| 2007-06-27 17:00:45 | BUILDING REVIEW CHECKLIST: |
| | |
| | *** PLEASE DON'T STAPLE PRODUCT APPROVALS TO PLANS *** |
| | |
| | 1- AFTER DRAWINGS ARE REVISED BRING THEM TO PALM BEACH |
| | COUNTY (2300 N. JOG RD (561)233-5115)TO PAY IMPACT |
| | FEES. BRING BACK STAMPED PLANS AND COPY OF PAID |
| | RECEIPTS. |
| | |
| | 2- PLANS CALL FOR HORIZONTAL ROLLER WINDOWS, WHILE |
| | PRODUCT APPROVAL SUBMITTED IS FOR SINGLE HUNG WINDOWS. |
| | REVISE AS REQUIRED AND MAKE SURE WINDOWS MEET THE |
| | EGRESS REQUIREMENTS OF R 310FLORIDA RESIDENTIAL CODE |
| | 2004 WITH 2006 REVISIONS. |
| | |
| | 3- SPECIFY SAFETY GLASS FOR WINDOW NEXT TO THE ENTRY |
| | DOOR AS REQUIRED BY SEC. R308.4 OF 2004 FLORIDA |
| | RESIDENTIAL CODE. |
| | |
| | 4- PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC. 13- |
| | 600 OF FBC 2004. |
| | ***NOTE: MAKE SUREREVISED FORM IS USED. |
| | |
| | 5- PROVIDE SOIL TEST REPORT. |
| | |
| | 6- PROVIDE DRAINAGE PLAN AS REQUIRED BY SEC. R401.3 OF |
| | 2004 FLORIDA RESIDENTIAL CODE. AND, SHOW HOW THE WATER |
| | GETS DIVERTED AWAY FROM NEIGHBOR'S PROPERTY. |
| | |
| | 7- PROVIDE CONCRETE SLABS JOINTS AS REQUIRED BY SEC. |
| | R506.2.4 OF 2004 FLORIDA RESIDENTIAL CODE. ***NOTE: |
| | REMEMBER THAT PROPERTY IS LOCATED ADJACENT TO THE TRAIN |
| | TRACKS. |
| | |
| | 8- SPECIFY ALL DESIGN LIVE AND DEAD LOADS, INCLUDING |
| | THE ATTIC LIVE LOAD AS REQUIRED BY TABLE R301.5 OF 2004 |
| | FLORIDA RESIDENTIAL CODE. |
| | |
| | 9- SPECIFY BUILDING CONSTRUCTION TYPE AS REQUIRED BY |
| | SEC. 602.1 FBC 2004. |
| | |
| | 10- SHEET 2/6: |
| | A) THREE ARE SOME HANDWRITTEN NOTES REGARDING WINDOW |
| | SILL. INFORMATION NEEDS TO BE REVISE ON ORIGINAL |
| | DRAWINGS. HANDWRITTEN REVISIONS ARE NOT ALLOWED. |
| | ***MAKE SURE ALL WINDOW SILL NOTES AND DETAILS ARE |
| | REVISED ACCORDINGLY TO AVOID CONFUSION AND |
| | DISCREPANCIES. |
| | |
| | B) WINDOW/DOOR BUCKS ARE NOT ALLOWED TO BE BEVELED. |
| | SEE SEC. R 613.6.2 OF FLORIDA RESIDENTIAL CODE FOR |
| | PROPER WAY OF INSTALLING THE BUCKS. |
| | |
| | C) BUCK DETAILS CALL FOR DOUBLE PT 1X2FURRING |
| | STRIPS, BUT DETAILS ONLY SHOW ONE. CLARIFY/REVISE AS |
| | REQUIRED. |
| | |
| | 11- SHEET 4/6: |
| | A) TYPICAL WALL SECTION: |
| | * SPECIFY ROOF SHEATHING NAIL TYPE AND SIZE AS REQUIRED |
| | BY SEC. R803.2.3.1 OF 2004 FLORIDA RESIDENTIAL CODE. ** |
| | SPECIFY FIREBLOCKING AS REQUIRED BY SEC. R602.1.2 OF |
| | 2004 FLORIDA RESIDENTIAL CODE,INCLUDING AT |
| | INTERSECTION OF WALL WITH CEILING. |
| | *** FOOTING NEEDS TO BE 12" MIN. BELOW GRADE.IF |
| | FOOTING IS 16" DEEP AND IS SHOWN AS 8" ABOVE GRADE, |
| | THEN IT DOESN'T COMPLY WITH THIS SECTION. REVISE AS |
| | REQUIRED. |
| | **** TYPICAL WALL SECTION AND TRUSS O.H. CONNECTION |
| | DETAIL DON'T CORRESPOND TO EACH OTHER. REVISE AS |
| | REQUIRED. |
| | |
| | 12- SHEET 5/6: |
| | A) SPECIFY BEAM AT PORCH AREA. SEC. 106.1.2 CITY |
| | AMENDMENTS TO FBC 2004. |
| | |
| | B) SPECIFY BUILDING CODE USED FOR THE DESIGN OF THE |
| | LOADS. |
| | |
| | C) THICKNESS OF ROOF SHEATHING DOESN'T MATCH |
| | INFORMATION ON TYP. WALLSECTION. REVISE AS REQUIRED. |
| | |
| | D) SEE SEC. R803.2.3.1 OF 2004 FLORIDA RESIDENTIAL |
| | CODE FOR MINIMUM SIZE AND TYPE OF NAIL TO BE USED. |
| | ALSO,FOR NAIL SPACING ACCORDING TO ROOF ZONE.THERE |
| | ARE NOT NAILING SPECIFICATIONS FOR ROOF ZONE 3. |
| | |
| | E) SPECIFY WHERE WASUSP CONNECTOR USFC53 TAKEN |
| | FROM. UNABLE TO FIND IT IN THE CURRENT CATALOG.SEC. |
| | 106.1.2 CITY AMENDMENTS TO FBC 2004. |
| | |
| | 13- PROVIDE PRODUCT APPROVAL AS REQUIRED BY DCA RULE |
| | 9B-72 FOR: |
| | A)"OUTSWING"DOORS AS SHOWN ON PLANS. NOA |
| | 02-0107.03 SUBMITTED IS FOR "INSWING" DOORS. |
| | |
| | B) HORIZONTAL ROLLING WINDOWS AS SHOWN ON PLANS?. |
| | |
| | C) WINDOW MULLIONS, IF USING SINGLE HUNG WINDOWS |
| | MULLED TOGETHER. |
| | |
| | D) ALL USP CONNECTORS SPECIFIED ON PLANS. PROVIDE |
| | ONLY THE FLORIDA PRODUCT APPROVAL COVER PAGE ALONG WITH |
| | THE CONNECTOR PAGE. |
| | |
| | 14- DECLARED VALUATION IS TOO LOW.OWES $599.62 FOR |
| | UPDATED VALUATION AND RADON FEES.SEC. 108.3 CITY |
| | AMENDMENTS TO FBC 2004. |
| | |
| | 15- STORM SHUTTERS: |
| | A) PROVIDE COMPLETE INSTALLATION SCHEDULE AND KEY |
| | PLAN.SEE ATTACHED SAMPLE. |
| | |
| | B) ON STORM SHUTTERS ENGINEERED DRAWINGS MARK |
| | SPECIFIC SHUTTERS MOUNTING CONDITIONS AND SPECIFIC |
| | ANCHOR TYPE AND SPACING TO BE USED. SEETHE ANCHOR |
| | SPACING SCHEDULE. |
| | |
| | C) PROVIDE CLEAR AND LEGIBLE DRAWINGS. |
| | |
| | JULIO GOMEZ |
| | BUILDING PLANS EXAMINER |
| | (561)805-6712 |