 CATEGORY
 3)- WIND EXPOSURE
 4)- INTERNAL PRESSURE COEFFICIENT,
 5)- COMPONENTS & CLADDING, THE DESIGN
 WIND PRESSURES IN TERMS OF PSF.
  
 29)PLANS INDICATE THE USE OF ? ? FRT PLYWOOD, PLEASE
 PROVIDE TYPE OF FASTENER WILL BE USED IN TO THE METAL
 PAN DECKING? PROVIDE FREQUENCY OF FASTENING ALSO.
  
 30) SHEET A4.1 DETAIL 12 INDICATES A 8? PONDING ON THE
 ROOF, WHEREAS ROOFS WITH SCUPPER OVERFLOWS ARE TO HAVE
 A MAXIMUM OF 4? PONDING,1503.4.3 OVERFLOW SCUPPERS .
  
 WHEN OTHER MEANS OF DRAINAGE OF OVERFLOW WATER IS NOT
 PROVIDED, OVERFLOW SCUPPERS SHALL BE PLACED IN WALLS OR
 PARAPETS NOT LESS THAN 2 INCHES (51 MM) NOR MORE THAN 4
 INCHES (102 MM) ABOVE THE FINISHED ROOF COVERING AND
 SHALL BE LOCATED AS CLOSE AS PRACTICAL TO REQUIRED
 VERTICAL LEADERS OR DOWNSPOUTS OR WALL AND PARAPET
 SCUPPERS . AN OVERFLOW SCUPPER SHALL BE SIZED IN
 ACCORDANCE WITH THE FLORIDA BUILDING CODE, PLUMBING.
  
 31) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
 BUILDING PLAN REVIEW II
 JIM WITMER C. B. O.
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
  
 WALMART SUPERCENTER 4225 45TH ST.DOC