| Plan Review Notes For Permit 07050661 |
| Permit Number |
07050661 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2007-07-23 09:20:22 | DENIED 2ND TIME | | | REFERENCE: | | | ** FBC-2004 SECTIONS 424.2 OR R4101 SWIMMING POOLS. | | | ** FBC-2004 PLUMBING. | | | ** FBC-2004 CHAPTER 1, THE CITY OF | | | WEST PALM BEACH AMENDMENTS. | | | ** FLORIDA ADMINISTRATIVE CODE. | | | ** FLORIDA STATUTES. | | | | | | 1. RESPONSE IS NOTED ON THE BADU JET SWIM PUMP BUT THE | | | SYSTEM IS NOT CODE COMPLIANT PER THE FOLLOWING: A} | | | FBC-2004 SEC.424.2.6.6.4, OR FBCR-2004 SEC. | | | R4101.6.6.4 MINIMUM OF TWO SUCTION INLETS SHALL BE | | | PROVIDED FOR EACH PUMP. SEPARATED BY A MINIMUM OF 3 | | | FEET OR LOCATED ON TWO DIFFERENT PLANES.B} FBC-2004 | | | SEC 424.2.6.6, OR FBCR-2004 SEC R4101.6.6 ENTRAPMENT | | | PROTECTION FOR SUCTION INLETS. THE RESUBMITTED BADU | | | SYSTEM DOES NOT REFLECT THOSE REQUIREMENTS. (DETAIL | | | REQUIRED ON SHEET 4 OF 5 AND INDICATED ON 1 OF 5) | | | NOTE: THE SUBMITTED BADU SYSTEM MATERIAL FROM MET | | | LABORATORIES IS INDICATING THAT THE BADU JET SUCTION | | | COVER HAS BEEN TESTED AND ACCEPTED BY A RECOGNIZED | | | FACILITY AND COMPLIES WITH ANSI/ASME A112.19.8M BUT | | | THIS SYSTEM IS NOT FBC-2004 CODE COMPLIANT. | | | | | | END OF COMMENTS: | | | | | | REVIEW BY MIKE PERSON | | | PLUMBING PLANS EXAMINER | | | (561) 805-6730 | | | FAX (561) 805-6731 | | | E-MAIL= [email protected] |
|