2007-06-27 17:00:45BUILDING REVIEW CHECKLIST:
  
 *** PLEASE DON'T STAPLE PRODUCT APPROVALS TO PLANS ***
  
 1- AFTER DRAWINGS ARE REVISED BRING THEM TO PALM BEACH
 COUNTY (2300 N. JOG RD (561)233-5115)TO PAY IMPACT
 FEES. BRING BACK STAMPED PLANS AND COPY OF PAID
 RECEIPTS.
  
 2- PLANS CALL FOR HORIZONTAL ROLLER WINDOWS, WHILE
 PRODUCT APPROVAL SUBMITTED IS FOR SINGLE HUNG WINDOWS.
 REVISE AS REQUIRED AND MAKE SURE WINDOWS MEET THE
 EGRESS REQUIREMENTS OF R 310FLORIDA RESIDENTIAL CODE
 2004 WITH 2006 REVISIONS.
  
 3- SPECIFY SAFETY GLASS FOR WINDOW NEXT TO THE ENTRY
 DOOR AS REQUIRED BY SEC. R308.4 OF 2004 FLORIDA
 RESIDENTIAL CODE.
  
 4- PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC. 13-
 600 OF FBC 2004.
 ***NOTE: MAKE SUREREVISED FORM IS USED.
  
 5- PROVIDE SOIL TEST REPORT.
  
 6- PROVIDE DRAINAGE PLAN AS REQUIRED BY SEC. R401.3 OF
 2004 FLORIDA RESIDENTIAL CODE. AND, SHOW HOW THE WATER
 GETS DIVERTED AWAY FROM NEIGHBOR'S PROPERTY.
  
 7- PROVIDE CONCRETE SLABS JOINTS AS REQUIRED BY SEC.
 R506.2.4 OF 2004 FLORIDA RESIDENTIAL CODE. ***NOTE:
 REMEMBER THAT PROPERTY IS LOCATED ADJACENT TO THE TRAIN
 TRACKS.
  
 8- SPECIFY ALL DESIGN LIVE AND DEAD LOADS, INCLUDING
 THE ATTIC LIVE LOAD AS REQUIRED BY TABLE R301.5 OF 2004
 FLORIDA RESIDENTIAL CODE.
  
 9- SPECIFY BUILDING CONSTRUCTION TYPE AS REQUIRED BY
 SEC. 602.1 FBC 2004.
  
 10- SHEET 2/6:
 A) THREE ARE SOME HANDWRITTEN NOTES REGARDING WINDOW
 SILL. INFORMATION NEEDS TO BE REVISE ON ORIGINAL
 DRAWINGS. HANDWRITTEN REVISIONS ARE NOT ALLOWED.
 ***MAKE SURE ALL WINDOW SILL NOTES AND DETAILS ARE
 REVISED ACCORDINGLY TO AVOID CONFUSION AND
 DISCREPANCIES.
  
 B) WINDOW/DOOR BUCKS ARE NOT ALLOWED TO BE BEVELED.
 SEE SEC. R 613.6.2 OF FLORIDA RESIDENTIAL CODE FOR
 PROPER WAY OF INSTALLING THE BUCKS.
  
 C) BUCK DETAILS CALL FOR DOUBLE PT 1X2FURRING
 STRIPS, BUT DETAILS ONLY SHOW ONE. CLARIFY/REVISE AS
 REQUIRED.
  
 11- SHEET 4/6:
 A) TYPICAL WALL SECTION:
 * SPECIFY ROOF SHEATHING NAIL TYPE AND SIZE AS REQUIRED
 BY SEC. R803.2.3.1 OF 2004 FLORIDA RESIDENTIAL CODE. **
 SPECIFY FIREBLOCKING AS REQUIRED BY SEC. R602.1.2 OF
 2004 FLORIDA RESIDENTIAL CODE,INCLUDING AT
 INTERSECTION OF WALL WITH CEILING.
 *** FOOTING NEEDS TO BE 12" MIN. BELOW GRADE.IF
 FOOTING IS 16" DEEP AND IS SHOWN AS 8" ABOVE GRADE,
 THEN IT DOESN'T COMPLY WITH THIS SECTION. REVISE AS
 REQUIRED.
 **** TYPICAL WALL SECTION AND TRUSS O.H. CONNECTION
 DETAIL DON'T CORRESPOND TO EACH OTHER. REVISE AS
 REQUIRED.
  
 12- SHEET 5/6:
 A) SPECIFY BEAM AT PORCH AREA. SEC. 106.1.2 CITY
 AMENDMENTS TO FBC 2004.
  
 B) SPECIFY BUILDING CODE USED FOR THE DESIGN OF THE
 LOADS.
  
 C) THICKNESS OF ROOF SHEATHING DOESN'T MATCH
 INFORMATION ON TYP. WALLSECTION. REVISE AS REQUIRED.
  
 D) SEE SEC. R803.2.3.1 OF 2004 FLORIDA RESIDENTIAL
 CODE FOR MINIMUM SIZE AND TYPE OF NAIL TO BE USED.
 ALSO,FOR NAIL SPACING ACCORDING TO ROOF ZONE.THERE
 ARE NOT NAILING SPECIFICATIONS FOR ROOF ZONE 3.
  
 E) SPECIFY WHERE WASUSP CONNECTOR USFC53 TAKEN
 FROM. UNABLE TO FIND IT IN THE CURRENT CATALOG.SEC.
 106.1.2 CITY AMENDMENTS TO FBC 2004.
  
 13- PROVIDE PRODUCT APPROVAL AS REQUIRED BY DCA RULE
 9B-72 FOR:
 A)"OUTSWING"DOORS AS SHOWN ON PLANS. NOA
 02-0107.03 SUBMITTED IS FOR "INSWING" DOORS.
  
 B) HORIZONTAL ROLLING WINDOWS AS SHOWN ON PLANS?.
  
 C) WINDOW MULLIONS, IF USING SINGLE HUNG WINDOWS
 MULLED TOGETHER.
  
 D) ALL USP CONNECTORS SPECIFIED ON PLANS. PROVIDE
 ONLY THE FLORIDA PRODUCT APPROVAL COVER PAGE ALONG WITH
 THE CONNECTOR PAGE.
  
 14- DECLARED VALUATION IS TOO LOW.OWES $599.62 FOR
 UPDATED VALUATION AND RADON FEES.SEC. 108.3 CITY
 AMENDMENTS TO FBC 2004.
  
 15- STORM SHUTTERS:
 A) PROVIDE COMPLETE INSTALLATION SCHEDULE AND KEY
 PLAN.SEE ATTACHED SAMPLE.
  
 B) ON STORM SHUTTERS ENGINEERED DRAWINGS MARK
 SPECIFIC SHUTTERS MOUNTING CONDITIONS AND SPECIFIC
 ANCHOR TYPE AND SPACING TO BE USED. SEETHE ANCHOR
 SPACING SCHEDULE.
  
 C) PROVIDE CLEAR AND LEGIBLE DRAWINGS.
  